The text of a manual · part 8 of 20
I/O Module Type Building Block User's Manual: 2. INPUT MODULE SPECIFICATIONS, pages 50 to 58
Pages 50 to 58 of 158, from I/O Module Type Building Block User's Manual
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi QG60 and Mitsubishi QX42
Page 50
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.9 QX41-S1 DC Input Module (Positive Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Set value 1 TYP. Response OFF to ON MAX. time TYP. ON to OFF MAX. Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
DC input module (Positive common type) QX41-S1 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3.0mA or higher 9.5V or lower/1.5mA or lower Approx. 5.6kΩ 0.1 0.2 0.4 0.6 1 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 0.12ms 0.20ms 0.40ms 0.60ms 1.20ms 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: B01, B02) 32 points (I/O assignment is set as a 32-point high-speed input module.) ON indication (LED) 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2
Appearance
QX41-S1 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA
QX41-S1
A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54, A6TBX70 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.15kg
1: Configured in PLC parameter. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW5D5C-GPPW or later). For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.
2 - 10
2 - 10
Page 51
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Derating chart (%) 100 90 80 ON ratio 70 60 50 40 0
Pin-Outs
28.8VDC
10 20 30 40 50 55 ( C ) Ambient temperature
External connection
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Pin No.
Signal No.
Pin No.
Signal No.
B20
X00
A20
X10
B19
X01
A19
X11
B18
X02
A18
X12
B17
X03
A17
X13
B16
X04
A16
X14
B15
X05
A15
X15
B14
X06
A14
X16
B13
X07
A13
X17
B12
X08
A12
X18
B11
X09
A11
X19
B10
X0A
A10
X1A
B09
X0B
A09
X1B
B08
X0C
A08
X1C
B07
X0D
A07
X1D
B06
X0E
A06
X1E
B05
X0F
A05
X1F
B04 Vacant A04 Vacant
Module front view
2 - 11
B03 Vacant A03 Vacant B02
COM
A02 Vacant
B01
COM
A01 Vacant
2 - 11
Page 52
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.10 QX41-S2 DC Input Module (Positive Common Type) Type Specifications
QX41-S2 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA Refer to the derating chart. 15V or higher/3mA or higher 5V or lower/1.7mA or lower Approx. 3.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: B01, B02) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2
Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time
DC input module (Positive common type)
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54, A6TBX70 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.15kg
Derating chart (%) 100 90 80 70 ON ratio 60 50 40 30 20 10 0
Appearance
Pin-Outs
(31.25%) 24VDC (18.75%) 28.8VDC
10 20 30 40 50 55 ( Ambient temperature
External connection
)
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Pin No.
Signal No.
Pin No.
Signal No.
B20
X00
A20
X10
B19
X01
A19
X11
B18
X02
A18
X12
B17
X03
A17
X13
B16
X04
A16
X14
B15
X05
A15
X15
B14
X06
A14
X16
B13
X07
A13
X17
B12
X08
A12
X18
B11
X09
A11
X19
B10
X0A
A10
X1A
B09
X0B
A09
X1B
B08
X0C
A08
X1C
B07
X0D
A07
X1D
B06
X0E
A06
X1E
B05
X0F
A05
X1F
B04 Vacant A04 Vacant B03 Vacant A03 Vacant B02
COM
A02 Vacant
B01
COM
A01 Vacant
1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.
2 - 12
2 - 12
Page 53
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.11 QX42 DC Input Module (Positive Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
DC input module (Positive common type) QX42 64 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02) 64 points (I/O assignment is set as a 64-point input module.) ON indication (LED), 32 point switch-over using switch 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2 A6CON1, A6CON2, A6CON3, A6CON4 (optional)
Appearance
QX42 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA
QX42 DISPLAY F L
A6TBXY36, A6TBXY54, A6TBX70 90mA (TYP. all points ON) 0.18kg
1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.
2 - 13
2 - 13
Page 54
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Derating chart (%) 100 90 80 70 ON ratio/ common 60 50 40 30 20 0
Pin-Outs
24VDC 26.4VDC 28.8VDC
10 20 30 40 50 55 ( C ) Ambient temperature
External connection
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Pin No. 4
Signal No.
