The text of a manual · part 3 of 6
Modicon 512/612 Micro PLC Hardware User Manual, pages 21 to 30
Pages 21 to 30 of 60
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon 110 CPU 512 02, Modicon 110 CPU 612 00, AEG 110 CPU 512 02, Gould 110 CPU 512 02, Schneider 110 CPU 512 02, AEG 110 CPU 612 00, Gould 110 CPU 612 00 and Schneider 110 CPU 612 00
Page 21
110CPU51201 Field Wiring (under 115 VAC power) Fixed I/O Topology I/O Type
Number of I/O Points
Number of Groups
115 VAC inputs
16
2 groups of 8
24 VDC user-selectable counter/interrupt
1
24 VDC dedicated high-speed interrupts
1
Triac outputs
8
2 groups of 4
Relay outputs
4 individually isolated
AC Hot AC Neutral
1 group of 2
In In In In In In 16 15 14 13 12 11
.16A Fuse
AC Hot AC Neutral
In In 10 9 Group A common
Group B common Cnt/ Int
Int 1
In 8
In 7
In 6
In 5
In In 4 3
In 2
In 1 .16A Fuse
22 21 115V
20 19
18 17 16 15 14 13 12 11 10
User-selectable +24 V out Dedicated counter or interrupt interrupt +24 V ref*
9
8
7
Group B 115 VAC Inputs
6
5
4
3
2
1
Group A 115 VAC Inputs
115V
Modicon 110CPU51201
Group B common Group B hot Group A common
Isolated Relay Outputs
Triac Group B
20 19 18 17 16 15 14 13 12 11 10
Fuses Relay Hot
3A
3A
3A
Out 12B
Out 11B
Out 10B
Relay Neutral
3A
9
Group A hot
Triac Group A
8
7
.8A .8A .8A .8A
6
5
4
3
2
1
.8A .8A .8A .8A
Out 9B
L 12
L 11
L 10
L 9
Out 12A
Out 11A
Out 10A
Out 9A
L 8
L 7
L 6
L 5
L 4
L 3
L 2
L 1
Out Out Out Out 8 7 6 5
Out Out Out Out 4 3 2 1 * The 24 V power supply from pins 19 and 20 in the top block provide up to 150 mA at 24 V. Note Fast-blow fuses are recommended for input and output protection.
20
512/612 Modicon Micro PLCs
890 USE 145 00
Page 22
110CPU51202 Field Wiring (under 230 VAC power) Fixed I/O Topology I/O Type
Number of I/O Points
Number of Groups
230 VAC inputs
16
2 groups of 8
24 VDC user-selectable counter/interrupt
1
24 VDC dedicated high-speed interrupts
1
1 group of 2
Triac outputs
8
2 groups of 4
Relay outputs
4 individually isolated
AC Hot AC Neutral
AC Hot AC Neutral
In In In In In In In In 16 15 14 13 12 11 10 9
.16 A Recommended
Group A common
Group B common Cnt/ Int int 1
230V
22 21
20 19 18 17 16 15 14 13 12 11 10
User-selectable Dedicated counter or Interrupt interupt
9
In 8
In In In 7 6 5
In In 4 3
In 2
In 1 .16A Fuse
8
7
4
2
1
6
Group B 230 VAC Inputs
+24 V out
5
3
Group A 230 VAC Inputs
+24 V ref
Modicon 110CPU51202
230V
Group B common Group B Hot Group A common Group A Hot Isolated Relay Outputs
Triac Group B
20 19 18 17 16 15 14 13 12 11 10
Relay Hot
3A
Out 12B
Relay Neutral
3A
3A
Out 11B
Out 10B
Out 9B
L 12
L 11
L 10
Out 12A
Out 11A
Out 10A
9
Triac Group A
8
7
6
5
4
3
2
1
.8A
.8A .8A .8A .8A
.8A .8A .8A .8A
L 9
L 8
L 4
Out 9A
L 7
L 6
L 5
