The text of a manual · part 9 of 13
FX Series Programmable Controllers Hardware Manual, pages 81 to 90
Pages 81 to 90 of 121
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Mitsubishi FX-8EYS
Page 81
FX Series Programmable Controllers
Outputs
6
6.3 ENG
Triac output example
FRE
Exemple d’un câblage de sortie triac
GER
Beispiel einer TriacAusgangsbeschaltung
ITL
Esempio del cablaggio di uscita di un triac
ESP
Ejemplo de una conexión de salida Triac
Figure: 6.4
ENG FRE GER ITL ESP
☞ Typical wiring ☞ Exemple de câblage ☞ Verdrahtungsbeispiel ☞ Esempio di cablaggio ☞ Ejemplo de cableado
Y0
Y0
Y1
Y1
Y2
Y2 com1
Y0
Y1
MC2
2
5
6
Y2
Y3
Y5
2 M C 1
M C 2
3
7
4
5
7
Y4
MC1
2
1 com2
1
Figure: 6.5
FX - 16EYS- ES-TB / FX2C
24 + 24 -
2
1
3
0
2 com1 com1 4
7
4
5
7 6 com2 com2
2
2
1
5 1 6
7 3
Table: 6.5 Item check
Description
Beschreibung
Descrizione
Descripción ESP
ITL
REF
ENG
A
AC power supply
Tension CA
AC-Spannung
Tensione AC
Tensión CA
B
Fuse
Fusible
Sicherung
Fusibile
Fusible
C
Solenoid valve
Electrovanne
Magnetventil
Elettrovalvola
Válvula electromagnética
D
Incandesent lamp
Lampe à incandescence
Glühlampe
Lampada a incandescenza
Bombilla
E
Neon lamp
Lampe fluorescente
Leuchtstofflampe
F
Contactor
Contacteur
Schütz
Relè di potenza
Contactor
G
Noise suppressor 0.1µF capacitor + 100 - 120 Ω resistor
Filtre antibruit: condensateur 0,1 µF + résistance 100 - 120 Ω
Rauschfilter: Kondensator 0,1 µF + Widerstand 100 120 Ω
Filtro antidisturbo: condensatore 0,1 µF + resistore 100 - 120Ω
Filtro de ruido: Condensador 0,1 µF + resistencia 100-120 Ω
GER
FRE
Lampada fluorescente Lámpara fluorescente
6-8
Page 82
FX Series Programmable Controllers
Outputs
6
6.4 ENG
Transistor output specification
FRE
GER
Technische Daten der Transistor-Ausgänge
ITL
Caractéristiques techniques des sorties des transistors
Dati tecnici delle uscite a transistor
Datos técnicos de las salidas transistorizadas Table: 6.6 ESP
FX/FX2C transistor specification
Caractéristiques des transistor FX/FX2C
Kenndaten der Transistor FX/FX2C
Parametri dei transistor FX/FX2C
Características de los transistor FX/FX2C
FX / FX2C Y0 ➩ ∞ ENG
Switched voltages (resistive load)
Rated current / N points (resistive load)
FRE
Tensions de démarrage (risistance ohmique)
Intensité nominale /N bornes (risistance ohmique)
GER
Einschaltspannungen (wirkwiderstand als verbraucher)
Nennstrom / N Klemmen (wirkwiderstand als verbraucher)
ITL
Tensioni di accensione (resistenza ohmica come consumatore)
Corrente nominale / N moresetti (resistenza ohmica come consumatore)
Tensiones de conexión (resistencia efectiva de consumo)
Corrente nominal / N bornas (resistencia efectiva de consumo)
Max. Inductive load
Max. lamp load (tungsten load)
ESP ENG FRE GER ITL ESP
Charge inductive max. max. induktive Last Carico max. Induttivo Carga inductiva máx
5 - 30V DC
FX 0.5A / 24V DC Charge d’allumage max. (tungsthne) (12W) max. Lampenlast FX2C (wolfram) 0.0125A/ 24V Carico max. lampade DC (volframio) (0.3W) Carga de lámpara máx. (tungsteno)
FX 0.5A / 1 point. 0.8A / common FX2C 0.1A / 1 point
FX 0.0625A / 24V DC (1.5W) FX2C 0.0125A / 24V DC (0.3W)
ENG
Response time (approx)(see note 6.4.1)
FRE
Temps de réponse (env.)(voir 6.4.1)
GER
Ansprechzeit (ca.)(siehe 6.4.1)
ITL
Tempo di reazione (circa)(v. 6.4.1)
ESP
Tiempo de reacción (aprox.)(ver 6.4.1)
ENG
Open circuit current leakage
Circuit isolation by photocoupler
FRE
Courant de fuite
Isolement du circuit
Par optocoupleur
Schaltkreisisolation
über Optokoppler
Corrente di dispersione
Isolamento circuiti tramite optoaccoppiatori
Corriente de fuga
Aislamiento de circuitode conmutación a través de optoacoplador
ENG
Operation indication
LED is lit when photocoupler is driven
FRE
Affichage de service
La LED s’allume lorsque l’optocoupleur est excitée.
