Page 1

Modicon 512/612 Micro PLC Hardware User Manual 890 USE 145 00 Ver 1.0

1

Page 2

Contents General Hardware Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Hardware Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PLC Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Memory Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Memory Backup Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General Hardware Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 The I/O Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 The J1 and J2 Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Wiring External Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 PLC Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Comm Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 A120 I/O Expansion Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Fixed Analog I/O in the 612 Models . . . . . . . . . . . . . . . . . . . . . . . . . 10 Base Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Optional Hardware Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Partial Sampling of Available A120 I/O Modules . . . . . . . . . . . . . . . 17 Fixed I/O Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 115 VAC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 230 VAC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 24 VDC Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 User-selectable High-speed Counter/interrupt Inputs . . . . . . . . . . 29 Dedicated High-speed Interrupt Inputs . . . . . . . . . . . . . . . . . . . . . . . 31 Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Triac Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 24 VDC (FET) Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Mounting Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Installing the Optional Battery or Battery Capacitor . . . . . . . . . . . . . . . 48 Serial I/O Expansion Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Terminating the Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 A120 I/O Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Calculating Power Requirements in an A120 I/O Expansion System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 A120 I/O Expansion Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Connecting the PLC to a Programming Panel . . . . . . . . . . . . . . . . . . . . 56 RS-232 Cable Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 RS-232 Cable Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

890 USE 145 00

512/612 Modicon Micro PLCs

1

Page 3

General Hardware Characteristics Hardware Characteristics On-board CPU, memory, fixed I/O circuitry, and power supply 16 MHz CPU speed for handling I/O throughput A built-in time-of-day clock A parallel expansion port for up to three racks of A120 I/O modules 24 VDC high-speed inputs that can be configured to operate as dedicated hardware interrupts and/or a user-configurable counter/timer/interrupt input Two RS-232 ports, comm 1 and comm 2, for communication with programming devices and with ASCII input/display devices

2

Customer Part Number

Power Supply

Fixed I/O Resources

110CPU51200

24 VDC

16 (24 VDC) in 12 relay out

110CPU61200

24 VDC

16 (24 VDC) in 12 relay out 4 analog in 2 analog out

110CPU51201

115 VAC

16 (115 VAC) in 8 triac out 4 relay out

110CPU51202

230 VAC

16 (230 VAC) in 8 triac out 4 relay out

110CPU51203

24 VDC

16 (24 VDC) in 12 (24 VDC) FET out

110CPU61203

24 VDC

16 (24 VDC) in 12 (24 VDC) FET out 4 analog in 2 analog out

110CPU61204

24 VDC

16 (24 VDC) in 12 relay out 4 analog in 2 analog out

512/612 Modicon Micro PLCs

Comm 2 of 61204 (only) supports Modbus master XMIT block. Default condition is slave. XMIT enabled permits port to be temporary Modbus master ASCII or RTU mode. Comm 1 or Comm 2 of 512xx and 612xx supports comm block, which is Modbus master ASCII only. An RS-485 port for serial I/O expansion with other Modicon Micro PLCs The 612 models also support four analog input channels and two analog output channels. The AC units (Models 51201 and 51202) have an on-board 24 VDC power supply that provides 150 mA. This supply is suitable for driving the hardware interrupts or the 24 VDC I/O points in an AC environment.

890 USE 145 00

Page 4

PLC Operating Modes The PLCs can operate in any one of three modes:

+

--

As a single PLC - i.e., a stand-alone programmable control system As a parent PLC on an I/O expansion link - with the ability to access the fixed I/O resources of the PLC(s) in child operating mode on the link As a child PLC whose fixed I/O resources can be accessed by the parent on an I/O expansion link Note Whenever A120 I/O is used in a child PLC, the logic that controls the A120 I/O must be run in the child. A parent cannot access the A120 I/O connected to a child - it can access only fixed I/O resources of its children.

Memory Resources 128 kbytes of RAM 2048 words available for program memory 2048 words of data memory 110CPU61204 PLC has 8192 words of user data memory Note The execution buffer is large enough to load the XMIT loadable or the Gas loadable without reducing the 8K of available user logic.

