Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 7 of 20

I/O Module Type Building Block User's Manual: 2. INPUT MODULE SPECIFICATIONS, pages 41 to 49

Pages 41 to 49 of 158, from I/O Module Type Building Block User's Manual

The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi QG60 and Mitsubishi QX42

Page 41

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2. INPUT MODULE SPECIFICATIONS 2.1 QX10 AC Input Module Type Specifications Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

AC input module QX10 16 points Photocoupler 100-120VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 200mA within 1ms (at 132VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 15ms or less (100VAC 50Hz, 60Hz) 20ms or less (100VAC 50Hz, 60Hz) 1780VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)

0

0 1 2 3 4 5 6 7 8 9 A B C D E F

1 2 3 4 5 6 7 8 9 A B C D E F COM NC 100VAC 8mA60Hz 7mA50Hz

0.17kg

120VAC 132VAC 10 20 30 40 50 55( C ) Ambient temperature

External connection

2-1

QX10 0 1 2 3 4 5 6 7 8 9 A B CDE F

50mA (TYP. all points ON)

Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0

Appearance

Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

COM

TB18

Vacant

2-1

2

Page 42

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.2 QX10-TS AC Input Module This module is a spring clamp terminal block type and an input module that has indicators for checking the insertion state of wire. Type Specifications

2

Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

AC input module QX10-TS 16 points Photocoupler 100-120VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 200mA within 1ms (at 132VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 15ms or less (100VAC 50Hz, 60Hz) 20ms or less (100VAC 50Hz, 60Hz) 1780VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) Two-piece spring clamp terminal block 0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1

012345 67 8 9 ABCDEF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

0.17kg

120VAC 132VAC 10 20 30 40 50 55( C ) Ambient temperature

External connection

2-2

QX10-TS

50mA (TYP. all points ON)

Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0

Appearance

Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

COM

TB18

Vacant

2-2

Page 43

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.3 QX28 AC Input Module Type Specifications Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

AC input module QX28 8 points Photocoupler 100-240VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 17mA (200VAC, 60Hz), approx. 14mA (200VAC, 50Hz) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 950mA within 1ms (at 264VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 10ms or less (200VAC 50Hz, 60Hz) 20ms or less (200VAC 50Hz, 60Hz) 2830VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 8 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)

0

0 1 2 3 4 5 6 7 8 9 A B C D E F

NC 1 NC 2 NC 3 NC 4 NC 5 NC 6 NC 7 NC COM NC 200VAC 17mA60Hz 14mA50Hz

0.20kg

100% 45 C

Terminal block No. 100% 55 C 87.5% 55 C

10 20 30 40 50 55( C ) Ambient temperature

External connection

2-3

QX28 0 1 2 3 4 5 6 7

50mA (TYP. all points ON)

Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0

Appearance

240V 264V

Signal name

TB1

X00

TB2

Vacant

TB3

X01

TB4

Vacant

TB5

X02

TB6

Vacant

TB7

X03

TB8

Vacant

TB9

X04

TB10

Vacant

TB11

X05

TB12

Vacant

TB13

X06

TB14

Vacant

TB15

X07

TB16

Vacant

TB17

COM

TB18

Vacant

2-3

Page 44

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.4 QX40 DC Input Module (Positive Common Type) Type

DC input module (Positive common type)

Specifications

QX40

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)

External connection

QX40 0 1 2 3 4 5 6 7 8 9 A B CDE F

1

0

0 1 2 3 4 5 6 7 8 9 A B C D E F

1 2

1

3 4 5 6 7 8 9 A B C D E F - +

COM

NC 24VDC 4mA

50mA (TYP. all points ON) 0.16kg Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

COM

TB18

Vacant

1: For the setting method, refer to Section 1.3.1.

2-4

2-4

Page 45

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.5 QX40-S1 DC Input Module (Positive Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Set value 1 TYP. Response OFF to ON MAX. time TYP. ON to OFF MAX. Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

DC input module (Positive common type) QX40-S1 16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA No 19V or higher/4.0mA or higher 11V or lower/1.7mA or lower Approx. 3.9kΩ 0.1 0.2 0.4 0.6 1 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 0.10ms 0.20ms 0.40ms 0.60ms 1.20ms 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point high-speed input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)

External connection

Appearance

QX40-S1 0 1 2 3 4 5 6 7 8 9 A B CDE F

0

0 1 2 3 4 5 6 7 8 9 A B C D E F

1 2 3 4 5 6 7 8 9 A B C D E F - +

COM

NC 24VDC 6mA

60mA (TYP. all points ON) 0.20kg Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

COM

TB18

Vacant

1: Configured in PLC parameter. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW5D5C-GPPW or later). For the setting method, refer to Section 1.3.1.

