Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual ยท part 2 of 6

Modicon 512/612 Micro PLC Hardware User Manual, pages 11 to 20

Pages 11 to 20 of 60

The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Modicon 110 CPU 512 02, Modicon 110 CPU 612 00, AEG 110 CPU 512 02, Gould 110 CPU 512 02, Schneider 110 CPU 512 02, AEG 110 CPU 612 00, Gould 110 CPU 612 00 and Schneider 110 CPU 612 00

Page 11

Fixed Analog I/O in the 612 Models The 110CPU61200, 62103 and 61204 PLCs have the additional feature of fixed analog inputs and outputs. The analog I/O is labeled across the lower left front of the unit assembly, the inputs labeled 21 ... 10 from left to right and the outputs labeled 9 ... 1 left to right. Here is how the front of the unit looks:

Front View of a 612 PLC

The additional connectors for analog input and output channels are located on the bottom of the unit to the left of the

10

512/612 Modicon Micro PLCs comm ports. The illustration on the following page shows the pin positions.

890 USE 145 00

Page 12

Analog inputs

21 20 19 18 17 16 15 14 13 12 11 10

Analog outputs

9

8 7 comm 1 RS-232 port

6 5 4 3 comm 2 RS-232 port

Exp. network RS-485 port

2 1

A Bottom View of a 612 CPU Unit

Two analog connectors are provided with the 612 PLCs - a 12-pin analog input connector and a 9-pin analog output connector. Each pin number is displayed on the connector.

890 USE 145 00

512/612 Modicon Micro PLCs

11

Page 13

Base Unit Specifications Electrical Input voltages 120 VAC input 230 VAC input 24 VDC input

96 ... 132 V RMS, 47 ... 63 Hz 192 ... 264 V RMS, 47 ... 63 Hz 19.2 ... 30.0 VDC

Output voltage 24 VDC output

20.5 ... 29.0 VDC @ .15 A maximum

Output ripple and noise 24 VDC output

2.5 V peak-to-peak @ 100/120 Hz maximum

Electrical immunity ESD

IEC 801-2, level 3

Radiated EMI

IEC 801-3, level 3

Fast transient

IEC 801-4, level 2

Surge transient

IEC 801-5, level 3

Input power interrupt AC inputs DC inputs

< 0.5 period with no affect < 1 ms with no affect

Ring wave Isolation voltages AC in to system ground AC in to chassis ground DC in to system ground

IEEE-STD 472 (1974) IEC-255-4, level 3 1780 V RMS, 1 min 1780 V RMS, 1 min 500 V RMS, 1 min

Input Power Specifications (Values in Amps)

12

512/612 Modicon Micro PLCs

890 USE 145 00

Page 14

Part Number

I/O and CPU Description

Base Unit 6 or less Outputs ON

Base Unit Add if More than 6 Hand--Held Outputs ON is Used

Add if PAB is Used

110CPU51200 DC Relay CPU 24V

.30

.50

.05

.125

110CPU61200 DC Relay CPU 24V

.30

.50

.05

.125

110CPU61204 DC Relay CPU 24V

.30

.50

.05

.125

110CPU51203 DC/DC FET CPU 24V

.25

.27

.05

.125

110CPU61203 DC/DC FET CPU 24V

.25

.27

.05

.125

890 USE 145 00

512/612 Modicon Micro PLCs

13

Page 15

Input Power Specifications (continued) (Values in VA)

Part Number

I/O and CPU Description

Base Unit 6 or less Outputs ON

Base Unit Add if More than 6 Hand--Held Outputs ON is Used

Add if PAB is Used

110CPU51201 115VAC/Triac CPU 115V

21.0

23.1

2.1

5.25

110CPU51202 230VAC/Triac CPU 230V

21.0

23.1

2.1

5.25

Input voltage fuses AC inputs DC inputs Power for external devices for a programming panel for A120 I/O expansion

14

1/

4 A SB in each primary input transformer 1.6 A SB in series with the input circuit

+5 VDC @ 150 mA continuous (maximum) +5 VDC @ 250 mA continuous (maximum)

