Page 41
Input Circuit Characteristics Simplified Schematic Field Connections
Jumper Current Input
Input 1 (+) Sense 1
4 ... 20 mA Input 1 (--) Input 2 (+) Sense 2 Input 2 (--) Voltage Input
Input 3 (+) Sense 3 Input 3 (--) Input 4 (+) Sense 4 Input 4 (--)
10 11
250
W .1%
Analog MUX
DC
DC
12 13
ADC CPU
14 15 16
V REF
17 18 19 20 21
Isolation barrier
Note: To reduce the possibility of erroneous readings if one or more device wires become disconnected, it is recommended that the appropriate input and sense lines be jumpered as shown in the above illustration.
40
512/612 Modicon Micro PLCs
890 USE 145 00
Page 42
Analog Outputs Electrical Characteristics Output channels Number Types Group Isolation
2 Current outputs Voltage outputs 1000 VAC RMS (60 Hz), 1 min. maximum (Analog outputs are isolated from analog inputs, input power, discrete I/O, and communication ports.) 1000 VDC, 1 min. maximum
Current range Loop supply voltage Maximum Minimum Max loop resistance Voltage range Output loads
Conversion Resolution
4 ... 20 mA 30 V 12 V Vloop -- 7 V = Max. R .02 0 ... 10 V 10 mA maximum .1 mF maximum 1 kW minimum 12 bits
Linearity errors
+.05% maximum
Differential nonlinearity
Guaranteed monotonic
Update time
10 ms/channel
Accuracy (Offset, Gain, and Linearity Errors) Initial @ 25 degrees C Typical Maximum Volt mode 0.2% 0.35% [200--350 mV] Current mode 0.35% 0.5% Additional drift (0 ... 60 degrees C) Volt mode .05% Current mode 0.18%
0.1% 0.26%
Note Additional separate 24 VDC supplies for I/O are not required because these circuits are isolated internally. Separate supplies may be used and can improve system performance by avoiding the interference caused by poor power supply regulation and load transients. Note Twisted shielded pair cable is recommended. Terminate shields to channel return to reduce power supply switching noise.
890 USE 145 00
512/612 Modicon Micro PLCs
41
Page 43
Output Circuit Characteristics Simplified Schematic Field Connections 1
0 ... 10V
2
ZL
3 DC
4
DC
5
D/A
6
W
V REF
250 .1%
ZL +
4 ... 20 mA
7
24V
8
--
9
CPU
D/A
Isolation barrier
W
250 .1%
1 = Channel 1, Volt out 2 = Channel 1 RTN * 3 = Channel 1 4 = Voltage monitor 5 = Channel 2, Volt out 6 = Channel 2 RTN * 7 = Channel 2 8 = Voltage monitor
4 ... 20 mA output
4 ... 20 mA output
Note -- All RTN’S are common inside box. Therefore both outputs are referenced to same point.
42
512/612 Modicon Micro PLCs
890 USE 145 00
Page 44
Installation Guidelines The Model 512 and 612 PLCs offer a straightforward plug-and-play installation capability.
bottom - to secure the unit to a flat surface such as a 1/4 in metal plate in a NEMA cabinet. To access these through-holes, remove the I/O terminal blocks at the top and bottom of the unit. The through-hole locations are shown in the dimension drawing below.
Mounting Options A PLC (or a PLC-based I/O expansion link) may be mounted: In a NEMA cabinet
The four holes are counter-bored in the housing so that the securing screws will not touch the terminal blocks when they are re-inserted onto the unit.
On a wall On an EIA rack On DIN rail Note If The PLC uses its A120 I/O expansion capability, the unit and its associated A120 I/O racks must be mounted on DIN rail.
Use M5 screws. The type and length of the screw depends on the kind of surface on which the units are being mounted - e.g., a machine screw with a minimum length of 5/8 in should be used to mount to a 1/4 in plate.
Securing a Unit to a Flat Surface The PLC housing contains four throughholes - two at the top and two at the 254.00 mm (10 in) 198.00 mm (7.8 in) 56.00 mm (2.20 in)
base + terminal blocks
141.5 mm (5.57 in) 158.75 mm 132.375 mm (5.21 in) (6.25 in)
9.125 mm (0.359 in)
44
123.5 mm (4.86 in)
PLC base
17.75 mm (.698 in)
512/612 Modicon Micro PLCs
890 USE 145 00
Page 45
Unit Dimensions 76 mm (3 in)
158.75 mm (6.25 in)
890 USE 145 00
512/612 Modicon Micro PLCs
45
Page 46
Mounting Units on DIN Rail The PLC can be mounted on a DIN EN 50 022 carrier rail. The DIN rail can be attached to a flat mounting surface or hung on an EIA rack or in a NEMA cabinet.
surface. 7.5 mm
15 mm
If the PLC uses its A120 I/O expansion capability, the unit and the backplanes that house the A120 modules must be mounted on DIN rail.
Mounted DIN Rail Profiles 35 mm
DIN EN 50 022 Carrier Rail
DIN rail may have either 7.5 mm or 15 mm clearance from the mounting
If the PLC is mounted on 15 mm DIN rail, the two spacers shipped with the PLC and should be placed on the lower back of the PLC, as shown below. The spacers keep the unit flush against a flat mounting surface and provide vibration protection.
