Page 59

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.15 QX70H DC High-speed Input Module (Positive Common Type) DC high-speed input module (Positive common type)

Type Specifications

QX70H

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance SW1 (noise filter) 1 Set value 2 Response TYP. time OFF to ON MAX. TYP. ON to OFF MAX. Function SW2 4 setting Dielectric withstand voltage Insulation resistance Noise immunity

5

Protection degree Common terminal arrangement Number of occupied I/O points Interrupt processing condition Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

Appearance

16 points Photocoupler 5VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA None 3.5V or higher/3mA or higher 1V or lower/1mA or lower Approx. 470Ω OFF

ON

Invalid 0ms 0ms -

3 3 3 3

0.1 0.04ms 0.05ms 0.04ms 0.05ms

0.2 0.10ms 0.15ms 0.10ms 0.15ms

0.4 0.25ms 0.30ms 0.25ms 0.30ms

0.6 0.50ms 0.60ms 0.50ms 0.60ms

1 0.95ms 1.00ms 0.95ms 1.00ms

OFF: Interrupt, ON: High-speed input 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency IP2X 8 points/common (common terminal: TB9, TB18) 16 points (I/O assignment is set as a 16-point high-speed input module or 16point interrupt module.) 4 Set by Switch setting in GX Developer 4 6 ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 80mA (TYP. all points ON) 0.14kg

1: If the noise filter selector switch (switch 1) on the bottom of the module (refer to Chapter 10) is turned on, the noise filter takes effect. The off-status noise filter disables I/O response time setting. After switching on or off the switch 1, reset the power supply of the CPU module. 2: Set an input response time in "I/O response time" combo box of PLC parameter in GX Developer. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW6D5C-GPPW or later). For the setting details, refer to Section 1.3.1. 3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added. For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals). 4: The module function can be changed according to the status of the function selector switch (switch 2) on the bottom of the module (refer to Chapter 10). ON: High-speed input OFF: Interrupt If the function selector switch (switch 2) setting is changed while the CPU module is in RUN, an error (error code: 2100) occurs. 5: Indicates the noise immunity when the noise filter takes effect (the noise filter selector switch (switch 1) is turned on). 6: For the setting method, refer to Section 1.3.3.

2 - 19

2 - 19

Page 60

2 INPUT MODULE SPECIFICATIONS External connection

2 - 20

MELSEC-Q Terminal block No.

Signal name

TB1 TB2 TB3 TB4 TB5 TB6 TB7 TB8 TB9 TB10 TB11 TB12 TB13 TB14 TB15 TB16 TB17 TB18

X00 X01 X02 X03 X04 X05 X06 X07 COM1 X08 X09 X0A X0B X0C X0D X0E X0F COM2

2 - 20

Page 61

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.16 QX71 DC Input Module (Positive/Negative Shared Common Type) Type

DC input module (Positive/negative shared common type)

Specifications

QX71

Number of input points Isolation method

5VDC (+20/-10%, ripple ratio within 5%) Approx. 1.2mA

Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input resistance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Internal current consumption (5VDC) Weight

Appearance

32 points Photocoupler 12VDC (+20/-15%, ripple ratio within 5%) Approx. 3.3mA None 3.5V or higher/1mA or higher 1V or lower/0.1mA or lower Approx. 3.3kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: B01, B02) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2

QX71 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 5/12VDC 1.2 / 3.3mA

QX71

A6CON1, A6CON2, A6CON3, A6CON4 (optional) 70mA (TYP, all points ON) 0.12kg External connection

Pin-Outs

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Pin No.

Signal No.

Pin No.

Signal No.

B20

X00

A20

X10

B19

X01

A19

X11

B18

X02

A18

X12

B17

X03

A17

X13

B16

X04

A16

X14

B15

X05

A15

X15

B14

X06

A14

X16

B13

X07

A13

X17

B12

X08

A12

X18

B11

X09

A11

X19

B10

X0A

A10

X1A

B09

X0B

A09

X1B

B08

X0C

A08

X1C

B07

X0D

A07

X1D

B06

X0E

A06

X1E

B05

X0F

A05

X1F

B04 Vacant A04 Vacant

Module front view

B03 Vacant A03 Vacant B02

COM

A02 Vacant

B01

COM

A01 Vacant

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.

2 - 21

2 - 21

Page 62

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.17 QX72 DC Input Module (Positive/Negative Shared Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input resistance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Internal current consumption (5VDC) Weight

DC input module (Positive/negative shared common type) QX72 Appearance 64 points Photocoupler 5VDC 12VDC QX72 (+20/-10%, ripple ratio within 5%) (+20/-15%, ripple ratio within 5%) 0 1 2 3 4 5 6 7 8 9 A B CDE F Approx. 1.2mA Approx. 3.3mA 0 1 2 3 4 5 6 7 None 8 9 A B CDE F 3.5V or higher/3mA or higher QX72 DISPLAY 5/12VDC 1V or lower/0.1mA or lower F L 1.2/3.3mA Approx. 3.3kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02) 64 points (I/O assignment is set as a 64-point input module.) ON indication (LED), 32-point switchover using switch 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2 A6CON1, A6CON2, A6CON3, A6CON4 (optional) 85mA (TYP, all points ON) (0.09A is shown on the rating plate of the module.) 0.13kg

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 and A6CON3, refer to Chapter 7.

