Page 51

Front of the unit

RJ11 Connector at the RS-485 Port

Back of the unit

RS-485 Port Location on the Bottom of a PLC

Serial I/O expansion establishes a parent-child relationship between the units on the link. One Micro PLC acts as the parent - its I/O processor can access the fixed I/O resources of all the child PLCs on the link, and its CPU can perform all the logic-solving activities for the fixed I/O resources on the link. Each child PLC on the link must have a unique numerical address in the range 1 ... 4. Note It is your responsibility as a programmer to make sure that each child has been uniquely addressed when the system is I/O mapped (see Modicon Micro Ladder Logic Manual, 890 USE 146 00, and your panel software documentation for more details). We recommend that you set the child PLCs to RUN mode or power them up before the parent. Individual child PLCs can be disconnected from the I/O expansion link without disrupting communications between the parent and other child PLCs as long as the disconnection does not break the cable link to the other child PLCs.

890 USE 145 00

Caution When a child PLC acts as an intelligent unit on an I/O expansion link - i.e., when the child uses some or all of its fixed I/O resources instead of giving them to the parent - servicing of the hardware interrupts by the child can disrupt predictable logic solving in the parent.

Terminating the Link 120 W termination is provided by tightening the screw labelled J2 on the front right of the PLC below the LED status display. Units are factory-delivered with the J2 screw tightened. The two units on the head and tail ends of an I/O expansion link require termination - i.e., the J2 screws must be tightened. All other units on the link are not terminated - i.e., their J2 screw must be loosened by one turn.

512/612 Modicon Micro PLCs

51

Page 52

A120 I/O Expansion On the right side of the PLC is a 30-pin connector that allows you to connect the unit to a secondary backplane (or rack) containing A120 I/O modules. This expansion capability can support up to 15 A120 I/O modules (depending on the modules’ combined power draw) in up to three DTA racks.

A 512/612 PLC in any operating mode - single, parent, or child - can use A120 I/O expansion. If a PLC using the A120 I/O is a child PLC on an I/O expansion link, the A120 I/O can be accessed only by that child, not by the parent on that expansion link.

A120 I/O tie point

Calculating Power Requirements in an A120 I/O Expansion System The PLC has a 250 mA internal power supply for A120 I/O expansion. When planning an expansion system, you must be aware of the power requirements of the A120 modules you want to use. To calculate these A120 power requirements, add up the maximum internal power draw specified for each module in your expansion system. Internal power specifications can be found in A120 Series I/O Modules User Guide 890USE10900 formerly (GM-A984-IOS).

Caution All internal power requirements for the A120 modules must be satisfied by the Modicon Micro PLC. A total internal power supply of 250 mA is available from the PLC for all modules in all racks. A120 modules such as the BDEP 216 DC input module and the BDAP 208 DC output module, which draw 15 mA each, enable you to power three fully loaded DTA 201 expansion racks. However, in applications that use A120 modules with large internal power draws - e.g., the BDEP 218 AC input module or the BDAP 210 AC output

52

512/612 Modicon Micro PLCs

890 USE 145 00

Page 53

module, which draw 60 mA and 88 mA, respectively - you could expend most of your available power with a few modules in a single DTA rack.

A120 I/O Expansion Racks The DTA 201 backplane is 213.4 mm wide x 142 mm high x 31 mm deep. It has an I/O expansion ribbon cable with 30-receptacle connector on its left side that connects it to the unit prior to it and a 30-pin expansion connector on its right side (the same as the one on the PLC) that enables extension to another backplane.

The DTA 202 backplane is 91.5 mm wide x 142 mm high x 31 mm deep. It also has an I/O expansion ribbon cable with 30-receptacle connector on its left side for connection to the unit prior to it. It does not have a connector on its right side - if the DTA 202 is used, it must be the last rack in the A120 I/O expansion. If you plan to use a DTA 202, remember that no more than one can be used and that it can be used only in a linear drop layout, not in a stacked (two-high) drop layout. Ribbon cable connector

Ribbon cable connector

DTA 202 Two-slot A120 I/O Backplane 30-pin A120 I/O expansion connector

DTA 201 Five-slot A120 I/O Backplane

890 USE 145 00

512/612 Modicon Micro PLCs

53

Page 54

512/612 PLC

DTA 202

Rack 1

Rack 2

512/612 PLC

DTA 201

Rack 1

Rack 2

512/612 PLC

DTA 201

DTA 202

Rack 1

Rack 2

Rack 3

512/612 PLC

DTA 201

DTA 201

Rack 1

Rack 2

Rack 3

512/612 PLC

DTA 201

DTA 201

DTA 202

Rack 1

Rack 2

Rack 3

Rack 4

512/612 PLC

Rack 1

DTA 201

Rack 2

DTA 201

Rack 3

DTA 201

Rack 4

Linear A120 I/O Expansion Layouts

54

512/612 Modicon Micro PLCs

890 USE 145 00

Page 55

Caution The connectors on the BXT 201 cable are polarized and must be connected properly - the A connector must be attached to the rightmost unit on the top DIN rail and the B connector must be attached to the rightmost unit on the bottom DIN rail.

