The text of a manual · part 7 of 20
I/O Module Type Building Block User's Manual: 2. INPUT MODULE SPECIFICATIONS, pages 41 to 49
Pages 41 to 49 of 158, from I/O Module Type Building Block User's Manual
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Mitsubishi QG60 and Mitsubishi QX42
Page 41
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2. INPUT MODULE SPECIFICATIONS 2.1 QX10 AC Input Module Type Specifications Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
AC input module QX10 16 points Photocoupler 100-120VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 200mA within 1ms (at 132VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 15ms or less (100VAC 50Hz, 60Hz) 20ms or less (100VAC 50Hz, 60Hz) 1780VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
1 2 3 4 5 6 7 8 9 A B C D E F COM NC 100VAC 8mA60Hz 7mA50Hz
0.17kg
120VAC 132VAC 10 20 30 40 50 55( C ) Ambient temperature
External connection
2-1
QX10 0 1 2 3 4 5 6 7 8 9 A B CDE F
50mA (TYP. all points ON)
Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0
Appearance
Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
2-1
2
Page 42
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.2 QX10-TS AC Input Module This module is a spring clamp terminal block type and an input module that has indicators for checking the insertion state of wire. Type Specifications
2
Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
AC input module QX10-TS 16 points Photocoupler 100-120VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 200mA within 1ms (at 132VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 15ms or less (100VAC 50Hz, 60Hz) 20ms or less (100VAC 50Hz, 60Hz) 1780VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) Two-piece spring clamp terminal block 0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1
012345 67 8 9 ABCDEF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
0.17kg
120VAC 132VAC 10 20 30 40 50 55( C ) Ambient temperature
External connection
2-2
QX10-TS
50mA (TYP. all points ON)
Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0
Appearance
Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
2-2
Page 43
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.3 QX28 AC Input Module Type Specifications Number of input points Isolation method Rated input voltage, frequency Input voltage distortion Rated input current Input derating Inrush current ON voltage/ON current OFF voltage/OFF current Input impedance OFF to ON Response time ON to OFF Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
AC input module QX28 8 points Photocoupler 100-240VAC (+10/-15%) 50/60Hz (±3Hz) Within 5% (Refer to section 1.2) Approx. 17mA (200VAC, 60Hz), approx. 14mA (200VAC, 50Hz) Approx. 8mA (100VAC, 60Hz), approx. 7mA (100VAC, 50Hz) Refer to the derating chart. Max. 950mA within 1ms (at 264VAC) 80VAC or higher/5mA or higher (50Hz, 60Hz) 30VAC or lower/1.7mA or lower (50Hz, 60Hz) Approx. 12kΩ (60Hz), approx. 15kΩ (50Hz) 10ms or less (200VAC 50Hz, 60Hz) 20ms or less (200VAC 50Hz, 60Hz) 2830VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 1500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP1X 8 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
NC 1 NC 2 NC 3 NC 4 NC 5 NC 6 NC 7 NC COM NC 200VAC 17mA60Hz 14mA50Hz
0.20kg
100% 45 C
Terminal block No. 100% 55 C 87.5% 55 C
10 20 30 40 50 55( C ) Ambient temperature
External connection
2-3
QX28 0 1 2 3 4 5 6 7
50mA (TYP. all points ON)
Derating chart (%) 100 90 ON 80 ratio 70 60 50 40 0
Appearance
240V 264V
Signal name
TB1
X00
TB2
Vacant
TB3
X01
TB4
Vacant
TB5
X02
TB6
Vacant
TB7
X03
TB8
Vacant
TB9
X04
TB10
Vacant
TB11
X05
TB12
Vacant
TB13
X06
TB14
Vacant
TB15
X07
TB16
Vacant
TB17
COM
TB18
Vacant
2-3
Page 44
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.4 QX40 DC Input Module (Positive Common Type) Type
DC input module (Positive common type)
Specifications
QX40
Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
Appearance
16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)
External connection
QX40 0 1 2 3 4 5 6 7 8 9 A B CDE F
1
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
1 2
1
3 4 5 6 7 8 9 A B C D E F - +
COM
NC 24VDC 4mA
50mA (TYP. all points ON) 0.16kg Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
1: For the setting method, refer to Section 1.3.1.
