Page 17

ABOUT MANUALS The following manuals are also related to this product. In necessary, order them by quoting the details in the tables below. Related Manuals Manual Number (Model Code)

Manual Name QCPU User's Manual (Hardware Design/Maintenance and Inspection) This manual provides the specifications of the CPU modules, power supply modules, base units, extension cables, memory cards and others.

(Sold separately)

QnUCPU User's Manual (Function Explanation/Program Fundamentals) This manual explains the functions, programming methods, devices on necessary to create programs with the QnUCPU.

SH-080483ENG (13JR73)

SH-080807ENG (13JZ27)

(Sold separately)

Qn(H)/QnPH/QnPRHCPU User's Manual (Function Explanation/Program Fundamentals) This manual explains the functions, programming methods, devices on necessary to create programs with the Qn(H)/QnPH/QnPRHCPU.

SH-080808ENG (13JZ28)

(Sold separately)

COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES (1) Method of ensuring compliance To ensure that Mitsubishi Electric programmable controllers maintain EMC and Low Voltage Directives when incorporated into other machinery or equipment, certain measures may be necessary. Please refer to one of the following manuals. • QCPU User's Manual (Hardware Design, Maintenance and Inspection) • Safety Guidelines (This manual is included with the CPU module or base unit.) The CE mark on the side of the programmable controller indicates compliance with EMC and Low Voltage Directives.

(2) Additional measures No additional measures are necessary for the compliance of this product with EMC and Low Voltage Directives.

A - 15

A - 15

Page 18

MEMO

A - 16

A - 16

Page 19

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

1. GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE This chapter describes the general specifications and precautions for use of the I/O modules.

1.1 General Specifications Refer to the following manual for the general specifications of the I/O modules. • QCPU User's Manual (Hardware Design, Maintenance and Inspection)

1.2 Precautions for Use 1.2.1 Input module (1) Simultaneous ON points The number of simultaneous on points of input module depends on the input voltage and ambient temperature. Refer to the derating chart of the input module specifications. (2) Input response time and pulse width Input modules may take in noise or the like as an input depending on the pulse width of a signal. This pulse width has a value as listed below depending on the parameter-set response time. Set input response time while fully consider the operating environment. Minimum value of pulse width Response time setting value (ms)

where noise or the like may be taken in as an input (ms)

1

0.3

5

3

10

6

20

12

70

45

For the setting of input response time values, refer to Section 1.3.1.

1-1

1-1

1

Page 20

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(3) Precautions for using the DC input module (a) Measure against back EMF When an inductive load is connected, connect a diode to the load in parallel. Use a diode that meets the following conditions. • Reverse breakdown voltage is 10 times as high as the circuit voltage or more. • Forward current is twice as high as the load current or more.

1

(4) Precautions for using the high-speed input module Read the following precautions carefully when using the high-speed input modules (QX40H, QX70H, QX80H, and QX90H). (a) When switching to the high-speed input, the specifications of the high-speed input modules and the input module QX40-S1 are identical. On the other hand, when switching to the interrupt input, the specifications of the highspeed input modules and the interrupt module QI60 are identical too. Therefore, the specifications of the input module (QX40-S1) are construed as the specifications of the high-speed input module switched to the high-speed input. Similarly, the specifications of the interrupt module (QI60) indicated in the manuals other than this manual are construed as the specifications of the high-speed input module switched to the interrupt input. (b) By using setting switches on the bottom of the module (refer to Chapter 10), the high-speed input module switches module types (high-speed input or interrupt input) for 16 input points all together and between valid and invalid noise filters as shown below. Noise filter (Switch 1) ON OFF

GX Developer setting

Function selector switch selector switch (Switch 2)

Module type

ON

High-speed input*1

OFF

Interrupt*1

ON

High-speed input *1

OFF

Interrupt*1

Interrupt operation

Input response time

*2

: Settable : Not settable *1: When selecting an improper module type, an error (error code: 2100) occurs. *2: The input response time value set in GX Developer is ignored.

1-2

1-2

Page 21

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(c) If the small number of value of input response time is set, the modules tend to have impact of noise. Ensure that the modules do not have impact of noise. For details of the measure against noise, refer to the QCPU User’s Manual (Hardware Design, Maintenance and Inspection). (d) The high-speed input modules connected with electric appliance such as relays may load a chattering as a signal. (e) To use a high-speed input module as a CE marked product, keep the cable length 3m or less.

1.2.2 Output module (1) Maximum switching frequency when the module drives inductive load The output must be on for one second or longer and off for one second or longer. (2) Load for connection When connecting a counter or timer that has a DC-DC converter as a load, select an output module whose maximum load current is larger than inrush current of the load. Selecting an output module by average current of the load may cause a failure of the module because inrush current flows at a constant frequency at power-on or during operation due to the connected load. If an output module needs to be selected by average current of the load, take either of the following actions to reduce an influence from inrush current.

• Connecting a resistor to the load in series

• Connecting an inductor to the load in series

(3) Replacement of fuses Fuses installed to an output module cannot be replaced. (4) Built-in fuses Built-in fuses works to prevent the external cables from being burned when a short circuit occurs in the internal output circuit. For this reason, the output module may not be protected if the fuses blow any other reasons except for a short circuit.

1-3

1-3

Page 22

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(5) Fuses installed to external terminals It is recommended to install fuses to each external terminal. These fuses works to prevent the external devices and the module from being burned when a short circuit occurs in the load circuit of the QY22 or QY68A. The following table lists the fuses whose operations have been checked and ensured by Mitsubishi. QY22*1

Module model

QY68A*2

Fuse model

216 02.5

216 002

216 3.15

312 003

Rated current

2.5A

2A

3.15A

3A

Manufacturer

Littelfuse, Inc

*1: Fuses that conform to Sheet 1 of IEC60127 are recommended. *2: Fast blow fuses whose rated current is 3A are recommended. (6) Precautions for using the transistor output module (a) Action against reverse current If a transistor output module is wired as shown below, reverse current flows in an output element, causing a failure of the element. When wiring a transistor output module, connect a diode as shown below. • When connecting transistor output modules in parallel

Sink type

Source type

• When incorporating an additional circuit parallel to a transistor output module Additional circuit

OUT

Additional circuit

OUT Diode

COM

COM Sink type

1-4

Diode

Source type

1-4

Page 23

1

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(b) Measure against back EMF When an inductive load is connected, connect a diode to the load in parallel. Use a diode that meets the following conditions. • Reverse breakdown voltage is 10 times as high as the circuit voltage or more. • Forward current is twice as high as the load current or more.

1-5

1-5

Page 24

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

MELSEC-Q

(7) Precautions for using the contact output module When using the contact output module, consider the following. • Relay life (contact switching life) • Effects to relay life due to connected load • Measures against back EMF (a) Relay life Applicable module: QY10, QY10-TS, QY18A The relay life depends on the operating environment. Select a module according to the operating environment. The relay lives shown below are the actual service values, not the guaranteed values. Replace the module well in advance since the actual switching life may be shorter than the one shown below.

200

100 70

Switching life (10,000 times)

1

50

30

20

10 7 30VDC =0ms

5 100VDC =7ms

100VAC cos =0.7 200VAC cos =0.7

3 (L/R): Time constant cos : Power factor

100VAC cos =0.35 200VAC cos =0.35 24VDC =7ms

2

120VAC cos =0.2 240VAC cos =0.2

1 0.1

0.2

0.3

0.5

0.7

1

2

3

5

Switching current (A)

1-6

1-6