The racks may also be stacked on two DIN rails and connected by a BXT 201 bus extension cable. There may be either one or two racks mounted on each DIN rail. Only DTA 201 backplanes can be used for A120 I/O in a stacked layout - DTA 202 (two-slot) backplanes are not allowed. PLC

PLC

A

A

Rack 1 DTA 201

DTA 201

Rack 1 BXT 201

DTA 201

BXT 201 B

B

Rack 2

PLC

Rack 3

Rack 3

DTA 201

PLC

DTA 201

A Rack 1

Rack 2

DTA 201

A Rack 1

BXT 201

DTA 201

Rack 2 DTA 201

BXT 201

B

Rack 3

Rack 4

B

Rack 4

Stacked A120 I/O Expansion Layouts

Note The rack numbers in a stacked layout are determined by the way the rack on the right side of the lower level is connected via BXT 201 cable to the PLC or to rack 1 above.

890 USE 145 00

512/612 Modicon Micro PLCs

55

Page 56

PLC

PLC

A Rack 1 DTA 201

A Rack 1

BXT 202

DTA 201

BXT 202

DTA 201 B

B

Rack 2

PLC

Rack 3

Rack 2

DTA 201

DTA 201

PLC

A Rack 1 DTA 201

A Rack 1

Rack 2

Rack 2

BXT 202 DTA 201

B

BXT 202

DTA 201 B

Rack 3

Rack 4

Rack 3

Stacked A120 I/O Expansion Layouts

56

512/612 Modicon Micro PLCs

890 USE 145 00

Page 57

Connecting the PLC to a Programming Panel A programming panel - for example, the 520VPU19200 Hand-held Programmer* (HHP) or a personal computer running

Modsoft programming software - can be connected to the PLC at one of its two RS-232 ports, comm 1 or comm 2. RJ45 Connectors at the RS-232 Ports

Front of the unit

Back of the unit

RS-232 Port Locations on the Bottom of a PLC

RS-232 Cable Cables

RS-232 Cable Connectors

Standard eight-position, foil-shielded, flat telephone cables with male RJ45 connectors on each end are used to connect the units. Three premade cable assemblies are available:

Two female D-shell adapters are available from Modicon for PLC-to-computer connections - a (110XCA20300) 9-pin adapter for PC-AT type computers and a (110XCA20400) 25-pin adapter for PC-XT type computers.

RS-232 Communications Cables Length

Part Number

1 m (3 ft)

110XCA28201

3m

(10 ft)

110XCA28202

6m

(20 ft)

110XCA28203

These adapters come equipped with an RJ45 jack that allows them to clip directly onto a cable assembly. Details are shown on the following page.

* Does not support the 61204.

890 USE 145 00

512/612 Modicon Micro PLCs

57

Page 58

110XCA20300 9-pin Female Adapter

Micro

9-pin D-shell

1*

1

DCD

TXD 3

2

RXD

RXD 4

3

TXD

DSR 2

4

DTR

GND 5

5

GND pin 1 pin 9

4--40 screw threads

RJ45 jack (8x8)

PC-AT Pinouts

RJ45 Connector

6

DSR

CTS

7

7

RTS

RTS

6

8

CTS

9

RI chassis ground

8 case of the connector

* CAUTION: Pin 1 receives 5 V from the Micro 50.8 mm (2 in)

pin 1

110XCA20400 25-pin Female Adapter

Micro RJ45 Connector

4--40 jack screws

1

RXD 4

2

TXD

TXD 3

3

RXD

CTS 7

4

RTS

RTS 6

5

CTS

6

DSR

7

GND

8

DCD

GND

RJ45 jack (8x8)

25-pin D-shell

1* pin 1 pin 25

PC-XT Pinouts

5

DSR

2

20

DTR chassis ground

8

1 chassis ground

* CAUTION: Pin 1 receives 5 V from the Micro

39.6 mm (1.56 in)

58 pin 1

512/612 Modicon Micro PLCs

890 USE 145 00

Page 59

Index Numbers 115 VAC input specifications, 24, 25 24 VDC (FET) output specifications, with 512/612, 37 24 VDC digital output specifications, 32, 35 512 controller A120 I/O expansion with, 51 base unit specifications, 13 fixed I/O specifications, 18 general hardware characteristics, 3 hardware overview, 6 installation, 43 optional battery/battery capacitor, 48 parent/child concept, 4 PLC status display, 9 serial I/O expansion link with, 49 612 controller A120 I/O expansion with, 51 base unit specifications, 13 fixed analog I/O with, 11 fixed I/O specifications, 18 general hardware characteristics, 3 hardware overview, 6 installation, 43 optional battery/battery capacitor, 48 parent/child concept, 4 PLC status display, 9 serial I/O expansion link with, 49

A A120 I/O expansion power requirements with, 51 racks for, 52 with 512/612, 51 analog inputs, characteristics of, 39 analog outputs, characteristics of, 41

B battery/battery capacitor, with 512/612, 48

C connecting PLC to a programming panel, 55

F fixed analog I/O, 11

I I/O specifications digital inputs, 24, 25, 29, 31 digital outputs, 32, 35 FET outputs, 37 input specifications 115 VAC, 24, 25 interrupt inputs, 29, 31 interrupt input specifications, 29, 31

890 USE 145 00

Index

59

Page 60

O output specifications 115/230 VAC triacs, 35 24 VDC, 32, 35 24 VDC (FET), 37 relays, 32

P parent/child concept with 512/612, 4 with 512/612 serial I/O, 49

R relay output specifications, 32

S specifications base unit, 13 fixed I/O, 18

T triac output specifcations, 35

60

Index

890 USE 145 00