Page 11
Fixed Analog I/O in the 612 Models The 110CPU61200, 62103 and 61204 PLCs have the additional feature of fixed analog inputs and outputs. The analog I/O is labeled across the lower left front of the unit assembly, the inputs labeled 21 ... 10 from left to right and the outputs labeled 9 ... 1 left to right. Here is how the front of the unit looks:
Front View of a 612 PLC
The additional connectors for analog input and output channels are located on the bottom of the unit to the left of the
10
512/612 Modicon Micro PLCs comm ports. The illustration on the following page shows the pin positions.
890 USE 145 00
Page 12
Analog inputs
21 20 19 18 17 16 15 14 13 12 11 10
Analog outputs
9
8 7 comm 1 RS-232 port
6 5 4 3 comm 2 RS-232 port
Exp. network RS-485 port
2 1
A Bottom View of a 612 CPU Unit
Two analog connectors are provided with the 612 PLCs - a 12-pin analog input connector and a 9-pin analog output connector. Each pin number is displayed on the connector.
890 USE 145 00
512/612 Modicon Micro PLCs
11
Page 13
Base Unit Specifications Electrical Input voltages 120 VAC input 230 VAC input 24 VDC input
96 ... 132 V RMS, 47 ... 63 Hz 192 ... 264 V RMS, 47 ... 63 Hz 19.2 ... 30.0 VDC
Output voltage 24 VDC output
20.5 ... 29.0 VDC @ .15 A maximum
Output ripple and noise 24 VDC output
2.5 V peak-to-peak @ 100/120 Hz maximum
Electrical immunity ESD
IEC 801-2, level 3
Radiated EMI
IEC 801-3, level 3
Fast transient
IEC 801-4, level 2
Surge transient
IEC 801-5, level 3
Input power interrupt AC inputs DC inputs
< 0.5 period with no affect < 1 ms with no affect
Ring wave Isolation voltages AC in to system ground AC in to chassis ground DC in to system ground
IEEE-STD 472 (1974) IEC-255-4, level 3 1780 V RMS, 1 min 1780 V RMS, 1 min 500 V RMS, 1 min
Input Power Specifications (Values in Amps)
12
512/612 Modicon Micro PLCs
890 USE 145 00
Page 14
Part Number
I/O and CPU Description
Base Unit 6 or less Outputs ON
Base Unit Add if More than 6 Hand--Held Outputs ON is Used
Add if PAB is Used
110CPU51200 DC Relay CPU 24V
.30
.50
.05
.125
110CPU61200 DC Relay CPU 24V
.30
.50
.05
.125
110CPU61204 DC Relay CPU 24V
.30
.50
.05
.125
110CPU51203 DC/DC FET CPU 24V
.25
.27
.05
.125
110CPU61203 DC/DC FET CPU 24V
.25
.27
.05
.125
890 USE 145 00
512/612 Modicon Micro PLCs
13
Page 15
Input Power Specifications (continued) (Values in VA)
Part Number
I/O and CPU Description
Base Unit 6 or less Outputs ON
Base Unit Add if More than 6 Hand--Held Outputs ON is Used
Add if PAB is Used
110CPU51201 115VAC/Triac CPU 115V
21.0
23.1
2.1
5.25
110CPU51202 230VAC/Triac CPU 230V
21.0
23.1
2.1
5.25
Input voltage fuses AC inputs DC inputs Power for external devices for a programming panel for A120 I/O expansion
14
1/
4 A SB in each primary input transformer 1.6 A SB in series with the input circuit
+5 VDC @ 150 mA continuous (maximum) +5 VDC @ 250 mA continuous (maximum)
512/612 Modicon Micro PLCs
890 USE 145 00
Page 16
Environmental Operating Temperature
0 ... 60 degrees C
Storage Temperature
--40 ... +85 degrees C
Relative Humidity
95% noncondensing
Altitude
3800 m (15,000 ft)
Shock
30 g for 11 ms, 3 pulses/axis for up to 18 pulses
Vibration
10 ... 62 Hz @ .075 mm displacement amplitude, 62 ... 500 Hz @ 1 g Duration: 23 min @ 2 sweeps/axis on 3 mutually orthogonal axes at a rate of 1 octave/min
Dimensions Height (including I/O terminal blocks): Width: Depth:
158.75 mm (6.25 in) 254 mm (10 in) 76 mm (3 in)
Weight
1.45 kg (3.2 lb)
Chemical Environmental
Enclosures are made of Lexan, a polycarbonate that can be damaged by strong alkaline solutions
Agency Approvals All models are F.M. Class I, Div. 2 approved (except for the 61204 which is pending), and are designed to meet VDE 0160 standards The following models are UL 508 Listed for Industrial Control Equipment and CSA 142 Certified for process control equipment: 110CPU51200 110CPU51201 110CPU51202 110CPU61200 110CPU61203 110CPU61204 The 110CPU51203 is CSA Certified, with UL pending CE Compliance To maintain compliance with the European Directive on EMC (89/336/EEC), the Micro controller must be installed in accordance with these installation instructions. Conformal Coating The 61204 is available as an option with conformal coating, (110CPU61204C).