Pin No. 4
Signal No.
Pin No. 4
Signal No.
Pin No. 4
Signal No.
1B20
X00
1A20
X10
2B20
X20
2A20
X30
1B19
X01
1A19
X11
2B19
X21
2A19
X31
1B18
X02
1A18
X12
2B18
X22
2A18
X32
1B17
X03
1A17
X13
2B17
X23
2A17
X33
1B16
X04
1A16
X14
2B16
X24
2A16
X34
1B15
X05
1A15
X15
2B15
X25
2A15
X35
1B14
X06
1A14
X16
2B14
X26
2A14
X36
1B13
X07
1A13
X17
2B13
X27
2A13
X37
1B12
X08
1A12
X18
2B12
X28
2A12
X38
1B11
X09
1A11
X19
2B11
X29
2A11
X39
1B10
X0A
1A10
X1A
2B10
X2A
2A10
X3A
1B09
X0B
1A09
X1B
2B09
X2B
2A09
X3B
1B08
X0C
1A08
X1C
2B08
X2C
2A08
X3C
1B07
X0D
1A07
X1D
2B07
X2D
2A07
X3D
1B06
X0E
1A06
X1E
2B06
X2E
2A06
X3E
1B05
X0F
1A05
X1F
2B05
X2F
2A05
X3F
1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant 1B03 Vacant 1A03 Vacant 2B03 Vacant 2A03 Vacant 1B02 COM1 1A02 Vacant 2B02
COM2
2A02 Vacant
1B01 COM1 1A01 Vacant 2B01
COM2
2A01 Vacant
The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar. 3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the latter half (X20 to X3F) LED indications. 4: Pin number of 1 indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand side connector.
2 - 14
2 - 14
Page 55
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.12 QX42-S1 DC Input Module (Positive Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Set value 1 TYP. Response OFF to ON MAX. time TYP. ON to OFF MAX. Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
DC input module (Positive common type) QX42-S1 64 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3.0mA or higher 9.5V or lower/1.5mA or lower Approx. 5.6kΩ 0.1 0.2 0.4 0.6 1 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 0.12ms 0.20ms 0.40ms 0.60ms 1.20ms 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: 1B01, 1B02, 2B01, 2B02) 64 points (I/O assignment is set as a 64-point high-speed input module.) ON indication (LED), 32 point switch-over using switch 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2 A6CON1, A6CON2, A6CON3, A6CON4 (optional)
Appearance
QX42-S1 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA
F
QX42-S1 DISPLAY L
A6TBXY36, A6TBXY54, A6TBX70 90mA (TYP. all points ON) 0.18kg
1: Configured in PLC parameter. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW5D5C-GPPW or later). For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.
2 - 15
2 - 15
Page 56
2 INPUT MODULE SPECIFICATIONS
Derating chart (%) 100 90 80 ON ratio/ 70 common 60 50 40 30 20 0
MELSEC-Q Pin-Outs
24VDC 26.4VDC 28.8VDC
10 20 30 40 50 55 ( C ) Ambient temperature
External connection
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Module front view
Pin No. 4
Signal No.
Pin No. 4
Signal No.
Pin No. 4
Signal No.
Pin No. 4
Signal No.
