The text of a manual · part 4 of 6

Modicon 512/612 Micro PLC Hardware User Manual, pages 31 to 40

Pages 31 to 40 of 60

The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon 110 CPU 512 02, Modicon 110 CPU 612 00, AEG 110 CPU 512 02, Gould 110 CPU 512 02, Schneider 110 CPU 512 02, AEG 110 CPU 612 00, Gould 110 CPU 612 00 and Schneider 110 CPU 612 00

Page 31

Circuit Characteristics Simplified schematic Field side

Logic side Interrupt/counter

5V

Com

Isolation Method Channel-to-bus Group-to-group

Opto-coupler 500 VDC 500 VDC

Addressing

1 register in

Maximum cable length

50 m

Response time OFF®ON ON®OFF

10 ... 20 ms 10 ... 20 ms

Required cable type

Shielded twisted pair, for noise immunity

Wire size

20 AWG

Up-counter positive edge trigger Maximum counter rate Pulse duration

5 kHz > 100 ms

Interrupt voltage level

30

512/612 Modicon Micro PLCs

To assure reliable system operation, interrupt voltage must be brought from OFF to ON and maintained ON for 350 ms minimum - any pulse duration < 20 ms is filtered

890 USE 145 00

Page 32

Dedicated High-speed Interrupt Inputs Electrical Characteristics ON level

15 ... 30 VDC

OFF level

0 ... 5 VDC

Minimum ON state input

6 mA @ 15 VDC

Maximum OFF current

0.3 mA @ 5 V

Maximum input impedance

15.8 kW when OFF 1.95 kW when ON @ 24 VDC

Current draw

12.3 mA @ 24 VDC

Note

We recommend the use of three-wire proximity switches on these inputs.

Circuit Characteristics Simplified schematic Field side

Logic side VCC

Isolation Method Channel-to-bus

Opto-coupler 500 VDC

Maximum cable length

50 m

Required cable type

Shielded twisted pair, for noise immunity

Wire size

20 AWG

Interrupt voltage level

To assure reliable system operation, interrupt voltage must be brought from OFF to ON and maintained ON for 350 ms minimum - any pulse duration < 50 ms is filtered

890 USE 145 00

512/612 Modicon Micro PLCs

31

Page 33

Relay Outputs Electrical Characteristics Working voltage range (for all Micro types)

24 ... 30 VDC 24 ... 250 VAC

Maximum load current

2 A/channel

Surge current

20 A for 1 cycle

VA rating

500 VA (switching)

Minimum load current

20 mA

Maximum switching rate

5 Hz

Required external fuse size

User-installed 3 A fuse - e.g. Bussman GMA-V-3.0 - in the field wiring between the output terminal screw and the load

Caution Internal overload protection is not provided for these outputs - external fusing is required. Derating curve 5000 4000 3000 2000

1000 120 VAC Resistive 500

3 OPERATION (x 10 )

400 300 200

100

50

20

120 VAC cos

0.1

0.2

Æ = 0.7

0.3 0.5 1

2

3

4

5

CONTACT CURRENT (A)

32

512/612 Modicon Micro PLCs

890 USE 145 00

Page 34

Circuit Characteristics Simplified schematic Logic side

Field side

5V

Varistor 280 VAC

Isolation Channel-to-bus Group-to-group

1780 VAC, 2500 VDC 1780 VAC, 2500 VDC

Mechanical operating cycles

20,000,000

Surge withstand capability

4 kV

Response times ON®OFF OFF®ON

10 ms 10 ms

Maximum wire length

100 m

Wire size One wire Two wires

14 AWG 20 AWG

Using Relay Outputs with Inductive Loads The mechanical relay outputs in Micro controllers must be provided with additional protection when connected to an inductive load. Properly suppressing inductive loads reduces radiated noise and prolongs the life of the relay contacts. The following three figures provide examples of how to suppress various inductive loads.

Inductive AC Load

OUTPUT

* 0.47 mf

* 50 W

115 AC SOURCE

COMMON *Minimum voltage rating of 200 VAC.

890 USE 145 00

512/612 Modicon Micro PLCs

33

Page 35

Inductive AC Load

OUTPUT

* 0.47 mf

* 50 W

230 AC SOURCE

COMMON *Minimum voltage rating of 400 VAC.

OUTPUT

Inductive DC Load

Clamping Diode*

+ 24VDC SOURCE --

COMMON *Diode must be a minimum of 2A, continuous, and greater than two times the maximum rated load voltage.