890 USE 145 00
512/612 Modicon Micro PLCs
15
Page 17
Optional Hardware Part Numbers RS-232 communication cable assemblies (with RJ45 connectors on both ends) 1 m (3 ft) 110XCA28201 3 m (10 ft) 110XCA28202 6 m (20 ft) 110XCA28203 RS-485 I/O expansion link cable assemblies (with RJ11 connectors on both ends) 61 cm (2 ft) 110XCA17101 3 m (10 ft) 110XCA17102 6 m (20 ft) 110XCA17103
16
1000 ft reels of flat cable Eight-position (for RS-232) Six-position (for RS-485)
490NAA00010 490NAA00020
RJ45 connectors (20/box) RJ11 connectors (20/box)
490NAD00010 490NAD00020
RJ type connector tool RJ11 die set RJ45 die set
490NAB00010 490NAB00011 490NAB00012
RJ11 Y--connector
110XCA10100
RJ45 adapter connections 9-pin Premade for PC-ATs Wire-it-yourself (male) Wire-it-yourself (female)
110XCA20300 110XCA20301 110XCA20302
25-pin Premade for PC-XTs Wire-it-yourself (male) Wire-it-yourself (female)
110XCA20400 110XCA20401 110XCA20402
Lithium battery assembly
110XCP98000
Battery capacitor assembly
110XCP99000
Spare I/O terminal strips and covers Input (22-pin) Output (20-pin)
110XTS00122 110XTS00120
512/612 Modicon Micro PLCs
890 USE 145 00
Page 18
Partial Sampling of Available A120 I/O Modules Discrete Input Modules 8 point 230 VAC 8 point 115 VAC 8 point 115 VAC 16 point 24 VDC (isolated) 16 point 24 VDC (non--isolated) 16 point 24 VDC Fast Response 16 point 115 VAC
AS-BDEP-208 AS-BDEP-209 AS-BDEP-210 AS-BDEP-216 AS-BDEO-216 AS-BDEP-220 AS-BDEP-218
Discrete Output Modules 4 point Relay 8 point Relay 8 point 115 VAC 8 point 24-230 VAC 16 point 115 VAC 16 point 24 VDC (isolated) 16 point 24 VDC
AS-BDAP-204 AS-BDAP-208 AS-BDAP-209 AS-BDAP-210 AS-BDAP-218 AS-BDAP-216 AS-BDAO-216
Discrete Combination Modules 8 point 24 VDC in / 4 point Relay out 8 point 24 VDC in / 8 point 24 VDC / 2 A out
AS-BDAP-212 AS-BDAP-220
Analog Input Modules 4 channel +500 mV RTD AS-BADU-204 4 channel +10 V/+20 mA AS-BADU-205 4 channel 12 bit AS-BADU-206 8 channel 12 bit RTD TC Vdc mA AS--BADU-21x 8 channel 12 bit RTD Vdc mA AS--BADU-214 8 channel 15 bit TC Vdc AS--BADU-216 Analog Output Modules 2 channel +10V / +20 mA AS-BDAU-202 8 channel +10 V AS-BDAU-208 Intelligent Modules 4 point turbine meter/frequency AS-BVRC-2xx 4 point high speed input AS-BCTR-2xx 4 channel 50 kHz high speed counter AS-BZAE-204 For more details and a complete listing of all current A120 I/O modules, see Modicon A120 Series I/O Modules User Guide, 890USE10900 formerly GM-A984-IOS.