Memory Backup Options User memory - for the system configuration and application program - can be backed up in three ways: Using an optional (110XCP98000) lithium battery assembly

890 USE 145 00

110XCP98000 Lithium Battery Assembly

Using an optional (110XCP99000) battery capacitor assembly Capacitor Resistor

-+

Label

110XCP99000 Battery Capacitor Assembly

Writing the information to a reserved area in the PLC’s Flash RAM The optional lithium battery or battery capacitor will automatically back up the current user memory in the event of a power shutdown. The battery can safely back up the data for one year. The battery capacitor can back up a typical user logic program for 72 hr. Note The 110XCP990000 battery capacitor must be charged in a powered-up PLC for at least 24 hours to assure full memory backup. The ability to back up user memory by writing it to Flash RAM is a standard feature of all Micro PLCs, except the 61204. Because of limitations of Flash storage capabilities in 61204, a battery is the only method available to backup user memory. Memory backed up in Flash remains completely nonvolatile over time.

512/612 Modicon Micro PLCs

3

Page 5

If you are using Flash RAM backup, save the changes you make in your program and/or system configuration at the end of each edit session. The Save to Flash command is issued from your panel software. Whenever PLC power is lost and then restored, the system firmware first attempts to restore any battery-backed memory. If there is no battery-backed memory, then it will restore any configuration and/or programming information stored in Flash - remember that information in Flash is only as current as the last time you issued a Save to Flash command. If there is no user memory saved in Flash, the firmware will assign the PLC a set of default configuration parameters and no logic program will exist.

4

512/612 Modicon Micro PLCs

890 USE 145 00

Page 6

General Hardware Overview Front View of a 512 PLC* Terminal block for fixed discrete and hardwired inputs Captive screw for the input terminal block

Captive screw for the input terminal block

Battery cover PLC status display with LED indicators

Five terminal screws for external power connection J1 screw for signal ground-to-chassis ground

J2 screw for 120 of the PLC Captive screw for the output terminal block

W termination

Captive screw for the output terminal block

Terminal block for fixed discrete outputs

* The 612 PLC has an additional set of terminal blocks for analog I/O (see page 11).

The I/O Terminal Blocks The terminal block at the top of the PLC provides screw terminal connections for the 16 fixed discrete inputs and the high-speed interrupt and counter/timer/ interrupt inputs. The terminal block at the bottom of the PLC provides screw terminal connections for the fixed discrete outputs (groups of relay, triac, and/or FET outputs).

890 USE 145 00

To make field wiring easier, terminal blocks can be removed from the PLC base. To remove a terminal block, loosen the two captive screws on the left and right of the block with a slotted screwdriver until they spring free of their mating pieces in the unit base. Then use the screwdriver to pop the block out of the PLC base.

512/612 Modicon Micro PLCs

5

Page 7

Use a Philips #2 screwdriver to make the field wire connections to the terminal screws, then push the terminal blocks back on the PLC base.

The J1 and J2 Screws Two factory-set screws are installed on the front of the unit. The J1 screw is located below the power connectors on the left front of the unit, and the J2 screw is located below the PLC status display on the right front of the unit. The position of the J1 screw in the PLC housing determines whether there is conventional signal ground-to-chassis grounding or grounding at different potentials for non-grounded applications. When J1 is fully tightened - i.e., in its factory-set position - both signal ground and chassis ground in the PLC are tied together and to the input power terminal block ground screw. This is the preferred method of grounding for all single, parent, or child PLCs whenever solid earth ground is available.

and damage to the PLCs or other attached devices. The J2 screw provides 120 W termination for the PLC when it is tightened - J2 is shipped from the factory in a tightened position. When the PLC is operating in single mode or when it is a parent or child at the head or tail end of an I/O expansion link, the J2 screw must remain tightened. When the PLC resides in a non-terminating location on an I/O expansion link, the J2 screw must be loosened by one turn.

