Page 25
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
Operating environment
Switching life
Rated switching voltage/current load 200VAC 1.5A, 240VAC 1A (COS
MELSEC-Q
100 thousand times
=0.7)
100 thousand times
200VAC 0.4A, 240VAC 0.3A (COS
=0.7)
300 thousand times
200VAC 1A, 240VAC 0.5A (COS
=0.35)
100 thousand times
200VAC 0.3A, 240VAC 0.15A (COS
=0.35)
300 thousand times
24VDC 1A, 100VDC 0.1A (L/R=7ms)
100 thousand times
24VDC 0.3A, 100VDC 0.03A (L/R=7ms)
300 thousand times
POINT When using the module for the application in which the relay contact is frequently switched, the relay life span should be considered. It is recommended to use a triac output module.
1-7
1-7
Page 26
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(b) Measures against inrush current The actual relay life may be significantly shortened compared to the one shown in (7)(a), depending on the type of a load connected and the characteristics of inrush current. Also, the inrush current may cause contact welding. Take the following measures to prevent shortening of the relay life and the contact welding. • Select a load so that the inrush current will be within the rated current of the module. • Connect an external relay that can withstand the inrush current. The following table shows the relation between the load and the inrush current. Select a load so that the inrush current (i) and the rated current (io) will be within the rated switching current specified for the output module used. The inrush current may flow for a longer time depending on the load. Inrush Load type
Signal waveform diagram current(i)/rated
Inrush Signal waveform diagram current(i)/rated current (io)
current (io)
Inductive
Approx. 10 to
Approx. 3 to load
20 times
10 times
Approx. 3 to
Approx. 3
10 times times*1
Lamp load
Approx. 5 to 10 times
―
―
(To the next page) *1: Typical electric-discharge lamp circuit includes discharge tubes, transformers, choke coils, and capacitors. Therefore, note that the inrush current may flow 20 to 40 times as large as the rated current in the case of high power factor and low power impedance.
1-8
1-8
Page 27
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
Inrush Load type
Signal waveform diagram current(i)/rated
Inrush Signal waveform diagram current (io)
Capacitive
Approx. 20 to load
40 times
MELSEC-Q current(i)/rated current (io)
―
―
*2: When the wiring of the circuit is long, take care of the wire capacity.
1-9
1-9
Page 28
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(c) Measures against back EMF Configure a contact protection circuit for extending the contact life, preventing noise when the contact is cut off, and suppressing the generation of carbide and nitric acid due to arc discharge. An Incorrect contact protection circuit may cause contact welding. Also, when using the contact protection circuit, the recovery time may be long. The following table shows the representative examples of the contact protection circuit.
Circuit example
Method for selecting elements
Remarks
Capacitor +
Refer to the following for
If a load is from a relay or
Resistor method constants of the capacitor and solenoid, the recovery time
(CR method)
resistor. Note that the delays.
following values may differ
A capacitor suppresses depending on a nature of the electric discharge while a load and a variation of contact is off, and a resistor characteristics of it.
restricts a flow of current
• Capacitor 0.5 to 1 ( F)
while a contact is on.
against contact current of 1A • Resistor 0.5 to 1 (Ω)against contact voltage of 1V Use a capacitor whose withstand voltage is 200 to 300V. In AC circuit, use a capacitor having no polarity. Diode method
Use a diode whose reverse
The recovery time is later breakdown voltage is 10 times than the CR method.
as high as the circuit voltage or more and whose forward current is twice as high as the load current or more. Diode + Zener
Use zener voltage for the
The diode method is effective diode method zener diode equal to or more when the recovery time is too than the power supply late.
voltage.
*1: When using AC power, impedance of CR must be larger enough than that of the load. (prevention of a malfunction due to leak current from the CR) (To the next page)
1 - 10
1 - 10
Page 29
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
Circuit example Varistor method
MELSEC-Q
Method for selecting elements
Remarks
Select a cut voltage (Vc) for
The recovery time delays the varistor to meet the slightly.
following condition. Multiply the value by root two for use of AC power. Vc Power supply voltage 1.5 (V) Note that when selecting an element whose Vc is too high, its effect will weaken.