890 USE 145 00
512/612 Modicon Micro PLCs
17
Page 19
Fixed I/O Specifications 110CPU51200/61200 Field Wiring (under 24 VDC power) Fixed Discrete I/O Topology I/O Type
Number of I/O Points
Number of Groups 2 groups of 8
24 VDC inputs
16
24 VDC user-selectable counter/interrupt
1
24 VDC dedicated high-speed interrupts
2
Relay outputs
12
1 group of 3
2 groups of 4 and 4 individually isolated with Source-configured 24 VDC Inputs 24 V common
Group B common
24 V common
Group A common
24 VDC
24 VDC .16 A
Cnt/ Int 2 int
Int 1
In In In In In In In In 16 15 14 13 12 11 10 9
In 8
In In 7 6
In 5
In 4
In 3
In 2
In 1
8
7
5
4
3
2
1
24 V
.16 A
24 V 22 21 20 19 18 17 16 15 14 13 12 11 10
User-selectable counter or Dedicated interrupt interrupts Cnt/int com
9
6
Group A 24 VDC Inputs
Group B 24 VDC Inputs
Modicon 110CPU51200 110CPU61200 110CPU61204 Group D common Group C common Group D Relay Outputs
Group C Relay Outputs
20 19 18 17 16 15 14 13 12 11 10
Isolated Relay Outputs 9
8
7
6
5
4
3
2 1
3 A Fuses
Out 4A L L 12 11
L L 10 9
L 8
L 7
L 6
L 5
L 4
Out Out Out Out Out Out Out Out Out 12 11 10 9 8 7 6 5 4B Note Fast-blow fuses are recommended for input and output protection.
18
512/612 Modicon Micro PLCs
Out 3A
Out 2A
Out 1A
L 3
L 2
L 1
Out 3B
Out 2B
Out 1B
890 USE 145 00
Page 20
with Sink-configured 24 VDC Inputs Cnt/ Int 2 int
Int 1
.16 A Fuse
.16 A Fuse
In In In In In In In In 16 15 14 13 12 11 10 9
In 8
In In 7 6
In 5
In 4
In 3
In 2
In 1
24 V
24 V 22 21 20 19 18 17 16 15 14 13 12 11 10
User-selectable Dedicated counter or interrupts Cnt/int com interrupt
9
8
7
Group B 24 VDC Inputs
6
5
4
3
2
1
Group A 24 VDC Inputs
Modicon 110CPU51200 110CPU61200 110CPU61204 Group D common Group C common Group D Relay Outputs
Group C Relay Outputs
20 19 18 17 16 15 14 13 12 11 10
Isolated Relay Outputs 9
8
7
6
5
4
3
2 1
3 A Fuses
Out 4A 24 V common 24 VDC
L L 12 11
L L 10 9
Out Out Out Out 12 11 10 9
Out 2A
Out 1A
L 5
L 4
L 3
L 2
L 1
Out Out Out Out 8 7 6 5
Out 4B
Out 3B
Out 2B
Out 1B
L 8
L 7
L 6
Out 3A
24 VDC
24 V common
Note Fast-blow fuses are recommended for input and output protection.
Note To reduce the risk that electrical noise from field I/O devices will effect Micro operation, we recommend that a separate 24 VDC power source be used for the field I/O. A dual power-source configuration can also be beneficial in preventing a failure in a single field device from shutting down power to the PLC. Note The wiring for the analog I/O of the 612s is shown in the simplified schematics on pages 40 (for the inputs) and 42 (for the outputs).
890 USE 145 00
512/612 Modicon Micro PLCs
19