Out Out Out Out 8 7 6 5
L 3
L 2
L 1
Out Out Out Out 4 3 2 1
Group B Hot Note: Fast-blow fuses are recommended for input and output protection
890 USE 145 00
512/612 Modicon Micro PLCs
21
Page 23
110CPU51203/61203 Field Wiring (under 24 VDC Power) Fixed Discrete I/O Topology I/O Type
Number of I/O Points
Number of Groups
24 VDC inputs
16
2 groups of 8
24 VDC user-selectable counter/interrupt
1
24 VDC dedicated high-speed interrupts
2
24 VDC (FET) outputs
12
1 group of 3
3 groups of 4 with Source-configured 24 VDC Inputs 24V common +24V
24V common +24V Group B common
.16 A
Group A common
In In In In 16 15 14 13
In In In In 12 11 10 9
Cnt/ Int int 2
Int 1
22 21
20 19 18 17 16 15 14 13 12 11 10
User-selectable Dedicated Counter or interrupts interrupt Cnt/int com
In 8
In 7
In 6
In 5
In In 4 3
In 2
In 1
8
7
6
5
4
2
1
9
Group B 24 VDC Inputs
3
.16 A
Group A 24 VDC Inputs
Modicon 110CPU51203 110CPU61203
Group C FET Outputs
Group C common
Group B common
Group A common
Group C hot
Group B hot
Group A hot
Group B FET Outputs
20 19 18 17 16 15 14 13 12 11 10
Group A FET Outputs 9
8
1.5A
L L L L 12 11 10 9 12 11 10 9 Out Out Out Out
7
6
5
4
3
2
1.5A
L 8
L 7
L 6
L 5
8 7 6 5 Out Out Out Out
1
1.5A Fuse recommended for each output L 4
L 3
L 2
L 1
4 3 2 1 Out Out Out Out
Note Fast-blow fuses are recommended for input and output protection.
22
512/612 Modicon Micro PLCs
890 USE 145 00
Page 24
with Sink-configured 24 VDC Inputs 24 V Common +24 V
.16 A Cnt/ Int int 2
Int 1
24 V Common Group B common In In In In 16 15 14 13
22 21
In In In In 12 11 10 9
20 19 18 17 16 15 14 13 12 11 10
User-selectable Dedicated Counter or interrupts Cnt/int com interrupt
.16 A
Group A common In 8
In 7
In 6
In 5
In In 4 3
In 2
In 1
8
7
6
5
4
2
1
9
Group B 24 VDC Inputs
3
+24 V
Group A 24 VDC Inputs
Modicon 110CPU51203 110CPU61203
Group C FET Outputs
Group C common
Group B common
Group A common
Group C hot
Group B hot
Group A hot
Group B FET Outputs
20 19 18 17 16 15 14 13 12 11 10
1.5A
L L L L 12 11 10 9 12 11 10 9 Out Out Out Out
Group A FET Outputs 9
8
7
6
5
4
3
2
1.5A
L 8
L 7
L 6
L 5
8 7 6 5 Out Out Out Out
1
1.5A Fuse recommended for each output L 4
L 3
L 2
L 1
4 3 2 1 Out Out Out Out
Note Fast-blow fuses are recommended for input and output protection.
Note To reduce the risk that electrical noise from field I/O devices will effect Micro operation, we recommend that a separate 24 VDC power source be used for the field I/O. A dual power-source configuration can also be beneficial in preventing a failure in a single field device from shutting down power to the PLC. Note The wiring for the analog I/O of the 110CPU61203 is shown in the simplified schematics on pages 40 (for the inputs) and 42 (for the outputs).