Wiring External Power External connections to the power supply are made at the five terminal screws located on the left front of the PLC. The wires from the external source are fed to the appropriate screws through slots along the left side of the PLC, as shown in the following illustration. A Left Front Isoview of the PLC

When the J1 is loosened (counterclockwise), it disconnects earth ground from signal ground. The PLC can now be connected as part of a non-grounded or single-point ground system. In a singlepoint ground system, only one PLC needs to be tied to chassis ground (J1 screw tightened); all other PLCs in the system can be referenced to this single point over the I/O expansion link (their J1 screws loosened). The expansion link must always be attached to prevent communication errors in the ungrounded PLCs. Caution Before you power up your system, make sure that all the PLCs are at the same earth ground potential to reduce communication errors, ground loop lockups,

6

512/612 Modicon Micro PLCs

3

2

1

1. Five terminal screws for external power wiring 2. Side slots for leading wires from the power source to the terminal screws 3. Label indicating power wiring scheme

890 USE 145 00

Page 8

The label affixed to the left front of the PLC indicates the power wiring scheme. Model 110CPU51200, 110CPU61200, 110CPU51203, 110CPU61204, and 110CPU61203 PLCs use a 24 VDC external power source, wired like this: 24 VDC

Model 51202 PLCs use a 230 VAC external power source, wired like this:

L

1

230 VAC 2

1 3 2

N

4

3 5 24 RET

4

The labels for the power source terminal connections are in red lettering. 5

Model 11051201 PLCs use a 115 VAC external power source, wired like this:

Note Add a wire loop between the pins labeled JUMPER.

1

L 2 115 VAC 3

N 4

5

890 USE 145 00

512/612 Modicon Micro PLCs

7

Page 9

PLC Status Display The display panel on the front of the Micro PLCs uses light-emitting diodes (LEDs) to indicate the health and status of the unit’s CPU, battery, communication ports, and fixed I/O points. The column of LEDs on the right side of the unit indicates PLC status: PLC Status LEDs LED

Function power ok

A green LED turned ON when internal power is OK ready

An amber LED that is ON when the PLC has passed its power-up diagnostics, and remains ON as long as the PLC is healthy run

A green LED that is ON when the PLC has started and is solving logic and that flashes when the PLC has power but cannot find a valid configuration/ operating mode battery low A red LED that goes ON when the internal battery needs to be replaced (Replacement should be within 14 days of the initial LED indication.) This LED also goes ON if a problem is detected in the optional battery capacitor or if the capacitor is not fully charged. exp. link

A green LED that goes ON steadily when valid communications occur on the I/O expansion link, and flashes when errors occur on the link. similar exp link indications occur in both PLCs involved in the communication comm 1

A green LED that flashes when communi-cations occur on the first RS-232 port comm 2

A green LED that flashes when communications occur on the second RS-232 port

To reference the physical I/O point to an LED number in the display, refer to the field wiring diagrams presented in this book. If the run LED on the right is flashing in conjunction with any of the input LEDs, an error has been detected. The pattern of the input LED flashes indicates the nature of the error. The person programming the PLC can refer to the Modicon Micro Ladder Logic Manual (890 USE 146 00) for a description of system crash codes.

Comm Ports Two RS-232 (comm 1 and comm 2) ports and one RS-485 (I/O exp link) port are located on the bottom of each unit. The RS-232 ports use eightposition RJ45 (phone jack-type) connectors. The RS-485 port uses a six-position RJ11 (phone jack-type) connector. The comm ports are multi-functional, and under the control of the system firmware, Their capabilities are described in the Modicon Micro Ladder Logic Manual (890 USE 146 00) and your panel software documentation.

The array of LEDs on the left side of the display indicates the status of the fixed discrete I/O points on the PLC. Each fixed input and output point lights a number (1 ... 16 for inputs, 1 ... 12 for outputs) with a red LED when the associated discrete point is ON.

8

512/612 Modicon Micro PLCs

890 USE 145 00

Page 10

Bottom Isoview of the PLC comm 1 (RJ45) port comm 2 (RJ45) port I/O exp link (RJ11) port 30-pin A120 I/O expansion receptacle

A120 I/O Expansion Port A dedicated A120 I/O parallel expansion port is located on the right side of the unit. It is a 30-pin, dual-row receptacle with locking tabs. It will accept the connector on the left side of a DTA 201 or DTA 202 rack, which houses the A120 I/O modules.

890 USE 145 00

512/612 Modicon Micro PLCs

9