I/O Module Type Building Block User's Manual, pages 110 to 118

Pages 110 to 118 of 158: 7. CONNECTORS; 8. SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Mitsubishi QG60 and Mitsubishi QX42

Page 110

7 CONNECTORS

MELSEC-Q

7. CONNECTORS The 40-pin connectors and 37-pin D-sub connectors used with the input and output modules are to be user-prepared. The following tables list the connector types and applicable models, and introduce crimp-contact and pressure-displacement tools.

(1) 40-pin connectors (a) 40-pin connectors Type

Model name

Applicable wire size

Applicable model

2

Soldering type connector

A6CON1

(straight out type)

*1

0.088 to 0.3mm

(28 to 22 AWG) (stranded wire) 2

2

0.088mm to 0.24mm

Crimp-contact type connector

A6CON2

(straight out type)

(28 to 24 AWG)

QX41-S2, QX42,

(stranded wire)

Pressure-displacement type connector (straight out type)

28 AWG (stranded wire) A6CON3

30 AWG (single wire) Flat cable 1.27mm pitch

Soldering type connector

QX41, QX41-S1, QX42-S1, QX71, QX72, QX82, QY41H, QY41P, QY42P, QY71, QY82P, QH42P, QX41Y41P

2

(both for straight out and 45-degree

A6CON4

*1 types)

0.088 to 0.3mm (28 to 22 AWG) (stranded wire)

*1: Use cables with outside diameter of 1.3mm or shorter to connect 40 cables to the connector. In addition, consider the amount of current to be used and select appropriate cables.

(b) 40-pin connector crimp-contact and pressure-displacement tools

7

Type Crimp-contact tool

Model name

Contact

FCN-363T-T005/H FCN-367T-T012/H (locator plate)

Pressure-displacement tool

FCN-707T-T001/H (cable cutter)

FUJITSU COMPONENT LIMITED

FCN-707T-T101/H (hand press)

7-1

7-1

Page 111

7 CONNECTORS

MELSEC-Q (2) 37-pin D-sub connectors (a) 37-pin D-sub connectors

Type

Model name

Applicable wire size

Applicable model

2

Soldering type connector

*1

A6CON1E

(straight out type) Crimp-contact type connector

A6CON2E

(straight out type) Pressure-displacement type connector (straight out type)

A6CON3E

0.088 to 0.3mm

(28 to 22 AWG) (stranded wire) 24 to 20 AWG (stranded wire)

QX81, QX81-S2, QY81P

28 AWG (stranded wire) 30 AWG (single wire)

*1: Use cables with outside diameter of 1.3mm or shorter to connect 37 cables to the connector. In addition, consider the amount of current to be used and select appropriate cables.

(b) 37-pin D-sub connector crimp-contact and pressuredisplacement tools Type Crimp-contact tool

Model name

Contact

91503-1

768349-1 (die set) 768338-1

Pressure-displacement tool

91220-1 (cable cutter)

Tyco Electronics AMP K.K.

91085-2 (hand minipress)

7-2

7-2

7

Page 112

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

MELSEC-Q

8. SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES 8.1 Specifications of Connector/Terminal Block Converter Modules This chapter explains the specifications of connector/terminal block converter modules.

(1) Connector/terminal block converter module Type

Weight

0.4kg

For positive common type input A6TBXY54 modules and sink type output modules (2-wire type)

0.5kg

For positive common type input modules (3-wire type)

For negative common type input modules (standard type) For negative common type input A6TBX54-E modules (2-wire type) For negative common type input A6TBX70-E modules (3-wire type) For source type output modules A6TBY36-E (standard type) For source type output modules A6TBY54-E (2-wire type) A6TBX36-E

8-1

Applicable wire size

Applicable crimping terminal

Applicable Models Q series

For positive common type input A6TBXY36 modules and sink type output modules (standard type)

A6TBX70

8

Details

0.6kg

0.75 to 2 2mm

1.25-3.5(JIS) 1.25-YS3A V1.25-M3 V1.25-YS3A 2-3.5(JIS) 2-YS3A V2-S3 V2-YS3A

QX41, QX41-S1, QX41-S2, QX42, QX42-S1, QY41H, QY41P, QY42P, QY82P, QH42P, QX41Y41P AnS series A1SX41, A1SX41-S1, A1SX41-S2, A1SX42, A1SX42-S1, A1SX42-S2, A1SX82-S1, A1SY41, A1SY41P, A1SY42, A1SY42P, A1SY82, A1SH42, A1SH42P, A1SH42-S1, A1SH42P-S1 A series AX42, AX42-S1, AY42, AY42-S1, AY42-S3, AY42-S4, AH42 CC-Link AJ65SBTCF1-32D, AJ65SBTCF1-32T, AJ65BTC1-32D, AJ65BTC1-32T MELSECNET-MINI AJ35TC1-32D, AJ35TC1-32T Q series QX41, QX41-S1, QX41-S2, QX42, QX42-S1, QH42P, QX41Y41P AnS series A1SX41, A1SX41-S1, A1SX41-S2, A1SX42, A1SX42-S1, A1SX42-S2, A1SX82-S1, A1SH42, A1SH42P, A1SH42-S1, A1SH42P-S1 A series AX42, AX42-S1, AH42 CC-Link AJ65SBTCF1-32D, AJ65BTC1-32D MELSECNET-MINI AJ35TC1-32D