1B20
X00
1A20
X10
2B20
X20
2A20
X30
1B19
X01
1A19
X11
2B19
X21
2A19
X31
1B18
X02
1A18
X12
2B18
X22
2A18
X32
1B17
X03
1A17
X13
2B17
X23
2A17
X33
1B16
X04
1A16
X14
2B16
X24
2A16
X34
1B15
X05
1A15
X15
2B15
X25
2A15
X35
1B14
X06
1A14
X16
2B14
X26
2A14
X36
1B13
X07
1A13
X17
2B13
X27
2A13
X37
1B12
X08
1A12
X18
2B12
X28
2A12
X38
1B11
X09
1A11
X19
2B11
X29
2A11
X39
1B10
X0A
1A10
X1A
2B10
X2A
2A10
X3A
1B09
X0B
1A09
X1B
2B09
X2B
2A09
X3B
1B08
X0C
1A08
X1C
2B08
X2C
2A08
X3C
1B07
X0D
1A07
X1D
2B07
X2D
2A07
X3D
1B06
X0E
1A06
X1E
2B06
X2E
2A06
X3E
1B05
X0F
1A05
X1F
2B05
X2F
2A05
X3F
1B04 Vacant 1A04 Vacant 2B04 Vacant 2A04 Vacant 1B03 Vacant 1A03 Vacant 2B03 Vacant 2A03 Vacant 1B02 COM1 1A02 Vacant 2B02 COM2 2A02 Vacant 1B01 COM1 1A01 Vacant 2B01 COM2 2A01 Vacant
The above diagram shows the first half of 32 points (F). The latter half of 32 points (L) are similar. 3: Selection of left-hand (F) side provides the first half (X00 to X1F) LED indications, and selection of right-hand (L) side provides the latter half (X20 to X3F) LED indications. indicates that of the left-hand side connector, and pin number of 2 indicates that of the right-hand 4: Pin number of 1 side connector.
2 - 16
2 - 16
Page 57
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.13 QX50 DC (Positive Common/Negative Common Shared Type)/ AC Input Module DC (positive/negative shared common type)/ AC input module QX50 Appearance DC Input AC Input 16 points Photocoupler QX50 012 345 67 48VDC 48VAC (+10/-15%) 50/60Hz 8 9 A B CDE F (+20/-15%, ripple ratio within 5%) (±3Hz) (ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 28V or higher/2.5mA or higher 0 10V or lower/1.0mA or lower 0 1 Approx. 11.2kΩ 2 1 5ms or less 15ms or less 3 2 20ms or less 20ms or less 4 3 1060VAC rms/3 cycles (altitude 2000m) 5 4 6 10MΩ or more by insulation resistance tester 5 7 By noise simulator of 500Vp-p noise voltage, 1 s noise width 6 8 and 25 to 60Hz noise frequency 9 7 First transient noise IEC61000-4-4: 1kV A 8 IP2X B 9 16 points/common (common terminal: TB17) C A 16 points (I/O assignment is set as a 16-point input module.) D B ON indication (LED) E C F 18-point terminal block (M3 6 screws) D 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) E
Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response OFF to ON ON to OFF time 1 Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
F
50mA (TYP. all points ON) 0.13kg Derating chart
Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
(%) 100 90 80 ON 70 ratio 60 50 40 0
48VDC/AC
57.6VDC 52.8VAC 10
20
30
40
50 55 ( C)
Ambient temperature
External connection
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
1: Response time cannot be changed. Parameter setting of the CPU module will be invalid.
2 - 17
2 - 17
Page 58
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.14 QX70 DC Input Module (Positive Common/Negative Common Shared Type) Type
DC input module (Positive/negative shared common type)
Specifications
QX70
Number of input points Isolation method
Appearance
16 points Photocoupler 5VDC (+20/-10%, ripple ratio within 5%) Approx. 1.2mA
Applicable wire size
12VDC (+20/-15%, ripple ratio within 5%) Approx. 3.3mA None 3.5V or higher/1mA or higher 1V or lower/0.1mA or lower Approx. 3.3kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screw) Core cable: 0.3 to 0.75mm2 (Outside diameter: 2.8mm or smaller)
Applicable crimping terminal Internal current consumption (5VDC) Weight
R1.25-3 (Sleeved crimping terminals cannot be used.) 55mA (TYP, all points ON) (0.06A is shown on the rating plate of the module.) 0.14kg
Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input resistance Response time
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections
External connection
QX70 0 1 2 3 4 5 6 7 8 9 A B CDE F
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
1 2 3 4 5 6 7 8 9 A B C D E F - +
COM
NC 5/12VDC 1.2mA 3.3mA
Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
1: For the setting method, refer to Section 1.3.1.
2 - 18
2 - 18