34

512/612 Modicon Micro PLCs

890 USE 145 00

Page 36

Triac Outputs Electrical Characteristics Working voltage Continuous range

24 ... 132 VAC for the -01 Models 24 ... 250 VAC for the -02 Models 500 VAC for 1 cycle

Maximum Frequency of operation

47 ... 63 Hz

Maximum load current

0.5 A/channel

Surge current

5 A for 1 cycle

Minimum load current

50 mA

Maximum OFF state leakage current 1.5 mA ON state voltage drop

1.5 V

Maximum switching rate

20 Hz

Static DV/DT

300 V/ms

Required external fuse size

User-installed 0.8 A fuse - e.g., Bussman GMA-V-.8 - in the field wiring between the output terminal screw and the load

Caution Internal overload protection is not provided for these outputs - external fusing is required. Derating curve 2.0

RMS current/ point All points on with same load Measured with PLC mounted in normal upright position.

AMPS

1.0 .75 .5

0

10

20

30

40

50

60

AMBIENT TEMPERATURE DEGREE C

890 USE 145 00

512/612 Modicon Micro PLCs

35

Page 37

Circuit Characteristics Simplified schematic Live

Logic side

Field side

Load Varistor 280 VAC Group Common

36

Isolation Method Channel-to-bus Group-to-group

Opto-coupler 1780 VAC, 2500 VDC 1780 VAC, 2500 VDC

Response times ON®OFF OFF®ON

8 ms 8 ms

Maximum wire length

100 m

Wire size One wire Two wires

14 AWG 20 AWG

512/612 Modicon Micro PLCs

890 USE 145 00

Page 38

24 VDC (FET) Outputs Electrical Characteristics Working voltage range Continuous Maximum

20 ... 30 VDC 32 V for 10 s 56 V for 1.5 ms

ON current (@ 60 degrees C)

0.5 A / channel 2 A / group 6 A total

Surge current

5 A for .5 ms @ 6 pulses / min

Minimum load current

10 mA

Maximum OFF leakage current

1 mA @ 30 V

ON state voltage drop

.4 V @ .5 A

Maximum switching rate

4 Hz inductive

Recommended external fuse size

User-installed 1.5 A fuse - e.g., Bussman GMA-V-1.5 - in the field wiring between the output terminal screw and the load. Note Internal overload protection is not provided for these outputs, and external fusing is strongly recommended.

Total current / group

2 A @ 60 degrees C

Derating curve All outputs similarly loaded

2.0

CURRENT / AMP.

Measured with PLC mounted in normal upright position.

1.0

.5

0

12

24

36

45 48

60

AMBIENT TEMPERATURE DEGREE C

890 USE 145 00

512/612 Modicon Micro PLCs

37

Page 39

Circuit Characteristics Simplified schematic Field side

+24 V Power IN

Logic side VCC

To Load

+24 REF

38

Isolation Channel-to-bus Group-to-group

1780 VAC, 2500 VDC 500 VAC

Response times ON®OFF OFF®ON

1 ms 1 ms

Maximum wire length

100 m

Wire size

14 AWG

512/612 Modicon Micro PLCs

890 USE 145 00

Page 40

Analog Inputs Electrical Characteristics Input channels Number Types

4 Current inputs, 20 mA full scale Voltage inputs, 10 V full scale

Input ranges

+10 V, 0 ... 10 V, 4 ... 20 mA

Input filter

Single-pole low-pass, --3 dB frequency of 10 Hz (+20%)

Input resistance Current mode Voltage mode

250 W (+0.1%) > 20 MW

Input protection Differential Channel-to-channel

50 VDC maximum 30 VDC maximum

Over current

25 mA maximum

Common mode range

25 VDC channel-to-channel

Group Isolation

1000 VAC RMS, 1 min. maximum (Analog inputs are isolated from analog outputs, input power, discrete I/O, and communication ports.)

Wire size 1 wire 2 wires Conversion Type

12 AWG 14 AWG Sigma Delta

Resolution

16 bits for +10 V 15 bits for 0 ... 10 V 13®14 bits for 4 ... 20 mA

Update time

55 ms/channel if scanned > 55ms; otherwise, 4 times the scan rate.

Differential nonlinearity

No missing codes

Repeatability

+3 counts

Accuracy (Offset, Gain, and Linearity Errors)* Initial @ 25 degrees C Typical Maximum +.025% +0.1% Additional drift (0 ... 60 degrees C) +.07% +0.25%

*

A 250 W current-to-voltage conversion resistor contributes an additional error of +0.1%, + 25 ppm/degree C (for a 4 ... 20 mA input range).

890 USE 145 00

512/612 Modicon Micro PLCs

39