2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.21 QX81 DC Input Module (Negative Common Type) Type Specifications

QX81 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 17, 18, 36) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 37-pin D-sub connector 0.088 to 0.3mm2 (For A6CON1E) 2

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

DC input module (Negative common type)

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight

QX81 0 1 2 3 4 5 6 7 8 9 A B CDEF 0 1 2 3 4 5 6 7 8 9 A B CDEF QX81 24VDC 4mA

A6CON1E, A6CON2E, A6CON3E (optional) A6TBX36-E, A6TBX54-E, A6TBX70-E 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.16kg

Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0

Appearance

Pin No.

Pin-Outs

28.8VDC

10 20 30 40 50 55 ( C ) Ambient temperature

External connection

19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20

Module front view

Signal No.

Pin No.

Signal No.

1

X00

9

X10

20

X01

28

X11

2

X02

10

X12

21

X03

29

X13

3

X04

11

X14

22

X05

30

X15

4

X06

12

X16

23

X07

31

X17

5

X08

13

X18

24

X09

32

X19

6

X0A

14

X1A

25

X0B

33

X1B

7

X0C

15

X1C

26

X0D

34

X1D

8

X0E

16

X1E

27

X0F

35

X1F

17

COM

37

Vacant

36

COM

19

Vacant

18

COM

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2E or A6CON3E, refer to Chapter 7.

2 - 28

2 - 28

Page 69

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.22 QX81-S2 DC Input Module (Negative Common Type) Type Specifications

QX81-S2 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA Refer to the derating chart. 15V or higher/3mA or higher 5V or lower/1.7mA or lower Approx. 3.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 17, 18, 36) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 37-pin D-sub connector 0.088 to 0.3mm2 (For A6CON1E) 2

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

DC input module (Negative common type)

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight

A6CON1E, A6CON2E, A6CON3E (optional) A6TBX36-E, A6TBX54-E, A6TBX70-E 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.16kg

Derating chart (%) 100 90 80 70 ON ratio 60 50 40 30 20 10 0

Pin No.

Pin-Outs

(31.25%) 24VDC (18.75%) 28.8VDC

10 20 30 40 Ambient temperature

Appearance

50 55 (

)

External connection

19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20

Module front view

Signal No.

Pin No.

Signal No.

1

X00

9

X10

20

X01

28

X11

2

X02

10

X12

21

X03

29

X13

3

X04

11

X14

22

X05

30

X15

4

X06

12

X16

23

X07

31

X17

5

X08

13

X18

24

X09

32

X19

6

X0A

14

X1A

25

X0B

33

X1B

7

X0C

15

X1C

26

X0D

34

X1D

8

X0E

16

X1E

27

X0F

35

X1F

17

COM

37

Vacant

36

COM

19

Vacant

18

COM

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2E or A6CON3E, refer to Chapter 7.

2 - 29

2 - 29

Page 70

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.23 QX82 DC Input Module (Negative Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight

DC input module (Negative common type) QX82 64 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02) 64 points (I/O assignment is set as a 64-point input module.) ON indication (LED), 32 point switch-over using switch 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2 A6CON1, A6CON2, A6CON3, A6CON4 (optional)

Appearance

QX82 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA

F

QX82 DISPLAY L, - - - - 90mA (TYP. all points ON) 0.18kg

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.

2 - 30

2 - 30

Page 71

2 INPUT MODULE SPECIFICATIONS

Derating chart (%) 100 90 80 70 ON ratio/ 60 common 50 40 30 20 0

MELSEC-Q Pin Pin Pin Pin Signal Signal Signal No. Signal No. No. No. No. No. No. No. 4 4 4 4

Pin-Outs

24VDC 26.4VDC 28.8VDC

10 20 30 40 50 55 ( C ) Ambient temperature

External connection

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Module front view

1B20

X00

1A20

X10

2B20

X20

2A20

X30

1B19

X01

1A19

X11

2B19

X21

2A19

X31

1B18

X02

1A18

X12

2B18

X22

2A18

X32

1B17

X03

1A17

X13

2B17

X23

2A17

X33

1B16

X04

1A16

X14

2B16

X24

2A16

X34

1B15

X05

1A15

X15

2B15

X25

2A15

X35

1B14

X06

1A14

X16

2B14

X26

2A14

X36

1B13

X07

1A13

X17

2B13

X27

2A13

X37

1B12

X08

1A12

X18

2B12

X28

2A12

X38

1B11

X09

1A11

X19

2B11

X29

2A11

X39

1B10

X0A

1A10

X1A

2B10

X2A

2A10

X3A

1B09

X0B

1A09

X1B

2B09

X2B

2A09

X3B

1B08

X0C

1A08

X1C

2B08

X2C

2A08

X3C

1B07

X0D

1A07

X1D

2B07

X2D

2A07

X3D

1B06

X0E

1A06

X1E

2B06

X2E

2A06

X3E

1B05

X0F

1A05

X1F

2B05

X2F

2A05

X3F

1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant 1B03 Vacant 1A03 Vacant 2B03 Vacant 2A03 Vacant 1B02 COM1 1A02 Vacant 2B02 COM2 2A02 Vacant

The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar.

1B01 COM1 1A01 Vacant 2B01 COM2 2A01 Vacant

3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the latter half (X20 to X3F) LED indications. 4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand side connector.

