Page 33

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1.2.4 I/O module with protection function The overload protection function and overheat protection function of the following modules are explained below. (1) QY40P, QY41P, QY42P, QX41Y41P, QH42P Function

Common (Overload and overheat protection functions)

Overload protection function Overheat protection function

Description • If an overcurrent due to overload keeps flowing, heat is generated and the overheat protection function is activated. • The functions are provided for protecting only the circuits inside the module. A load error, which causes an increase in temperature within the module, may deteriorate output elements or discolour the module case or printed circuit board. If a load error occurs, turn off the corresponding output immediately and eliminate the error cause. • The overload protection function is activated in units of 1 point at 1A to 3A/point. • The overload protection function returns to normal operation when the load becomes a rated load. • The overheat protection function is activated in units of 1 point. • The overheat protection function automatically returns to normal operation after heat reduces.

(2) QY81P, QY82P Function

Common (Overload and overheat protection functions)

Overload protection function

Overheat protection function

1 - 15

Description • If an overcurrent due to overload keeps flowing, heat is generated and the overheat protection function is activated. • The functions are provided for protecting only the circuits inside the module. A load error, which causes an increase in temperature within the module, may deteriorate output elements or discolour the module case or printed circuit board. If a load error occurs, turn off the corresponding output immediately and eliminate the error cause. • The overload protective function is activated in units of 1 point at 1A to 3A/point. • The overload protective function returns to normal operation when the load becomes a rated load. • The overheat protection function is activated in units of 2 points. (It is activated in units of 2 points of Y0/Y1, Y2/Y3, ..., and when overheat protection is activated, 2 points of them are activated simultaneously. If an overheat status persists, heat is conducted, and which may activate another overheat protection function.) • If an output turns on at the activation of the overheat protection function, the actual output voltage oscillates between 0V and load voltage. At the load voltage of 24V, the average voltage during oscillation is approx. 7V. No oscillation occurs when the output is off at the activation of the overheat protection function. To ensure that the output is turned off at the activation of the overheat protection function, use an external load that turns off at 7V or more. • The overheat protective function automatically returns to normal operation after heat reduces.

1 - 15

Page 34

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1.2.5 Interrupt module (1) If setting the response time during the interrupt input operation of QI60 or QX40H, QX70H, QX80H, and QX90H, use the module whose contents are shown below. The response time cannot be set with other contents (fixed at 0.2ms.). Product

Description

CPU module

Product information "021120000000000-B" or later

GX Developer

SW6D5C-GPPW or later

For how to check product information of the CPU module, refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection).

1.2.6 Installation and wiring (1) Solderless terminal with insulation sleeve A solderless terminal with insulation sleeve cannot be used for a terminal block. It is recommended that the junction of a solderless terminal and a cable should be covered up with a cable tag or an insulation tube. (2) Applicable wire Use wires of 0.3 to 0.75mm2 core and 2.8mm OD max. to connect to the terminal block. When using a wire whose core is 0.75mm or more, it is preferable to use the spring clamp terminal block (Q6TE-18S, Q6TE-18SN). (3) Tightening torque range Tighten screws (such as a module fixing screw) within the following torque range. Screw location

1 - 16

Tightening torque range

Module fixing screw (M3 12 screw)

0.36 to 0.48 N•m

Terminal block screw (M3 screw)

0.42 to 0.58 N•m

Terminal block mounting screw (M3.5 screw)

0.66 to 0.89 N•m

Connector screw (M2.6 screw)

0.20 to 0.29 N•m

1 - 16

Page 35

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1.3 Various Settings for I/O Module Various settings for the I/O module can be made with GX Developer. This section describes how to make the settings with GX Developer.

1.3.1 Setting of I/O response time Set the I/O response time on the I/O assignment tab of PLC Parameter. (1) For Input/I/O mix module Select "Input" or "I/O mix" in "Type" combo box on the I/O assignment tab of PLC parameter. Then, click the "Detailed setting" button, and then select the input response time in "I/O response time" combo box. Choose Input/I/O mix.

Choose Detailed setting.

Choose I/O response time (default: 10ms).

1 - 17

1 - 17

Page 36

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(2) For input module/QX40-S1, QX41-S1, QX42-S1, QX82-S1 and interrupt module/QI60 Select "Hi. input" or "Interrupt" in "Type" combo box on the I/O assignment tab of PLC parameter. Then, click the "Detailed setting" button, and then select the input response time in "I/O response time"*1 combo box. Choose Hi. input/Interrupt.

Choose Detailed setting.

Choose I/O response time (default: 0.2ms).

*1: When the actual response time differs from the setting value, refer to the specifications of the relevant input modules.

1 - 18

1 - 18

Page 37

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(3) For high-speed input module/QX40H, QX70H, QX80H, QX90H Select "Hi.input" or "Interrupt", which is the same module type as the one selected with the high-speed input module switch, in "Type" combo box on the I/O assignment tab of PLC parameter.*1 Then, click the "Detailed setting" button, and then select the input response time in "I/O response time"*2 *3 combo box. Choose Hi. input/Interrupt.

Choose Detailed setting.

Choose I/O response time (default: 0.2ms).

*1: If a different module type from the one selected by the function selector switch (switch 2) of the high-speed input module is selected, an error occurs. *2: If the noise filter is disabled with the noise filter selector switch (switch 1) of the high-speed input module, the setting value is ignored. *3: When the actual response time differs from the setting value, refer to the specifications of the relevant input modules.

1 - 19

1 - 19

Page 38

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1.3.2 Setting of error-time output mode Set the error-time output mode on the I/O assignment tab of PLC parameter in GX Developer. Select "Output" or "I/O mix" in the "Type" combo box on the I/O assignment tab of PLC parameter. Then, click the "Detailed setting" button, and then select "Clear" or "Hold" in the "Error time output mode" combo box. Choose Output/I/O mix.

Choose Detailed setting.

Choose Clear/Hold (default: Clear).

1 - 20

1 - 20

Page 39

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1.3.3 Switch setting of interrupt module Perform the switch setting on the I/O assignment tab of PLC parameter when operating the interrupt input for QI60, QX40H, QX70H, QX80H, or QX90H. Select "Interrupt" in the "Type" combo box on the I/O assignment tab of PLC parameter. Then, click the "Switch setting" button, and then select "HEX" in the "Input format" combo box. Lastly, set 0 (leading edge) or 1 (trailing edge) in the "Switch 1" box for the interrupt processing. Choose Interrupt.

Choose Switch setting.

Choose HEX.

Set the interrupt processing conditions Setting inhibited. (leading edge/trailing edge) of CH1 to CH16.

Set the interrupt processing condition with switch 1. The relationships between bits and inputs are as indicated below. b15 XF to XE

XD

XC

XB

XA

X9

X8 b0 X7

X6

X5

X4

X3

X2

X1

X0

0: Leading edge, 1: Trailing edge 1 - 21

1 - 21

Page 40

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

MEMO

1 - 22

1 - 22