Spacers for a PLC to be mounted on 15 mm DIN rail
46
512/612 Modicon Micro PLCs
890 USE 145 00
Page 47
Installing a PLC on DIN Rail Step 1 Remove the output terminal block on the bottom of the PLC to gain access to the three clips shown in (1). Pull the clips down before placing the unit on the DIN rail.
4a
4b
1
Step 2 Place the clip on the top of the PLC housing over the top of the DIN rail and drop the unit into place.
2
Spacer
Step 4 Push the three clips on the bottom of the unit up to lock the unit onto the DIN rail, then snap the output terminal block back into place. Step 5 To keep the Micro PLC assembly from sliding on the DIN rail, we recommend that you place a DIN rail end clamp such as the one shown below on both sides of the unit assembly.
3
Step 3 If the DIN rail is on a wall or a plate, the unit will fall flush against the surface (see 4a). If you are using a 15 mm DIN rail, insert the two spacers on the lower backside of the unit (see 4b).
End clamps such as the one above can be ordered from your DIN rail supplier. 890 USE 145 00
512/612 Modicon Micro PLCs
47
Page 48
135 mm (5.31 in)
940 mm (37 in)
225 mm (8.85 in)
~ 10 mm (.39 in)
Modicon Micro PLC
DTA 201 Backplane
DTA 201 Backplane
DTA 201 Backplane
DIN Rail Length to Support A120 I/O Expansion on a Modicon Micro
A DIN rail must be at least 255 mm (10.04 in) long to support a single PLC. To support a PLC with three DTA 201 five-slot backplanes, a DIN rail needs to be at least 940 mm (37 in) long.
39 mm (1.5 in) minimum
117 ... 195 mm (3 ... 5 in)
Installing a PLC on DIN Rail Below is an illustration of recommended clearance requirements for mounting PLCs with A120 I/O racks in an enclosure.
100 mm 3.9 in
200 mm 7.8 in
158.75 mm 6.25 in
Plastic wire trough allowed
130 mm 5.07 in
158.75 mm 6.25 in
Input air temp < 60 degrees C
130 mm 5.07 in
Minimum Height and Length Requirements for a NEMA Cabinet Installation
48
512/612 Modicon Micro PLCs
890 USE 145 00
Page 49
Installing the Optional Battery or Battery Capacitor Memory backup may be provided by either a lithium battery assembly (110XCP98000) or a battery capacitor assembly (110XCP99000). Both assemblies include wire leads and a 3-position feed-thru receptacle connector. They may be ordered as options from Modicon or from your local distributor. Installing a Battery or Battery Capacitor Assembly Step 1 With a slotted screwdriver, remove the battery cover from the Micro PLC. This cover is located on the top right corner of the unit above the LED panel.
Step 3 Connect the 3-position re-ceptacle connector on the assembly to the three pins on the printed circuit board on the PLC beneath the battery cover. The receptacle is keyed so that only the correct connections can be made with the pins. Step 4 Place the cover back on the PLC unit. The memory backup assembly is now installed and available.
Step 2 The underside of the cover has a finger pattern that will grab either the lithium battery or the capacitor. Snap the desired component into the cover:
+ -110 XCP 990 00 Battery Capacitor installed in the battery cover
890 USE 145 00
110 XCP 980 00 Lithium Battery installed in the battery cover
512/612 Modicon Micro PLCs
49
Page 50
Serial I/O Expansion Link Up to five PLCs can be interconnected on a serial I/O expansion link. The link contains one parent PLC and from one ... four child PLCs. I/O Expansion Link Characteristics 2 ... 5
Physical comm port
RS-485
Cable type
Six-position line long body
Connector type on the cableboth ends
RJ11 male on
125 kbyte (+ )
Encoding scheme
NRZ
W
RS-485 port
RJ11 direct connect J2 screw loosened
Child # 1
W
120
Data rate on the link
J2 screw tightened for 120 termination Parent PLC
Number of PLCs
Termination
An I/O Expansion Link
RS-485 port
Length of link500 m (1500 ft) maximum 6 m (20 ft) minimum
The PLCs are connected to each other on the link via their RS-485 ports. Connections are point-to-point. Standard six-position, foil-shielded, flat telephone cables with male RJ11 connectors on each end are used to connect the units. Three premade cable assemblies are available:
110XCA10100 Y - connector
J2 screw loosened
Child # 2 RS-485 port
110XCA10100 Y - connector J2 screw loosened Child # 3
RS-485 port 110XCA10100 Y - connector J2 screw tightened for 120 termination
I/O Expansion Link Cables Length
Part Number
61 cm (2 ft)
110XCA17101
3m
(10 ft)
110XCA17102
6m
(20 ft)
110XCA17103
W
Child # 4 RS-485 port
The RJ11 cable plugs directly into the RS-485 ports on the two units at the head and tail ends of the link. All the other units on the link use a (110XCA10100) RJ11 Y-connector.
RJ11 direct connect
110XCA10100 Y-connector Pinouts RJ11 Plug for the RS485 Port 1 2
3 4
5 6
The 110 XCA 101 00 Y-connector
RJ11 plug RJ11 jacks
1 2 3 4 5 6 RJ11 Jack for the Cable
1 2 3 4 5 6 RJ11 Jack for the Cable
Pin 1 = chassis ground Pin 2 = TXHi 37.3 mm (1.47 in)
50
512/612 Modicon Micro PLCs
Pin 3 = TXLo
890 USE 145 00