512/612 Modicon Micro PLCs

890 USE 145 00

Page 16

Environmental Operating Temperature

0 ... 60 degrees C

Storage Temperature

--40 ... +85 degrees C

Relative Humidity

95% noncondensing

Altitude

3800 m (15,000 ft)

Shock

30 g for 11 ms, 3 pulses/axis for up to 18 pulses

Vibration

10 ... 62 Hz @ .075 mm displacement amplitude, 62 ... 500 Hz @ 1 g Duration: 23 min @ 2 sweeps/axis on 3 mutually orthogonal axes at a rate of 1 octave/min

Dimensions Height (including I/O terminal blocks): Width: Depth:

158.75 mm (6.25 in) 254 mm (10 in) 76 mm (3 in)

Weight

1.45 kg (3.2 lb)

Chemical Environmental

Enclosures are made of Lexan, a polycarbonate that can be damaged by strong alkaline solutions

Agency Approvals All models are F.M. Class I, Div. 2 approved (except for the 61204 which is pending), and are designed to meet VDE 0160 standards The following models are UL 508 Listed for Industrial Control Equipment and CSA 142 Certified for process control equipment: 110CPU51200 110CPU51201 110CPU51202 110CPU61200 110CPU61203 110CPU61204 The 110CPU51203 is CSA Certified, with UL pending CE Compliance To maintain compliance with the European Directive on EMC (89/336/EEC), the Micro controller must be installed in accordance with these installation instructions. Conformal Coating The 61204 is available as an option with conformal coating, (110CPU61204C).

890 USE 145 00

512/612 Modicon Micro PLCs

15

Page 17

Optional Hardware Part Numbers RS-232 communication cable assemblies (with RJ45 connectors on both ends) 1 m (3 ft) 110XCA28201 3 m (10 ft) 110XCA28202 6 m (20 ft) 110XCA28203 RS-485 I/O expansion link cable assemblies (with RJ11 connectors on both ends) 61 cm (2 ft) 110XCA17101 3 m (10 ft) 110XCA17102 6 m (20 ft) 110XCA17103

16

1000 ft reels of flat cable Eight-position (for RS-232) Six-position (for RS-485)

490NAA00010 490NAA00020

RJ45 connectors (20/box) RJ11 connectors (20/box)

490NAD00010 490NAD00020

RJ type connector tool RJ11 die set RJ45 die set

490NAB00010 490NAB00011 490NAB00012

RJ11 Y--connector

110XCA10100

RJ45 adapter connections 9-pin Premade for PC-ATs Wire-it-yourself (male) Wire-it-yourself (female)

110XCA20300 110XCA20301 110XCA20302

25-pin Premade for PC-XTs Wire-it-yourself (male) Wire-it-yourself (female)

110XCA20400 110XCA20401 110XCA20402

Lithium battery assembly

110XCP98000

Battery capacitor assembly

110XCP99000

Spare I/O terminal strips and covers Input (22-pin) Output (20-pin)

110XTS00122 110XTS00120

512/612 Modicon Micro PLCs

890 USE 145 00

Page 18

Partial Sampling of Available A120 I/O Modules Discrete Input Modules 8 point 230 VAC 8 point 115 VAC 8 point 115 VAC 16 point 24 VDC (isolated) 16 point 24 VDC (non--isolated) 16 point 24 VDC Fast Response 16 point 115 VAC

AS-BDEP-208 AS-BDEP-209 AS-BDEP-210 AS-BDEP-216 AS-BDEO-216 AS-BDEP-220 AS-BDEP-218

Discrete Output Modules 4 point Relay 8 point Relay 8 point 115 VAC 8 point 24-230 VAC 16 point 115 VAC 16 point 24 VDC (isolated) 16 point 24 VDC

AS-BDAP-204 AS-BDAP-208 AS-BDAP-209 AS-BDAP-210 AS-BDAP-218 AS-BDAP-216 AS-BDAO-216

Discrete Combination Modules 8 point 24 VDC in / 4 point Relay out 8 point 24 VDC in / 8 point 24 VDC / 2 A out