GER
Betriebsanzeige
Die LED leuchtet, wenn Optokoppler aktiviert.
ITL
Indicazione di funzionamento
Il LED si accende quan l’optoaccop è eccitata.
Indicador de funcionamiento
El LED se enciende cuando está activado el optoacoplador
GER ITL ESP
ESP
Leckstrom
0.1mA / 30V DC
OFF é ON < 0.2 msec (FX = 200mA /24V DC FX2C = 100mA / 24V DC) ON é OFF < 0.2 msec (FX = 200mA /24V DC FX2C = 100mA / 24V DC)
6-9
Page 83
FX Series Programmable Controllers
6.4.1 ENG
FRE
GER
ITL
ESP
Outputs
6
Response times OFF times increase as the load current decreases. For improved response times use a ’dummy’ resistor, see Figure 6.6. If a response time of 0.5 msec or better is required when using ’light loads’ use a ’dummy’ resistor and ensure the signal line has a current greater than 60mA/24V DC. Temps de réponse Le temps de mise hors circuit augmente au fur et à mesure que le courant de charge augmente. Il est possible d’améliorer le pouvoir de réaction en ajoutant une réactance (voir illustration). Si un temps de réponse de 0.5 ms maximum est souhaité, il faut s’assurer qu’un courant de charge de 60 mA minimum avec 24 V CC soit disponible.
Ansprechzeiten Die Ausschaltzeit steigt bei abnehmenden Laststrom. Das Ansprechvermögen kann durch einen zusätzlichen Blindwiderstand verbessert werden (siehe Abb.). Falls eine Ansprechzeit von höchstens 0.5 ms gewünscht wird, muß sichergestellt werden, daß ein Laststrom vom mind. 60 mA bei DC 24 V ansteht.
Tempi di reazione Il tempo di spegnimento aumenta man mano che aumenta la corrente del carico. La capacità di reazione può essere migliorata mediante un’ulteriore reattanza efficace (v. figura). Se si desidera un tempo di reazione di max. 0.5 ms, si deve garantire una corrente di carico di almeno 60 mA a 24 V DC.
Tiempos de reacción El tiempo de desconexión aumenta a medida que aumenta la corriente de carga. La capacidad de reacción se puede optimizar mediante una reactancia inductiva adicional (ver la figura). En caso de que se desee un tiempo de reacción de 0.5 ms como máximo, se tiene que asegurar, que esté aplicada una tensión de carga de mín. 60 mA con 24 V CC.
Figure: 6.6
60 to 200mA +V
ENG FRE GER ITL ESP
☞ Dummy load ☞ Réactance ☞ Blindwiderstand ☞ Reattanza efficace ☞ Reactancia inductiva
5 to 30V
Y
ENG FRE GER ITL ESP
☞ Dummy load ☞ Réactance (charge fictive) ☞ Blindwiderstand ☞ Reattanza efficace ☞ Reactancia inductiva
Load Charge Last Carico Carga
6 - 10
Page 84
FX Series Programmable Controllers
Outputs
6.5 ENG
Transistor output example
FRE
Exemple d’un câblage de sortie de transistor
GER
Beispiel einer TransistorAusgangsbeschaltung
ITL
Esempio del cablaggio di uscita di un transistor
ESP
Ejemplo de una conexión de salida transistorizada
FX -✰✰MT-ESS, FX-✰✰ET-ESS, (Source)
Figure: 6.7
4 +V0
Y0
+V1
Y1
+V2
Y2
+V1
Y0
Y1
Y2
Y3
+V2
Y4
Y5 com2
Y4
Y5
3 MC2
2
2
MC1
M C 1
1 1
2 M C 2
FX -✰✰MT, FX-✰✰ET (Sink)Japanese spec.