2-4
2-4
Page 45
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.5 QX40-S1 DC Input Module (Positive Common Type) Type Specifications Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Set value 1 TYP. Response OFF to ON MAX. time TYP. ON to OFF MAX. Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
DC input module (Positive common type) QX40-S1 16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA No 19V or higher/4.0mA or higher 11V or lower/1.7mA or lower Approx. 3.9kΩ 0.1 0.2 0.4 0.6 1 0.05ms 0.15ms 0.30ms 0.55ms 1.05ms 0.10ms 0.20ms 0.40ms 0.60ms 1.20ms 0.15ms 0.20ms 0.35ms 0.60ms 1.10ms 0.20ms 0.30ms 0.50ms 0.70ms 1.30ms 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point high-speed input module.) ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.)
External connection
Appearance
QX40-S1 0 1 2 3 4 5 6 7 8 9 A B CDE F
0
0 1 2 3 4 5 6 7 8 9 A B C D E F
1 2 3 4 5 6 7 8 9 A B C D E F - +
COM
NC 24VDC 6mA
60mA (TYP. all points ON) 0.20kg Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
1: Configured in PLC parameter. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW5D5C-GPPW or later). For the setting method, refer to Section 1.3.1.
2-5
2-5
Page 46
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.6 QX40-TS DC Input Module (Positive Common Type) This module is a spring clamp terminal block type and an input module that has indicators for checking the insertion state of wire. Type
DC input module (Positive common type)
Specifications
QX40-TS
Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections
Appearance
16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA No 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)
1
(Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter)
1
(Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 16 points/common (common terminal: TB17) 16 points (I/O assignment is set as a 16-point input module.) ON indication (LED) Two-piece spring clamp terminal block
Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight External connection
0.3 to 2.0mm2 core (22 to 15 AWG) Refer to section 9.1
QX40-TS 012 34 567 8 9 A B CDE F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
50mA (TYP. all points ON) 0.16kg Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
X08
TB10
X09
TB11
X0A
TB12
X0B
TB13
X0C
TB14
X0D
TB15
X0E
TB16
X0F
TB17
COM
TB18
Vacant
1: For the setting method, refer to Section 1.3.1.
2-6
2-6
Page 47
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.7 QX40H DC High-Speed Input Module (Positive Common Type) DC high-speed input module (Positive common type)
Type Specifications
QX40H
Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance SW1 (noise filter) 1 Set value 2 Response TYP. time OFF to ON MAX. TYP. ON to OFF MAX. Function SW2 4 setting Dielectric withstand voltage Insulation resistance Noise immunity
5
Protection degree Common terminal arrangement Number of occupied I/O points Interrupt processing condition Operation indicator External connections Applicable wire size Applicable crimping terminal Internal current consumption (5VDC) Weight
Appearance
16 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 6mA Refer to the derating chart. 13V or higher/3mA or higher 8V or lower/1.6mA or lower Approx. 3.9kΩ OFF
ON
Invalid 0ms 0ms -
3 3 3 3
0.1 0.04ms 0.05ms 0.04ms 0.05ms
0.2 0.10ms 0.15ms 0.10ms 0.15ms
0.4 0.25ms 0.30ms 0.25ms 0.30ms
0.6 0.50ms 0.60ms 0.50ms 0.60ms
1 0.95ms 1.00ms 0.95ms 1.00ms
OFF: Interrupt, ON: High-speed input 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency IP2X 8 points/common (common terminal: TB9, TB18) 16 points (I/O assignment is set as a 16-point high-speed input module or 16point interrupt module.) 4 Set by Switch setting in GX Developer 4 6 ON indication (LED) 18-point terminal block (M3 6 screws) 0.3 to 0.75mm2 core (2.8mm OD max.) R1.25-3 (Sleeved crimping terminals cannot be used.) 80mA (TYP. all points ON) 0.16kg
1: If the noise filter selector switch (switch 1) on the bottom of the module (refer to Chapter 10) is turned on, the noise filter takes effect. The off-status noise filter disables I/O response time setting. After switching on or off the switch 1, reset the power supply of the CPU module. 2: Set an input response time in "I/O response time" combo box of PLC parameter in GX Developer. (Default: 0.2ms) A response time setting value can be changed in GX Developer (SW6D5C-GPPW or later). For the setting details, refer to Section 1.3.1. 3: The actual response time is 5 s delay when turning on, 10 s delay when turning off, because the hardware response time is added. For the details of the CPU overhead time, refer to manuals for the CPU module used (Function Explanation, Program Fundamentals). 4: The module function can be changed according to the status of the function selector switch (switch 2) on the bottom of the module (refer to Chapter 10). ON: High-speed input OFF: Interrupt If the function selector switch (switch 2) setting is changed while the CPU module is in RUN, an error (error code: 2100) occurs. 5: Indicates the noise immunity when the noise filter takes effect (the noise filter selector switch (switch 1) is turned on). 6: For the setting method, refer to Section 1.3.3.