POINT (1) Avoid providing contact protection circuits shown below. These circuits are effective for preventing an arc at shut-off. However, the contact welding may occur because the charge current flows to capacitor when the contact turns on or off. A DC inductive load is usually harder for switching than a resistor load, but if a proper protection circuit is configured, the performance will be similar to the resistor load.
(2) A protection circuit must be provided closely to a load or contact (module). If their distance is far, the protection circuit may not be effective. Appropriate distance is within 50cm.
1 - 11
1 - 11
Page 30
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
(8) Precautions for using the triac output module Because of characteristics of a triac, a sudden change of voltage or current may cause unstable operations of a triac used for the triac output module. Whether the voltage or current change causes a problem differs depending on an individual part (each triac), thus check the following when using the triac output module. (a) Checking of the load current When the current consumption is equal to or smaller than the minimum load current and the margin is low by using an inductive load such as a solenoid valve, a triac may not turn on or off properly. In that case, an action such as connecting a bleeder resistance is required. For detail on actions, refer to Section 11.2. (b) Precautions on a full-wave rectifier load The load current of a full-wave rectifier load forms waves similar to rectangular waves as shown below.
A triac may not operate properly if the current forms rectangular waves associated with sudden current changes. To avoid it, use a load with which the load current does not form rectangular waves. (c) Measures for connecting an inductive load To connect an inductive load, take measures to reduce noise to the side where the load is connected as shown below.
Circuit example Varistor method
Method for selecting elements
Remarks
Select a cut voltage (Vc) for
The recovery time delays the varistor to meet the slightly.
following condition. • Vc > Power supply voltage 1.5(V)
√2
This method is not effective when the Vc is too high.
1 - 12
1 - 12
Page 31
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
Circuit example
MELSEC-Q
Method for selecting elements
Remarks
Capacitor +
Refer to the following for
If a load is a relay or
Resistor constants of the capacitor and solenoid, the recovery time method (CR resistor. Note that the following delays.
method)
values may differ depending on a nature of the load and a variation of characteristics of it. • Capacitor: 0.5 to 1 ( F) against load current of 1A • Resistor: 0.5 to 1(Ω) against power supply voltage of 1V Use a capacitor whose withstand voltage is equal to or more than the rated voltage. Use a capacitor having no polarity.
(d) Measures for connecting an inductive load (when installing a contact between the load and the output terminal) To install a contact (such as an interlock) between the load and the output terminal, take measures to reduce noise as shown below. Though measures (varistor method, capacitor + resistor method) are normally taken to the load side, in some cases, it is more efficient to take the measures to the module side considering the contact effect.
Varistor method
Circuit example
Method for selecting elements
Remarks
• Measure taken to the load side
Select a cut voltage (Vc) for
The recovery time delays the varistor to meet the slightly.
following condition. • Vc > Power supply voltage 1.5(V)
√2
This method is not effective • Measure taken to the module side
1 - 13 when the Vc is too high.
1 - 13
Page 32
1
GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE
MELSEC-Q
1.2.3 I/O combined module (1) I/O numbers of I/O combined modules There are two types of I/O combined modules: • Module using same I/O numbers for input and output Since same number is used for input and output, the I/O numbers to be used can be saved. • Module using sequential I/O numbers for input and output Since I/O assignments are the same for A series, it is useful when replacing modules from those of A series.
00
Input (X)
Output (Y)
X00
Y00
Input (X) 00
X00
1F
X1F
32 points 1F
X1F
Output (Y) 32 points
Vacant
Y1F
Y20
20
32 points
Vacant 3F
Y3F
Module using same I/O numbers for input
Module using sequential I/O numbers for input and output (QH42P)
and output (QX41Y41P)
(2) Configuration of when an I/O combined module is used For the QH42P, QX41Y41P, and QX48Y57, use them in the configuration below. Product CPU module
Description The module whose serial number (first 5 digits) is "01112" or later
Precautions • Use it with "Output" being set to
SW4D5C-GPPW or earlier GX Developer the I/O assignment. • Input response time cannot be set. (fixed at 10ms)
SW5D5C-GPPW or later
Use it with "I/O combined" being set to the I/O assignment.
For how to check the serial number of the CPU module, refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection).
1 - 14
1 - 14