The text of a manual · part 11 of 20
I/O Module Type Building Block User's Manual: 3. OUTPUT MODULE SPECIFICATIONS, pages 77 to 86
Pages 77 to 86 of 158, from I/O Module Type Building Block User's Manual
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi QG60 and Mitsubishi QX42
Page 77
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3. OUTPUT MODULE SPECIFICATIONS 3.1 QY10 Contact Output Module Type Specifications Number of output points Isolation method Rated switching voltage, current Minimum switching load Maximum switching load OFF to ON Response time ON to OFF Mechanical
Life
Electrical
Maximum switching frequency Surge suppressor Fuse Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
Contact output module QY10 16 points Relay 24VDC 2A (resistive load) /point, 8A/common 240VAC 2A (cos =1) 5VDC 1mA 264VAC 125VDC 10ms or less 12ms or less 20 million times or more Rated switching voltage/current load 100 thousand times or more 200VAC 1.5A, 240VAC 1A (COS =0.7) 100 thousand times or more 200VAC 0.4A, 240VAC 0.3A (COS =0.7) 300 thousand times or more 200VAC 1A, 240VAC 0.5A (COS =0.35) 100 thousand times or more 200VAC 0.3A, 240VAC 0.15A (COS =0.35) 300 thousand times or more 24VDC 1A, 100VDC 0.1A (L/R=7ms) 100 thousand times or more 24VDC 0.3A, 100VDC 0.03A (L/R=7ms) 300 thousand times or more 3600 times/hour No No 2830VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point output module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)
External connection
3-1
Appearance
QY10 0 1 2 3 4 5 6 7 8 9 A B CDE F
3 0
L L
1 2
L L
3 4
L L
5 6
L L
7 8
L L
9 A
L L
B C
L L
D E
L L
F COM
NC 24VDC 240VAC 2A
0 1 2 3 4 5 6 7 8 9 A B C D E F
430mA (TYP. all points ON) 0.22kg Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y08 Y09 Y0A Y0B Y0C Y0D Y0E Y0F COM Vacant
3-1
Page 78
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.2 QY10-TS Contact Output Module This module is a spring clamp terminal block type and an output module that has indicators for checking the insertion state of wire. Type Specifications
3
Number of output points Isolation method Rated switching voltage, current Minimum switching load Maximum switching load OFF to ON Response time ON to OFF Mechanical
Life
Electrical
Maximum switching frequency Surge suppressor Fuse Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
Contact output module QY10-TS 16 points Relay 24VDC 2A (resistive load) /point, 8A/common 240VAC 2A (cos =1) 5VDC 1mA 264VAC 125VDC 10ms or less 12ms or less 20 million times or more Rated switching voltage/current load 100 thousand times or more 200VAC 1.5A, 240VAC 1A (COS =0.7) 100 thousand times or more 200VAC 0.4A, 240VAC 0.3A (COS =0.7) 300 thousand times or more 200VAC 1A, 240VAC 0.5A (COS =0.35) 100 thousand times or more 200VAC 0.3A, 240VAC 0.15A (COS =0.35) 300 thousand times or more 24VDC 1A, 100VDC 0.1A (L/R=7ms) 100 thousand times or more 24VDC 0.3A, 100VDC 0.03A (L/R=7ms) 300 thousand times or more 3600 times/hour No No 2830VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point output module.)
