Manual · Modicon
Modicon 512/612 Micro PLC Hardware User Manual
Manual60 pagesPDF 13 MB
Hardware user manual for the Modicon 512 and 612 Micro PLCs (110CPU512xx and 110CPU612xx), covering fixed I/O, wiring and expansion.
Names · 8 models
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
The Modicon hardware user manual for the 512 and 612 Micro PLC base units, including the 110CPU51200 to 51203 and 110CPU61200, 61203 and 61204. It describes hardware characteristics, operating modes, memory and backup options, terminal blocks, power wiring, the status display and comm ports, fixed analog I/O on the 612 models, electrical and environmental specifications, fixed I/O specifications, mounting, the serial I/O expansion link, A120 I/O expansion and programming panel cables.
Its parts
- General Hardware Characteristics
- General Hardware Overview
- Base Unit Specifications
- Fixed I/O Specifications
- Installation Guidelines
- Serial I/O Expansion Link
- A120 I/O Expansion
- Connecting the PLC to a Programming Panel
From the manual
Key facts from this manual
Each line names its page in the PDF.
Modicon 512/612 Micro PLC Hardware User Manual (890 USE 145 00), covering the 110CPU51200, 110CPU51201, 110CPU51202, 110CPU51203, 110CPU61200, 110CPU61203 and 110CPU61204 Micro PLCs. It lists the fixed I/O and power of each model, memory and backup options, electrical and environmental specifications, and I/O characteristics. It also walks through field wiring, grounding, mounting, A120 I/O expansion and connecting a programming panel, with part numbers for cables, batteries and spares.
- Type
- Micro PLC with on-board CPU, memory, fixed I/O and power supply p. 3
- 110CPU51202
- 110CPU51202: 230 VAC power; 16 230 VAC inputs, 8 triac outputs, 4 relay outputs p. 3
- 110CPU61200
- 110CPU61200: 24 VDC power; 16 24 VDC inputs, 12 relay outputs, 4 analog in, 2 analog out p. 3
- Memory
- 128 kbytes RAM; 2048 words program memory, 2048 words data memory p. 4
- Comm ports
- Two RS-232 ports (RJ45) and one RS-485 I/O expansion link port (RJ11) p. 9
- Operating temperature
- 0 to 60 degrees C; storage -40 to +85 degrees C p. 16
- Memory backup
- 110XCP98000 lithium battery (one year), 110XCP99000 battery capacitor (72 hr), or Flash RAM p. 4
- I/O expansion
- A120 parallel port for up to three racks; accepts DTA 201 or DTA 202 racks p. 3, 10
- Analog I/O
- 612 models: 4 analog inputs (0 to 10 V or 4 to 20 mA) and 2 analog outputs p. 3, 40
- Relay outputs
- 24 to 30 VDC or 24 to 250 VAC, 2 A/channel; user-installed 3 A fuse required p. 33
- Triac outputs
- 110CPU51202: 24 to 250 VAC, 0.5 A/channel; user-installed 0.8 A fuse required p. 3, 36
- 24 VDC supply
- 110CPU51202: on-board 24 VDC supply, 150 mA p. 3
- Cables
- RS-232: 110XCA28201 (1 m), 110XCA28202 (3 m), 110XCA28203 (6 m); RS-485 link: 110XCA17101 (61 cm), 110XCA17102 (3 m), 110XCA17103 (6 m) p. 17
- Weight
- 1.45 kg (3.2 lb) p. 16
What this manual walks you through
- Removing terminal blocks for field wiring p. 6, 7
- Setting the J1 grounding and J2 termination screws p. 7
- Wiring external power p. 7, 8
- Reading the status LEDs p. 9
- Field wiring the 110CPU51202 p. 22
- Suppressing inductive loads on relay outputs p. 34, 35
- Wiring analog inputs p. 41
- DIN rail length and cabinet clearances p. 48
- Installing the optional battery or battery capacitor p. 49
- Connecting a programming panel p. 57
Good to know
- Relay and triac outputs have no internal overload protection; external fuses are required. p. 33, 36
- The battery capacitor must charge in a powered-up PLC for at least 24 hours for full memory backup. p. 4
- Flash backup holds only what was saved at the last Save to Flash command. p. 5
- When the battery low LED comes on, the battery should be replaced within 14 days. p. 9
- Before power-up, all PLCs should be at the same earth ground potential. p. 7
Questions this manual answers
What I/O does the Modicon 110CPU51202 have?
It runs on 230 VAC and has 16 230 VAC inputs, 8 triac outputs and 4 relay outputs. p. 3
What is the difference between the Modicon 512 and 612 Micro PLCs?
The 612 models add four analog input channels and two analog output channels. p. 3
What battery backs up memory on a Modicon Micro PLC?
The optional 110XCP98000 lithium battery assembly, which backs up data for one year, or the 110XCP99000 battery capacitor assembly. p. 4
Which cable connects a Modicon Micro PLC to a PC?
An RJ45 RS-232 cable (110XCA28201, 110XCA28202 or 110XCA28203) with the 110XCA20300 9-pin adapter for PC-AT computers. p. 57
What does a flashing run LED mean on a Modicon Micro PLC?
The PLC has power but cannot find a valid configuration or operating mode. p. 9
The whole text · 6 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file