2 - 22

2 - 22

Page 63

2 INPUT MODULE SPECIFICATIONS

External connection

MELSEC-Q Pin-Outs

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Pin Pin Pin Pin Signal Signal Signal Signal No. No. No. No. No. No. No. No. 4 4 4 4 1B20

X00

1A20

X10

2B20

X20

2A20

X30

1B19

X01

1A19

X11

2B19

X21

2A19

X31

1B18

X02

1A18

X12

2B18

X22

2A18

X32

1B17

X03

1A17

X13

2B17

X23

2A17

X33

1B16

X04

1A16

X14

2B16

X24

2A16

X34

1B15

X05

1A15

X15

2B15

X25

2A15

X35

1B14

X06

1A14

X16

2B14

X26

2A14

X36

1B13

X07

1A13

X17

2B13

X27

2A13

X37

1B12

X08

1A12

X18

2B12

X28

2A12

X38

1B11

X09

1A11

X19

2B11

X29

2A11

X39

1B10

X0A

1A10

X1A

2B10

X2A

2A10

X3A

1B09

X0B

1A09

X1B

2B09

X2B

2A09

X3B

1B08

X0C

1A08

X1C

2B08

X2C

2A08

X3C

1B07

X0D

1A07

X1D

2B07

X2D

2A07

X3D

1B06

X0E

1A06

X1E

2B06

X2E

2A06

X3E

1B05

X0F

1A05

X1F

2B05

X2F

2A05

X3F

1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant

Module front view The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar.

1B03 Vacant 1A03 Vacant 2B03 Vacant 2A03 Vacant 1B02 COM1 1A02 Vacant 2B02 COM2 2A02 Vacant

1B01 COM1 1A01 Vacant 2B01 COM2 2A01 Vacant

3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the latter half (X20 to X3F) LED indications. 4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand side connector.

2 - 23

2 - 23

Page 64

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.18 QX80 DC Input Module (Negative Common Type) Type

DC input module (Negative common type)

Specifications

QX80

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB18) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)

External connection

QX80 0 1 2 3 4 5 6 7 8 9 A B CDE F

1

0

0 1 2 3 4 5 6 7 8 9 A B C D E F

1 2

1

3 4 5 6 7 8 9 A B C D E F NC COM

24VDC 4mA

50mA (TYP. all points ON) 0.16kg Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

Vacant

TB18

COM

1: For the setting method, refer to Section 1.3.1.

2 - 24

2 - 24

Page 65

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.19 QX80-TS DC Input Module (Negative Common Type) This module is a spring clamp terminal block type and an input module that has indicators for checking the insertion state of wire. Type

DC input module (Negative common type)

Specifications

QX80-TS

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)

1

(Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)

1

(Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB18) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) Two-piece spring clamp terminal block

Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight External connection

0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1 50mA (TYP. all points ON) 0.16kg

QX80-TS

0123 4567 8 9 AB CDEF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

Vacant

TB18

COM

1: For the setting method, refer to Section 1.3.1.

2 - 25

2 - 25

Page 66

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.20 QX80H DC High-speed Input Module (Negative Common Type) DC high-speed input module (Negative common type)

Type Specifications

QX80H

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance SW1 (noise filter) 1 Set value 2 Response TYP. time OFF to ON MAX. TYP. ON to OFF MAX. Function SW2 4 setting Dielectric withstand voltage Insulation resistance Noise immunity

5

Protection degree Common terminal arrangement Number of occupied I/O points Interrupt processing condition Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA Refer to the derating chart. 13V or higher/3mA or higher 8V or lower/1.6mA or lower Approx. 3.9kΩ OFF

ON

Invalid 0ms 0ms -

3 3 3 3

0.1 0.04ms 0.05ms 0.04ms 0.05ms

0.2 0.10ms 0.15ms 0.10ms 0.15ms

0.4 0.25ms 0.30ms 0.25ms 0.30ms

0.6 0.50ms 0.60ms 0.50ms 0.60ms

1 0.95ms 1.00ms 0.95ms 1.00ms

OFF: Interrupt, ON: High-speed input 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency IP2X 8 points/common (common terminal: TB9, TB18) 16 points (I/O assignment is set as a 16-point high-speed input module or 16point interrupt module.) 4 Set by Switch setting in GX Developer 4 6 ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 80mA (TYP. all points ON) 0.16kg

1: If the noise filter selector switch (switch 1) on the bottom of the module (refer to Chapter 10) is turned on, the noise filter takes effect. The off-status noise filter disables I/O response time setting. After switching on or off the switch 1, reset the power supply of the CPU module. 2: Set an input response time in "I/O response time" combo box of PLC parameter in GX Developer. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW6D5C-GPPW or later). For the setting details, refer to Section 1.3.1. 3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added. For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals). 4: The module function can be changed according to the status of the function selector switch (switch 2) on the bottom of the module (refer to Chapter 10). ON: High-speed input OFF: Interrupt If the function selector switch (switch 2) setting is changed while the CPU module is in RUN, an error (error code: 2100) occurs. 5: Indicates the noise immunity when the noise filter takes effect (the noise filter selector switch (switch 1) is turned on). 6: For the setting method, refer to Section 1.3.3.

2 - 26

2 - 26

Page 67

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

Derating chart (%) 100 90 80 ON ratio/ 70 common 60 50 40 0

26.4VDC 28.8VDC

10 20 30 40 50 55 ( Ambient temperature

External connection

2 - 27

)

Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

COM1

TB10

X08

TB11

X09

TB12

X0A

TB13

X0B

TB14

X0C

TB15

X0D

TB16

X0E

TB17

X0F

TB18

COM2

2 - 27