2 - 31

2 - 31

Page 72

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.24 QX82-S1 DC Input Module (Negative Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Set value 1 TYP. Response OFF to ON MAX. time TYP. ON to OFF MAX. Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight

DC input module (Negative common type) QX82-S1 64 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3.0mA or higher 9.5V or lower/1.5mA or lower Approx. 5.6kΩ 0.1 0.2 0.4 0.6 1 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 0.12ms 0.20ms 0.40ms 0.60ms 1.20ms 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02) 64 points (I/O assignment is set as a 64-point high-speed input module.) ON indication (LED), 32 point switch-over using switch 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2 A6CON1, A6CON2, A6CON3, A6CON4 (optional)

Appearance

QX82-S1 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA

F

QX82-S1 DISPLAY L, - - - - 90mA (TYP. all points ON) 0.18kg

1: Configured in PLC parameter. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW5D5C-GPPW or later). For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.

2 - 32

2 - 32

Page 73

2 INPUT MODULE SPECIFICATIONS

Derating chart (%) 100 90 80 ON ratio/ 70 common 60 50 40 30 20 0

Pin Pin Pin Pin Signal Signal Signal Signal No. No. No. No. No. No. No. No. 4 4 4 4

Pin-Outs

24VDC 26.4VDC 28.8VDC

10 20 30 40 50 55 ( C ) Ambient temperature

External connection

MELSEC-Q

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Module front view

1B20

X00

1A20

X10

2B20

X20

2A20

X30

1B19

X01

1A19

X11

2B19

X21

2A19

X31

1B18

X02

1A18

X12

2B18

X22

2A18

X32

1B17

X03

1A17

X13

2B17

X23

2A17

X33

1B16

X04

1A16

X14

2B16

X24

2A16

X34

1B15

X05

1A15

X15

2B15

X25

2A15

X35

1B14

X06

1A14

X16

2B14

X26

2A14

X36

1B13

X07

1A13

X17

2B13

X27

2A13

X37

1B12

X08

1A12

X18

2B12

X28

2A12

X38

1B11

X09

1A11

X19

2B11

X29

2A11

X39

1B10

X0A

1A10

X1A

2B10

X2A

2A10

X3A

1B09

X0B

1A09

X1B

2B09

X2B

2A09

X3B

1B08

X0C

1A08

X1C

2B08

X2C

2A08

X3C

1B07

X0D

1A07

X1D

2B07

X2D

2A07

X3D

1B06

X0E

1A06

X1E

2B06

X2E

2A06

X3E

1B05

X0F

1A05

X1F

2B05

X2F

2A05

X3F

1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant 1B03 Vacant 1A03 Vacant 2B03 Vacant 2A03 Vacant 1B02 COM1 1A02 Vacant 2B02 COM2 2A02 Vacant 1B01 COM1 1A01 Vacant 2B01 COM2 2A01 Vacant

The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar. 3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the latter half (X20 to X3F) LED indications. 4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand side connector.

2 - 33

2 - 33

Page 74

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.25 QX90H DC High-speed Input Module (Negative Common Type) DC high-speed input module (Negative common type)

Type Specifications

QX90H

Appearance

Number of input points Isolation method Rated input voltage Rated input current Input derating

16 points Photocoupler 5VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA None

ON voltage/ON current OFF voltage/OFF current Input impedance SW1 (noise filter) 1 Set value 2 Response TYP. time OFF to ON MAX. TYP. ON to OFF MAX. Function SW2 4 setting Dielectric withstand voltage Insulation resistance

3.5V or higher/3mA or higher 1V or lower/1mA or lower Approx. 470Ω

Noise immunity

5

Protection degree Common terminal arrangement Number of occupied I/O points Interrupt processing condition Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

OFF

ON

Invalid 0ms 0ms -

3 3 3 3

0.1 0.04ms 0.05ms 0.04ms 0.05ms

0.2 0.10ms 0.15ms 0.10ms 0.15ms

0.4 0.25ms 0.30ms 0.25ms 0.30ms

0.6 0.50ms 0.60ms 0.50ms 0.60ms

1 0.95ms 1.00ms 0.95ms 1.00ms

OFF: Interrupt, ON: High-speed input 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency IP2X 8 points/common (common terminal: TB9, TB18) 16 points (I/O assignment is set as a 16-point high-speed input module or 16point interrupt module.) 4 Set by Switch setting in GX Developer 4 6 ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 80mA (TYP. all points ON) 0.14kg

1: If the noise filter selector switch (switch 1) on the bottom of the module (refer to Chapter 10) is turned on, the noise filter takes effect. The off-status noise filter disables I/O response time setting. After switching on or off the switch 1, reset the power supply of the CPU module. 2: Set an input response time in "I/O response time" combo box of PLC parameter in GX Developer. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW6D5C-GPPW or later). For the setting details, refer to Section 1.3.1. 3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added. For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals). 4: The module function can be changed according to the status of the function selector switch (switch 2) on the bottom of the module (refer to Chapter 10). ON: High-speed input OFF: Interrupt If the function selector switch (switch 2) setting is changed while the CPU module is in RUN, an error (error code: 2100) occurs. 5: Indicates the noise immunity when the noise filter takes effect (the noise filter selector switch (switch 1) is turned on). 6: For the setting method, refer to Section 1.3.3.

2 - 34

2 - 34

Page 75

2 INPUT MODULE SPECIFICATIONS

External connection

2 - 35

MELSEC-Q Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

COM1

TB10

X08

TB11

X09

TB12

X0A

TB13

X0B

TB14

X0C

TB15

X0D

TB16

X0E

TB17

X0F

TB18

COM2

2 - 35

Page 76

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

MEMO

2 - 36

2 - 36