2-5

2-5

Page 46

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.6 QX40-TS DC Input Module (Positive Common Type) This module is a spring clamp terminal block type and an input module that has indicators for checking the insertion state of wire. Type

DC input module (Positive common type)

Specifications

QX40-TS

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)

1

(Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)

1

(Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) Two-piece spring clamp terminal block

Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight External connection

0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1

QX40-TS 012 34 567 8 9 A B CDE F

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

50mA (TYP. all points ON) 0.16kg Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

X08

TB10

X09

TB11

X0A

TB12

X0B

TB13

X0C

TB14

X0D

TB15

X0E

TB16

X0F

TB17

COM

TB18

Vacant

1: For the setting method, refer to Section 1.3.1.

2-6

2-6

Page 47

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.7 QX40H DC High-Speed Input Module (Positive Common Type) DC high-speed input module (Positive common type)

Type Specifications

QX40H

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance SW1 (noise filter) 1 Set value 2 Response TYP. time OFF to ON MAX. TYP. ON to OFF MAX. Function SW2 4 setting Dielectric withstand voltage Insulation resistance Noise immunity

5

Protection degree Common terminal arrangement Number of occupied I/O points Interrupt processing condition Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight

Appearance

16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA Refer to the derating chart. 13V or higher/3mA or higher 8V or lower/1.6mA or lower Approx. 3.9kΩ OFF

ON

Invalid 0ms 0ms -

3 3 3 3

0.1 0.04ms 0.05ms 0.04ms 0.05ms

0.2 0.10ms 0.15ms 0.10ms 0.15ms

0.4 0.25ms 0.30ms 0.25ms 0.30ms

0.6 0.50ms 0.60ms 0.50ms 0.60ms

1 0.95ms 1.00ms 0.95ms 1.00ms

OFF: Interrupt, ON: High-speed input 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency IP2X 8 points/common (common terminal: TB9, TB18) 16 points (I/O assignment is set as a 16-point high-speed input module or 16point interrupt module.) 4 Set by Switch setting in GX Developer 4 6 ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 80mA (TYP. all points ON) 0.16kg

1: If the noise filter selector switch (switch 1) on the bottom of the module (refer to Chapter 10) is turned on, the noise filter takes effect. The off-status noise filter disables I/O response time setting. After switching on or off the switch 1, reset the power supply of the CPU module. 2: Set an input response time in "I/O response time" combo box of PLC parameter in GX Developer. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW6D5C-GPPW or later). For the setting details, refer to Section 1.3.1. 3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added. For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals). 4: The module function can be changed according to the status of the function selector switch (switch 2) on the bottom of the module (refer to Chapter 10). ON: High-speed input OFF: Interrupt If the function selector switch (switch 2) setting is changed while the CPU module is in RUN, an error (error code: 2100) occurs. 5: Indicates the noise immunity when the noise filter takes effect (the noise filter selector switch (switch 1) is turned on). 6: For the setting method, refer to Section 1.3.3.

2-7

2-7

Page 48

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

Derating chart (%) 100 90 80 ON ratio/ 70 common 60 50 40 0

26.4VDC 28.8VDC

10 20 30 40 50 55 ( Ambient temperature

External connection

2-8

)

Terminal block No.

Signal name

TB1

X00

TB2

X01

TB3

X02

TB4

X03

TB5

X04

TB6

X05

TB7

X06

TB8

X07

TB9

COM1

TB10

X08

TB11

X09

TB12

X0A

TB13

X0B

TB14

X0C

TB15

X0D

TB16

X0E

TB17

X0F

TB18

COM2

2-8

Page 49

2 INPUT MODULE SPECIFICATIONS

MELSEC-Q

2.8 QX41 DC Input Module (Positive Common Type) Type Specifications

QX41 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: B01, B02) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2

Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time

DC input module (Positive common type)

OFF to ON ON to OFF

Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight

QX41 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA

QX41

A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54, A6TBX70 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.15kg

Derating chart (%) 100 90 80 ON ratio 70 60 50 40 0

Appearance

Pin-Outs

28.8VDC

10 20 30 40 50 55 ( C ) Ambient temperature

External connection

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Pin No.

Signal No.

Pin No.

Signal No.

B20

X00

A20

X10

B19

X01

A19

X11

B18

X02

A18

X12

B17

X03

A17

X13

B16

X04

A16

X14

B15

X05

A15

X15

B14

X06

A14

X16

B13

X07

A13

X17

B12

X08

A12

X18

B11

X09

A11

X19

B10

X0A

A10

X1A

B09

X0B

A09

X1B

B08

X0C

A08

X1C

B07

X0D

A07

X1D

B06

X0E

A06

X1E

B05

X0F

A05

X1F

B04 Vacant A04 Vacant

Module front view

B03 Vacant A03 Vacant B02

COM

A02 Vacant

B01

COM

A01 Vacant

1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.

2-9

2-9