AS-BDAP-212 AS-BDAP-220

Analog Input Modules 4 channel +500 mV RTD AS-BADU-204 4 channel +10 V/+20 mA AS-BADU-205 4 channel 12 bit AS-BADU-206 8 channel 12 bit RTD TC Vdc mA AS--BADU-21x 8 channel 12 bit RTD Vdc mA AS--BADU-214 8 channel 15 bit TC Vdc AS--BADU-216 Analog Output Modules 2 channel +10V / +20 mA AS-BDAU-202 8 channel +10 V AS-BDAU-208 Intelligent Modules 4 point turbine meter/frequency AS-BVRC-2xx 4 point high speed input AS-BCTR-2xx 4 channel 50 kHz high speed counter AS-BZAE-204 For more details and a complete listing of all current A120 I/O modules, see Modicon A120 Series I/O Modules User Guide, 890USE10900 formerly GM-A984-IOS.

890 USE 145 00

512/612 Modicon Micro PLCs

17

Page 19

Fixed I/O Specifications 110CPU51200/61200 Field Wiring (under 24 VDC power) Fixed Discrete I/O Topology I/O Type

Number of I/O Points

Number of Groups 2 groups of 8

24 VDC inputs

16

24 VDC user-selectable counter/interrupt

1

24 VDC dedicated high-speed interrupts

2

Relay outputs

12

1 group of 3

2 groups of 4 and 4 individually isolated with Source-configured 24 VDC Inputs 24 V common

Group B common

24 V common

Group A common

24 VDC

24 VDC .16 A

Cnt/ Int 2 int

Int 1

In In In In In In In In 16 15 14 13 12 11 10 9

In 8

In In 7 6

In 5

In 4

In 3

In 2

In 1

8

7

5

4

3

2

1

24 V

.16 A

24 V 22 21 20 19 18 17 16 15 14 13 12 11 10

User-selectable counter or Dedicated interrupt interrupts Cnt/int com

9

6

Group A 24 VDC Inputs

Group B 24 VDC Inputs

Modicon 110CPU51200 110CPU61200 110CPU61204 Group D common Group C common Group D Relay Outputs

Group C Relay Outputs

20 19 18 17 16 15 14 13 12 11 10

Isolated Relay Outputs 9

8

7

6

5

4

3

2 1

3 A Fuses

Out 4A L L 12 11

L L 10 9

L 8

L 7

L 6

L 5

L 4

Out Out Out Out Out Out Out Out Out 12 11 10 9 8 7 6 5 4B Note Fast-blow fuses are recommended for input and output protection.

18

512/612 Modicon Micro PLCs

Out 3A

Out 2A

Out 1A

L 3

L 2

L 1

Out 3B

Out 2B

Out 1B

890 USE 145 00

Page 20

with Sink-configured 24 VDC Inputs Cnt/ Int 2 int

Int 1

.16 A Fuse

.16 A Fuse

In In In In In In In In 16 15 14 13 12 11 10 9

In 8

In In 7 6

In 5

In 4

In 3

In 2

In 1

24 V

24 V 22 21 20 19 18 17 16 15 14 13 12 11 10

User-selectable Dedicated counter or interrupts Cnt/int com interrupt

9

8

7

Group B 24 VDC Inputs

6

5

4

3

2

1

Group A 24 VDC Inputs

Modicon 110CPU51200 110CPU61200 110CPU61204 Group D common Group C common Group D Relay Outputs

Group C Relay Outputs

20 19 18 17 16 15 14 13 12 11 10

Isolated Relay Outputs 9

8

7

6

5

4

3

2 1

3 A Fuses

Out 4A 24 V common 24 VDC

L L 12 11

L L 10 9

Out Out Out Out 12 11 10 9

Out 2A

Out 1A

L 5

L 4

L 3

L 2

L 1

Out Out Out Out 8 7 6 5

Out 4B

Out 3B

Out 2B

Out 1B

L 8

L 7

L 6

Out 3A

24 VDC

24 V common

Note Fast-blow fuses are recommended for input and output protection.

Note To reduce the risk that electrical noise from field I/O devices will effect Micro operation, we recommend that a separate 24 VDC power source be used for the field I/O. A dual power-source configuration can also be beneficial in preventing a failure in a single field device from shutting down power to the PLC. Note The wiring for the analog I/O of the 612s is shown in the simplified schematics on pages 40 (for the inputs) and 42 (for the outputs).

890 USE 145 00

512/612 Modicon Micro PLCs

19