QY10-TS 01234567 8 9 ABCDEF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ON indication (LED) Two-piece spring clamp terminal block 0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1 430mA (TYP. all points ON) 0.22kg External connection
3-2
Appearance
Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y08 Y09 Y0A Y0B Y0C Y0D Y0E Y0F COM Vacant
3-2
Page 79
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.3 QY18A Contact Output Module (All Points Independent) Type Specifications Number of output points Isolation method Rated switching voltage/current Minimum switching load Maximum switching load OFF to ON Response time ON to OFF Mechanical
Life
Electrical
Maximum switching frequency Surge suppressor Fuse Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
Contact output module (All points independent) QY18A 8 points Relay isolation 24VDC 2A (resistive load) /point, 8A/unit 240VAC 2A (cos =1) 5VDC 1mA 264VAC 125VDC 10ms or shorter 12ms or shorter 20 million cycles or more Rated switching voltage/current load 100 thousand cycles or more 200VAC 1.5A, 240VAC 1A (COS =0.7) 100 thousand cycles or more 200VAC 0.4A, 240VAC 0.3A (COS =0.7) 300 thousand cycles or more 200VAC 1A, 240VAC 0.5A (COS =0.35) 100 thousand cycles or more 200VAC 0.3A, 240VAC 0.15A (COS =0.35) 300 thousand cycles or more 24VDC 1A, 100VDC 0.1A (L/R=7ms) 100 thousand cycles or more 24VDC 0.3A, 100VDC 0.03A (L/R=7ms) 300 thousand cycles or more 3600 cycles/hour
QY18A 0 1 2 3 4 5 6 7 8 9 A B CDE F
L
L
L
L
None None 2830VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 16 points (I/O assignment is set as a 16-point output module.) ON indication (LED) 18-point terminal block (M3 6 screws) Core cable 0.3 to 0.75mm2 (Outside diameter 2.8mm or smaller)
L
L
L
L
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
1
2
3
4
5
6
7
NC NC 24VDC 240VAC 2A
R1.25-3 (Sleeved crimping terminals cannot be used.) 240mA (TYP. all points ON) 0.22kg External connection
3-3
Appearance
Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Vacant Vacant
3-3
Page 80
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.4 QY22 TRIAC Output Module Type
TRIAC output module
Specifications
QY22
Number of output points
Appearance
16 points
Isolation method
Photocoupler
Rated load voltage
100 to 240VAC 50/60Hz
Load voltage distortion rate
5%
Within 5%
Maximum load voltage
264VAC
Maximum load current
0.6A/point, 4.8A/common
Minimum load voltage/current
24VAC 100mA, 100VAC 25mA, 240VAC 25mA
Maximum rush current
20A/cycle or less
Leakage current at OFF
3mA or lower (for 240V, 60Hz), 1.5mA or lower (for 120V, 60Hz)
Maximum voltage drop at ON Response time
QY22 0 1 2 3 4 5 6 7 8 9 A B CDE F
1.5V or lower 1ms + 0.5 cycles or less
ON to OFF
1ms + 0.5 cycles or less (rated load, resistance load)
Surge suppressor
L
L
Fuse
None (Attaching a fuse to each external wiring is recommended. Refer to Section 1.2)
L
Dielectric withstand voltage
2830VAC rms/3 cycles (altitude 2000m)
L
Insulation resistance
10MΩ or higher by insulation resistance meter
L
Noise immunity
By noise simulator of 1.5kVp-p noise voltage, s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV
Protection degree
IP1X
Common terminal arrangement
16 points/common (common terminal: TB17)
Number of occupied I/O points
16 points (I/O assignment is set as a 16-point output module.)
Operation indicator
ON indication (LED)
External connections Applicable wire size
18-point terminal block (M3 6 screws) Core cable 0.3 to 0.75mm2 (Outside diameter 2.8mm or smaller)
Applicable crimping terminal
R1.25-3 (Sleeved crimping terminals cannot be used.) 250mA (Max., all points ON)
Weight
0.40kg
3-4
2
L
3 4 5 6
L
L
7 8 9 A
L L
B C
L L
D E
L
Internal current consumption (5VDC)
External connection
1
L
CR absorber
1
0
L
OFF to ON
Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
L
F
COM
100VAC 240VAC 0.6A
0 1 2 3 4 5 6 7 8 9 A B C D E F
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y08 Y09 Y0A Y0B Y0C Y0D Y0E Y0F COM Vacant
3-4
Page 81
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
POINT Do not touch the module during turning on electricity and immediately after power supply interception. There is fear of a burn.
3-5
3-5
Page 82
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.5 QY40P Transistor Output Module (Sink Type) Type
Transistor output module (Sink type)
Number of output points Isolation method Rated load voltage Maximum load current Maximum inrush current Leakage current at OFF Maximum voltage drop at ON OFF to ON Response time ON to OFF Surge suppressor Fuse Voltage External supply power Current Dielectric withstand voltage Insulation resistance