890 USE 145 00
512/612 Modicon Micro PLCs
23
Page 25
115 VAC Inputs Electrical Characteristics ON level ON current @ 120 VAC OFF level
79 ... 132 VAC with a maximum source impedance of 6.2 kW @ 60 Hz 10 mA 0 ... 20 VAC
Maximum OFF state input current Minimum ON state input current
1.7 mA @ 20 V 6.5 mA @ 79 V
Input impedance
12 kW @ 60 Hz
Circuit Characteristics Simplified schematic Field side
Logic side VCC
Isolation Method Channel-to-bus Group-to-group
24
Opto-coupler 1780 VAC, 2 kV DC 1780 VAC, 2 kV DC
Addressing
16 discrete bits in 1 register in
Maximum wire length
100 m
Wire size
20 AWG
Response time ON®OFF OFF®ON
25 ... 30 ms 25 ... 30 ms
512/612 Modicon Micro PLCs
890 USE 145 00
Page 26
230 VAC Inputs Electrical Characteristics ON level OFF level
164 ... 253 VAC with a maximum source impedance of 16 kW 0 ... 40 VAC
ON state input OFF current
7 mA @ 230 VAC, 50 Hz 1.2 mA maximum @ 40 VAC
Maximum OFF state current
1.2 mA @ 40 VAC
Minimum ON state current
5.0 mA @ 164 VAC
Input impedance
33 kW @ 50 Hz
Circuit Characteristics Simplified schematic Field side
Logic side VCC
Isolation Method Channel-to-bus Group-to-group
Opto-coupler 1780 VAC, 2500 VDC 1780 VAC, 2500 VDC
Maximum wire length
100 m
Wire size
14 AWG
Response time ON®OFF OFF®ON
25 ... 30 ms 25 ... 30 ms
890 USE 145 00
512/612 Modicon Micro PLCs
25
Page 27
24 VDC Inputs Electrical Characteristics for Source (True High) Inputs ON level 15 ... 30 VDC, source impedance < 1.5 kW OFF level
0 ... 5 VDC
Minimum ON state input current
3.4 mA @ 15 VDC
Maximum OFF current
.6 mA @ 5 V
Maximum input impedance
7.8 kW when OFF 3.0 kW when ON @ 24 VDC input
Typical impedance curve 30 V
25 V
INPUT VOLTAGE
20 V
15 V
10 V
+5 V
0 mA
26
1 mA
2 mA
3 mA
4 mA
512/612 Modicon Micro PLCs
5 mA
6 mA
7 mA
8 mA
9 mA
10 mA
11 mA
890 USE 145 00
Page 28
Electrical Characteristics for Sink (True Low) Inputs ON level Source ground to (source voltage -- 15 V) OFF level
Source voltage to (source voltage -- 5 V)
Minimum ON state input current
3.4 mA with 20 ... 30 V source
Maximum OFF current
.7 mA with 20 ... 30 V source
Maximum input voltage
30 VDC
Maximum input impedance
7.8 kW when OFF 3.0 kW when ON @ 24 VDC
Typical impedance curve (Tested with 24 VDC source to common pin 18) 0 Ground
+5 V
INPUT VOLTAGE
Minimum 10 V Typical 15 V
20 V Maximum 25 V
30 V 0 mA
Note
890 USE 145 00
1 mA
2 mA
3 mA
4 mA
5 mA
6 mA
7 mA
8 mA
9 mA
10 mA
11 mA
We recommend the use of three-wire proximity switches on these inputs.
512/612 Modicon Micro PLCs
27
Page 29
Circuit Characteristics Simplified schematic Field side
28
Logic side
Isolation Method Channel-to-bus Group-to-group
Opto-coupler 1780 VAC, 2500 VDC 1780 VAC, 2500 VDC
Response time ON®OFF OFF®ON
2 ms 2 ms
Maximum wire length
100 m
Wire size
14 AWG
512/612 Modicon Micro PLCs
890 USE 145 00
Page 30
User-selectable High-speed Counter/interrupt Inputs Electrical Characteristics ON level
15 ... 30 VDC
OFF level
0 ... 5 VDC
Minimum ON state input
6 mA @ 24 VDC
Maximum OFF current
0.7 mA @ 5 V
Input impedance
15.8 kW when OFF 1.95 kW when ON @ 24 VDC
Current draw
12.3 mA @ 24 VDC
Typical impedance curve 25 V
INPUT VOLTAGE
20 V
15 V
10 V
+5 V
0 mA
2 mA
Note
We recommend the use of three-wire proximity switches on these inputs.
890 USE 145 00
4 mA
6 mA
8 mA
10 mA
12 mA
14 mA
512/612 Modicon Micro PLCs
29