Figure: 6.8
4 com0
Y0 com1
Y1 com2
Y2 com1
Y0
Y1
Y2
Y3
3 2
2
MC2
1 1
2
MC1
M C 1
M C 2
Table 6.7 Item check REF
ENG
Description
FRE
Beschreibung
GER
Descrizione
ITL
Descripción
ESP
A
DC power supply
Alimentation en tension CC
DC-Spannungsversorgung
Tensione di alimentazione DC
Alimentación de tensión CC
B
Fuse
Fusible
Sicherung
Fusibile
Fusible
C
External, mechanical inter-lock
Verrouillage mécanique extérieur externe mechanische Verriegelung
Bloccaggio meccanico esterno
Bloqueo mecánico externo
D
Internal noise suppressor
Filtre antibruit intérieur
Interner Rausch-Filter
Filtro antidisturbo interno
Filtro de ruido interno
6 - 11
6
Page 85
FX Series Programmable Controllers Figure: 6.9
Outputs
FX- 16EYT-ESS-TB / FX2C (Source )
4 24 + 24 -
1 0
3 2 com1 com1
5 4
2
2
1
7
MC2 M C 1
3
Figure: 6.10 com2
6 com2
MC1
2
M C 2
1
FX - 16EYT- TB / FX2C, (Sink) Japanese spec. 4 24 + 24 -
2 1
1 0
3 2 com1 com1
5 4
2
7 com2
6
MC2 M C 1
3 com2
MC1
2
M C 2
1
6 - 12
6
Page 86
FX Series Programmable Controllers
6.6 ENG
FRE
Outputs
6
Applying safe loads Ensure all loads are applied to the same side of each PC output, see previous figures. Loads which should NEVER simultaneously operate (e.g. direction control of a motor), because of a safety critical situation, should not rely on the PC’s sequencing alone. Mechanical interlocks MUST be fitted to all safety critical circuits. see Figure 6.7 Prescriptions de sécurité pour la mise en circuit de charges Assurez-vous que toutes les charges d’une application sont en circuit dans un trajet du courant d’un API. Les charges qui ne doivent JAMAIS être mises en circuit simultanément (par ex. commande directe d’un moteur), ne doivent pas être verrouillées mutuellement par l’intermédiaire du seul programme de l’API en raison de la situation de danger particulière. Un verrouillage mécanique supplémentaire est en tout cas nécessaire (voir illustrations précédentes).
GER
Sicherheitshinweise zur Beschaltung von Lasten Stellen Sie sicher, daß alle Lasten einer Anwendung im Strompfad einer SPS geschaltet werden. Lasten, die NIEMALS gleichzeitig eingeschaltet sein dürfen (z. B. direkte Steuerung eines Motors), sollten aufgrund der besonderen Gefahrensituation nicht allein über das SPS-Programm gegenseitig verriegelt werden. Es ist auf jeden Fall eine zusätzliche mechanische Verriegelung erforderlich (siehe vorherige Abbildungen).
ITL
Avvertenze per la sicurezza nel cablaggio di carichi Accertatevi che tutti i carichi di un’applicazione vengano comandati nella catena di un PC. I carichi che non devono MAI essere attivati insieme (ad es. comando diretto di un motore), non dovrebbero essere interbloccati soltanto tramite programma PC a causa della particolare situazione di pericolo. Occorre in ogni caso un interbloccaggio meccanico supplementare (v. figure precedenti).
ESP
Instrucciones de seguridad para la conexión de cargas Asegurar que todas las cargas de una aplicación sean conectadas en el circuito amperimétrico de una PC. Las cargas, que NUNCA deben estar conectadas simultáneamente (p.ej. mando directo de un motor), no deberán ser bloqueadas recíprocamente sólo a través del programa PC debido a causa de una situación crítica de peligro. Para ello se requiere siempre un bloqueo mecánico adicional (ver las figuras anteriores).
6 - 13
Page 87
FX Series Programmable Controllers Outputs 6
MEMO a’a MITSUBISHI 6-14
Page 88
FX Series Programmable Controllers
1 2 3
Diagnostics
ENG
FRE
GER
ITL
ESP
Introduction
Introduction
Einleitung
Introduzione
Introducción
Occupation des bornes
Klemmenbelegungen
Assegnazione dei morsetti
Ocupaciones de bornas
Installation
Installation
Installazione
Instalación
Terminal Layouts
Installation Notes
4
Power supply
Alimentation en tension
Spannungsversorgung
Alimentazione della tensione
Alimentación de tensión
5
Inputs
Entrées
Eingänge
Ingressi
Entradas
6
Outputs
Sorties
Ausgänge
Uscite
Salidas
7
Diagnostics
Diagnostic d’erreurs
Fehlerdiagnose
Diagnostica
Diagnóstico de fallos y errores
8
Index
Index
Stichwortverzeichnis
Indice analitico
Indice alfabético
7-1
Page 89
FX Series Programmable Controllers Diagnostics sa MITSUBISHI
Page 90
Diagnostics
FX Series Programmable Controllers
7
7.1 ENG
Preliminary checks
FRE
Vérifications à effectuer avant la mise en service
GER
Überprüfungen vor Betrieb
ITL
Controlli prima del funzionamento
ESP
Verificaciones preliminares
Table: 7.1 REF POWER RUN BATT.V PROG-E CPU-E
POWER RUN BATT.V PROG-E CPU-E
POWER RUN BATT.V PROG-E CPU-E
Check list
Points de contrôle
Prüfpunkte
Punti da controllare
Puntos de verificación
ENG
FRE
GER
ITL
ESP
Check power supply, ground and I/O cables are wired correctly. Check all terminal screws are tight.