16 points Photocoupler 12-24VDC (+20/-15%) 0.1A/point, 1.6A/common 0.7A, 10ms or less 0.1mA or less 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A 1ms or less 1ms or less (rated load, resistive load) Zener diode No 12-24VDC (+20/-15%) (ripple ratio within 5%) MAX. 10mA (when 24VDC and all points are ON) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB18) 16 points (I/O assignment is set as a 16-point output module.) Yes (overload protection function, overheat protection function) • Overheat protection function is activated in increments of 1 point. • Overload protection function is activated in increments of 1 point. ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 65mA (TYP. all points ON) (0.07A is shown on the rating plate of the module.) 0.16kg
Specifications
QY40P
Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Protection function Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
External connection
3-6
Appearance
Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
QY40P 0 1 2 3 4 5 6 7 8 9 A B CDE F
0
L L
1 2
L L
3 4
L L
5 6
L L
7 8
L L
9 A
L L
B C
L L
D E
L L
F
COM
12VDC 24VDC 0.1A
0 1 2 3 4 5 6 7 8 9 A B C D E F
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y08 Y09 Y0A Y0B Y0C Y0D Y0E Y0F 12/24VDC COM
3-6
Page 83
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.6 QY40P-TS Transistor Output Module (Sink Type) This module is a spring clamp terminal block type and an output module that has indicators for checking the insertion state of wire. Type
Transistor output module (Sink type)
Specifications
QY40P-TS
Number of output points Isolation method Rated load voltage Maximum load current Maximum inrush current Leakage current at OFF Maximum voltage drop at ON OFF to ON Response time ON to OFF Surge suppressor Fuse Voltage External supply power Current Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Protection function Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
QY40P-TS 0123 4567 8 9 AB CDEF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Refer to section 9.1 65mA (TYP. all points ON) (0.07A is shown on the rating plate of the module.) 0.16kg
External connection
3-7
Appearance
16 points Photocoupler 12-24VDC (+20/-15%) 0.1A/point, 1.6A/common 0.7A, 10ms or less 0.1mA or less 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A 1ms or less 1ms or less (rated load, resistive load) Zener diode No 12-24VDC (+20/-15%) (ripple ratio within 5%) MAX. 10mA (when 24VDC and all points are ON) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB18) 16 points (I/O assignment is set as a 16-point output module.) Yes (overload protection function, overheat protection function) • Overheat protection function is activated in increments of 1 point. • Overload protection function is activated in increments of 1 point. ON indication (LED) Two-piece spring clamp terminal block 0.3 to 2.0mm2 core (22 to 15 AWG)
Terminal block No. TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18
Signal name Y00 Y01 Y02 Y03 Y04 Y05 Y06 Y07 Y08 Y09 Y0A Y0B Y0C Y0D Y0E Y0F 12/24VDC COM
3-7
Page 84
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.7 QY41H Transistor High-speed Output Module (Sink Type) Type Specifications Number of output points Isolation method Rated load voltage Maximum load current Maximum inrush current Leakage current at OFF Maximum voltage drop at ON OFF to ON Response time ON to OFF Surge suppressor Fuse Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
Transistor high-speed output module (Sink type) QY41H 32 points Photocoupler 5-24VDC (+20/-15%) 0.2A/point, 2A/common 0.7A, 10ms or less 0.1mA or less 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A 2 s or less 2 s or less (rated load, resistive load) Zener diode None (Attaching a fuse to external wiring is recommended.) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: A01, A02) 32 points (I/O assignment is set as a 32-point output module.) ON indication (LED) 40-pin connector
Appearance
0.088 to 0.3mm2 (For A6CON1 or A6CON4) 1 A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54 370mA (TYP. all points ON) 0.10kg External connection
Pin-Outs
LED B20
Load
Internal circuit LED A05
Load
A01,A02 5/24VDC
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Pin No.
Signal No.
Pin No.
Signal No.
B20 B19
Y00 Y01
A20 A19
Y10 Y11
B18 B17
Y02 Y03
A18 A17
Y12 Y13
B16 B15
Y04 Y05
A16 A15
Y14 Y15
B14 B13
Y06 Y07
A14 A13
Y16 Y17
B12 B11
Y08 Y09
A12 A11
Y18 Y19
B10 B09
Y0A Y0B
A10 A09
Y1A Y1B
B08 B07
Y0C Y0D
A08 A07
Y1C Y1D
B06 B05
Y0E Y0F
A06 A05
Y1E Y1F
B04 Vacant A04 Vacant B03 Vacant A03 Vacant B02 Vacant A02 B01 Vacant A01
1: When using A6CON2 or A6CON3, refer to Chapter 7.