2-7
2-7
Page 48
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
Derating chart (%) 100 90 80 ON ratio/ 70 common 60 50 40 0
26.4VDC 28.8VDC
10 20 30 40 50 55 ( Ambient temperature
External connection
2-8
)
Terminal block No.
Signal name
TB1
X00
TB2
X01
TB3
X02
TB4
X03
TB5
X04
TB6
X05
TB7
X06
TB8
X07
TB9
COM1
TB10
X08
TB11
X09
TB12
X0A
TB13
X0B
TB14
X0C
TB15
X0D
TB16
X0E
TB17
X0F
TB18
COM2
2-8
Page 49
2 INPUT MODULE SPECIFICATIONS
MELSEC-Q
2.8 QX41 DC Input Module (Positive Common Type) Type Specifications
QX41 32 points Photocoupler 24VDC (+20/-15%, ripple ratio within 5%) Approx. 4mA Refer to the derating chart. 19V or higher/3mA or higher 11V or lower/1.7mA or lower Approx. 5.6kΩ 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 1ms/5ms/10ms/20ms/70ms or less (configured in PLC parameter) 1 (Default: 10ms) 560VAC rms/3 cycles (altitude 2000m) 10MΩ or more by insulation resistance tester By noise simulator of 500Vp-p noise voltage, 1 s noise width and 25 to 60Hz noise frequency First transient noise IEC61000-4-4: 1kV IP2X 32 points/common (common terminal: B01, B02) 32 points (I/O assignment is set as a 32-point input module.) ON indication (LED) 40-pin connector 0.088 to 0.3mm2 (For A6CON1 or A6CON4) 2
Number of input points Isolation method Rated input voltage Rated input current Input derating ON voltage/ON current OFF voltage/OFF current Input impedance Response time
DC input module (Positive common type)
OFF to ON ON to OFF
Dielectric withstand voltage Insulation resistance Noise immunity Protection degree Common terminal arrangement Number of occupied I/O points Operation indicator External connections Applicable wire size Applicable connector Applicable connector/terminal block converter module Internal current consumption (5VDC) Weight
QX41 0 1 2 3 4 5 6 7 8 9 A B CDE F 0 1 2 3 4 5 6 7 8 9 A B CDE F 24VDC 4mA
QX41
A6CON1, A6CON2, A6CON3, A6CON4 (optional) A6TBXY36, A6TBXY54, A6TBX70 75mA (TYP. all points ON) (0.08A is shown on the rating plate of the module.) 0.15kg
Derating chart (%) 100 90 80 ON ratio 70 60 50 40 0
Appearance
Pin-Outs
28.8VDC
10 20 30 40 50 55 ( C ) Ambient temperature
External connection
B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1
A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1
Pin No.
Signal No.
Pin No.
Signal No.
B20
X00
A20
X10
B19
X01
A19
X11
B18
X02
A18
X12
B17
X03
A17
X13
B16
X04
A16
X14
B15
X05
A15
X15
B14
X06
A14
X16
B13
X07
A13
X17
B12
X08
A12
X18
B11
X09
A11
X19
B10
X0A
A10
X1A
B09
X0B
A09
X1B
B08
X0C
A08
X1C
B07
X0D
A07
X1D
B06
X0E
A06
X1E
B05
X0F
A05
X1F
B04 Vacant A04 Vacant
Module front view
B03 Vacant A03 Vacant B02
COM
A02 Vacant
B01
COM
A01 Vacant
1: For the setting method, refer to Section 1.3.1. 2: When using A6CON2 or A6CON3, refer to Chapter 7.
2-9
2-9