A vérifier: l’alimentation en tension; le câblage de la terre et les câbles E/S; les bornes à vis
Überprüfen: Spannungsversorgung; Verdrahtung der Erdung und E-/A-Kabel; Schraubklemmen
Controllare: tensione di alimentazione; cablaggio della messa a terra e cavo I/O; morsetti a vite
Verificación: Alimentación de tensión; cableado de la puesta a tierra y cables de entrada/salida; bornas roscadas
Turn the power supply on. Check the power LED is lit. Down load a small test program into the PC using a handheld programmer or MEDOC. Verify the program to ensure it has been written to the PC correctly. Using the programming device forcibly turn ON/OFF each output. Check the output LEDS for operation.
Mettre en circuit l’alimentation en tension. Vérifier si la LED POWER s’allume. Transmettre le programme de test simple de l’appareil de programmation à l’API. Vérifier si le programme a bien été transmis à la mémoire de l’API. Mettre en horscircuit chaque sortie à l’aide de l’appareil de programmation. Vérifier les LED des sorties.
Spannungsversorgung einschalten. Überprüfen, ob die POWER-LED leuchtet. Einfaches Testpogramm vom Programmiergerät zur SPS übertragen. Überprüfen, ob das Programm richtig in den SPS-Speicher übertragen wurde. Mit Hilfe des Programmiergerätes jeden Ausgang EIN/AUS schalten. LEDs der Ausgänge überprüfen.
Attivare la tensione di alimentazione. Controllare se è acceso il LED POWER. Trasferire il programma di test semplice dal dispositivo di programmazione al PC. Controllare se il programma è stato trasmesso correttamente alla memoria del PC. Attivare/disattivare ogni uscita con il dispositivo di programmazione. Controllare i LED delle uscite.
Conectar la alimentación de corriente. Verificar, si se enciende el diodo POWERLED. Transferir el programa de prueba simple de la unidad de programación a la unidad PC. Verificar, si el programa ha sido transferido correctamente a la memoria de la unidad PC. Con ayuda de la unidad de programación, realizar una Conexion /Desconexion de cada salida. Comprobar los LED de las salidas.
Put the PC into RUN. Check the RUN LED is lit. Check the previously down loaded program works correctly. Once all checks are complete take the PC out of run and turn OFF the power supply.
Commuter l’API dans le mode RUN. Vérifier la LED RUN. Vérifier si le programme transmis auparavant fonctionne correctement. A l’issue des vérifications, couper le mode RUN et la tension.
SPS in den RUNModus schalten. RUN-LED überprüfen. Überprüfen, ob das vorher übertragene Programm korrekt arbeitet. Nach Abschluß der Überprüfungen RUN-Modus und Spannung auschalten.
Attivare la modalità RUN nel PC. Controllare il LED RUN. Controllare se il programma precedentemente trasmesso funziona correttamente. Al termine dei controlli disattivare la modalità RUN e disinserire la tensione.
Conmutar la unidad PC al modo RUN. Comprobar el diodo LED de RUN. Verificar, si el programa anteriormente transferido trabaja correctamente. Una vez terminadas las pruebas de verificación y comprobación, desconectar el modo RUN y la tensión.
During this testing stage take extrem care not to touch any live or hazardous parts.
Veillez à ne pas toucher de pièces sous tension pendant les vérifications.
Achten Sie darauf, daß Sie während der Überprüfungen keine unter Spannung stehenden Teile berühren.
Fate attenzione a non toccare durante i controlli parti che si trovano sotto tensione.
Durante las pruebas de verificación se tiene que observar, que no se toque ninguna de las piezas que se encuentran bajo tensión.
7-3