3-8
3-8
COM COM
Page 85
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.8 QY41P Transistor Output Module (Sink Type) Type Specifications Number of output points Isolation method Rated load voltage Maximum load current Maximum inrush current Leakage current at OFF Maximum voltage drop at ON OFF to ON Response time ON to OFF Surge suppressor Fuse Voltage External supply power Current Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Protection function Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
Transistor output module (Sink type) QY41P 32 points Photocoupler 12-24VDC (+20/-15%) 0.1A/point, 2A/common 0.7A, 10ms or less 0.1mA or less 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A 1ms or less 1ms or less (rated load, resistive load) Zener diode No 12-24VDC (+20/-15%) (ripple ratio within 5%) 20mA (at 24VDC) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: A01, A02) 32 points (I/O assignment is set as a 32-point output module.) Yes (overheat protection function, overload protection function) • Overheat protection function is activated in increments of 1 point. • Overload protection function is activated in increments of 1 point. ON indication (LED) 40-pin connector
Appearance
QY41P 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 12/24VDC 0.1A
QY41P
0.088 to 0.3mm2 (For A6CON1 or A6CON4) 1 A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54 105mA (TYP. all points ON) (0.11A is shown on the rating plate of the module.) 0.15kg External connection
Pin-Outs
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Pin No. B20
Signal No. Y00
Pin No. A20
Signal No. Y10
B19 B18
Y01 Y02
A19 A18
Y11 Y12
B17 B16
Y03 Y04
A17 A16
Y13 Y14
B15 B14
Y05 Y06
A15 A14
Y15 Y16
B13 B12
Y07 Y08
A13 A12
Y17 Y18
B11 B10
Y09 Y0A
A11 A10
Y19 Y1A
B09 B08
Y0B Y0C
A09 A08
Y1B Y1C
B07 B06
Y0D Y0E
A07 A06
Y1D Y1E
B05 Y0F A05 Y1F B04 Vacant A04 Vacant B03 Vacant A03 Vacant 12/24 B02 A02 COM VDC B01
12/24 VDC
A01
1: When using A6CON2 or A6CON3, refer to Chapter 7.
3-9
3-9
COM
Page 86
3 OUTPUT MODULE SPECIFICATIONS
MELSEC-Q
3.9 QY42P Transistor Output Module (Sink Type) Type Specifications Number of output points Isolation method Rated load voltage Maximum load current Maximum inrush current Leakage current at OFF Maximum voltage drop at ON OFF to ON Response time ON to OFF Surge suppressor Fuse Voltage External supply power Current Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Protection function Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
Transistor output module (Sink type) QY42P 64 points Photocoupler 12-24VDC (+20/-15%) 0.1A/point, 2A/common 0.7A, 10ms or less 0.1mA or less 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A 1ms or less 1ms or less (rated load, resistive load) Zener diode No 12-24VDC (+20/-15%) (ripple ratio within 5%) 20mA (at 24VDC)/common 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1A01, 1A02, 2A01, 2A02) 64 points (I/O assignment is set as a 64-point output module.) Yes (overheat protection function, overload protection function) • Overheat protection function is activated in increments of 1 point. • Overload protection function is activated in increments of 1 point. ON indication (LED), 32 point switch-over using switch 40-pin connector
Appearance
QY42P 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 12/24VDC F 0.1A
QY42P DISPLAY L
0.088 to 0.3mm2 (For A6CON1 or A6CON4) 3 A6CON1, A6CON2, A6CON3, A6CON4 (optional)
External connection
A6TBXY36, A6TBXY54 150mA (TYP. all points ON) 0.17kg
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar.
Pin No.
Pin-Outs
1 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Signal No.
Pin No.
1
1B20 Y00 1A20 1B19 Y01 1A19 1B18 Y02 1A18 1B17 Y03 1A17 1B16 Y04 1A16 1B15 Y05 1A15 1B14 Y06 1A14 1B13 Y07 1A13 1B12 Y08 1A12 1B11 Y09 1A11 1B10 Y0A 1A10 1B09 Y0B 1A09 1B08 Y0C 1A08 1B07 Y0D 1A07 1B06 Y0E 1A06 1B05 Y0F 1A05 1B04 Vacant 1A04 1B03 Vacant 1A03 12/24V 1B02 1A02 DC 12/24V 1B01 1A01 DC
Signal No. Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17 Y18 Y19 Y1A Y1B Y1C Y1D Y1E Y1F Vacant Vacant
Pin No.
1
Signal No.
Pin No.
1
2B20 Y20 2A20 2B19 Y21 2A19 2B18 Y22 2A18 2B17 Y23 2A17 2B16 Y24 2A16 2B15 Y25 2A15 2B14 Y26 2A14 2B13 Y27 2A13 2B12 Y28 2A12 2B11 Y29 2A11 2B10 Y2A 2A10 2B09 Y2B 2A09 2B08 Y2C 2A08 2B07 Y2D 2A07 2B06 Y2E 2A06 2B05 Y2F 2A05 2B04 Vacant 2A04 2B03 Vacant 2A03 12/24V COM1 2B02 2A02 DC 12/24V COM1 2B01 2A01 DC
Signal No. Y30 Y31 Y32 Y33 Y34 Y35 Y36 Y37 Y38 Y39 Y3A Y3B Y3C Y3D Y3E Y3F Vacant Vacant COM2 COM2
1: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand side connector. 2: Selection of left-hand (F) side provides the first half (Y00 to Y1F) LED indications, and selection of right-hand (L) side provides the latter half (Y20 to Y3F) LED indications. 3: When using A6CON2 or A6CON3, refer to Chapter 7.
3 - 10
3 - 10