0.4kg 0.5kg

Q series QX81, QX81-S2 AnS series A1SX81, A1SX81-S2 A series AX82

0.6kg 0.4kg 0.5kg

Q series QY81P AnS series A1SY81 A series AY82EP

8-1

Page 113

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

MELSEC-Q

POINT (1) The number of connectable I/O points is 32 for all connector/terminal block converter modules. Two connector/terminal block converter modules and two cables for connector/terminal block converter modules are required for 64-point I/O modules. (2) Though the A1SX81(S2) is used either as a sink or source type, use the A6TBX36-E, A6TBX54-E or A6TBX70-E. The A6TBXY36, A6TBXY54 or A6TBX70 cannot be used. (3) Though the A1SX82-S1 is used either as a sink or source type, the A6TBXY36/XY54/X70 may be used only when the A1SX82-S1 is used as a sink type. When it is used as a source type, the A6TBXY36/XY54/X70 cannot be used. (4) Though the A1SY82 and QY82P are source type output modules, use the A6TBXY36 or A6TBXY54. The A6TBY36-E or A6TBY54-E cannot be used. (5) In the A series, the positive common input module is separately labeled as a sink type input module, and the negative common input module is separately labeled as a source type input module. (6) When using the A6TBX70 as I/O combined module, use at the input side. (7) Tighten the module terminal screws to the following torque. Terminal screw (M3.5 screw): Tightening torque 0.78N•m

(2) Cable Type AC05TB AC10TB AC20TB AC30TB AC50TB AC80TB AC100TB AC05TB-E AC10TB-E AC20TB-E AC30TB-E AC50TB-E

8-2

Details 0.5 m, for sink modules 1 m, for sink modules 2 m, for sink modules 3 m, for sink modules 5 m, for sink modules 8 m, for sink modules (common current not exceeding 0.5 A) 10 m, for sink modules (common current not exceeding 0.5 A) 0.5 m, for source modules 1 m, for source modules 2 m, for source modules 3 m, for source modules 5 m, for source modules

Weight 0.17kg 0.23kg 0.37kg 0.51kg 0.76kg 1.2kg

Applicable Models

A6TBXY36 A6TBXY54 A6TBX70

1.5kg 0.17kg 0.23kg 0.37kg 0.51kg 0.76kg

A6TBX36-E A6TBY36-E A6TBX54-E A6TBY54-E A6TBX70-E

8

8-2

Page 114

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

MELSEC-Q

8.2 Connector/terminal block converter module connection diagrams 8.2.1 A6TBXY36 (1) When connecting an input module

(2) When connecting an output module (a) Sink type

(b) Source type

8-3

8-3

Page 115

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

MELSEC-Q

8.2.2 A6TBXY54 (1) When connecting an input module

(2) When connecting an output module (a) Sink type

(b) Source type

8-4

8-4

Page 116 read from a scan by OCR; it may hold reading errors

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER

MELSEC-Q

MODULES

8.2.3 A6TBX70

24VDC

| 3-wire type sensor | | 2-wire type sensor | iH

14

TE nT

| - ¢ ic i i cc a ce a J Lh ful GG

|<

8.2.4 A6TBX36-E li 11 13 15 17 19 1B 1D 1F ov 10 12 14 16 18 JA ic iE 24V)

Page 117 read from a scan by OCR; it may hold reading errors

MELSEC-Q

Load

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER MODULES

8.2.5 A6TBY36-E

Tyo be] Bfe [ofa cle le fe bey

+ ain

8

6

+6)

5 |e | 7

4

TT]

[i 11 13 15 17 19 1B 1D 1F ov 10 12 14 16 18 1A 1¢ iE AV

2

S[aaapopeonroopopaeyreqeqayy - oo] TT TT TT TTT |

+0)

2-wire type sensor i)

Aaaa

J] TTT lecleal Im leololvalual

8.2.6 A6TBX54-E

1E +C OV!

19[6 RB 1B 1D +C 1A icy +c

18

15/6 Lo 17 +C 16

14 li 1176 Lo 13 10 +C) 12

Page 118 read from a scan by OCR; it may hold reading errors

8 SPECIFICATIONS OF CONNECTOR/TERMINAL BLOCK CONVERTER

MELSEC-Q

MODULES

8.2.7 A6BTBY54-E

1E -G lov.

-<C ic

JA

-C

19/6 1B 1D

18

16

<C

15 H.0| 17

14

Pete e le obo ole bel lel bobs le ke +] 1}¢ 10] 3 5 {+ to| 7 2+ }o| B Die {c| F L¢ bavi

12

-C

11 || 13

TT

Gf i i a WU) Teslcolealm rte ol val ual el io lS cleat clei etc cer ees teste

8.2.8 A6TBX70-E

[ 3-wire type sensor | | 2-wire type sensor yey

Ed

Input Module ca} <<fca) <x {cnx {cn <c{en)<c|en|<x|en) <c|en|<c{enl<c|on|<<|on|<c|ea}<c|oa|<clon}<c|oa|<c|oa}<c|on|<clon|<c|oa}<c|oa|<c

Das bi Pad Pf DP PB Bs DD Mi i IN) NN i Ba al a i le a le a le il a il