The text of a manual · part 6 of 6
Modicon 512/612 Micro PLC Hardware User Manual, pages 51 to 60
Pages 51 to 60 of 60
The original document is the PDF (13 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Modicon 110 CPU 512 02, Modicon 110 CPU 612 00, AEG 110 CPU 512 02, Gould 110 CPU 512 02, Schneider 110 CPU 512 02, AEG 110 CPU 612 00, Gould 110 CPU 612 00 and Schneider 110 CPU 612 00
Page 51
Front of the unit
RJ11 Connector at the RS-485 Port
Back of the unit
RS-485 Port Location on the Bottom of a PLC
Serial I/O expansion establishes a parent-child relationship between the units on the link. One Micro PLC acts as the parent - its I/O processor can access the fixed I/O resources of all the child PLCs on the link, and its CPU can perform all the logic-solving activities for the fixed I/O resources on the link. Each child PLC on the link must have a unique numerical address in the range 1 ... 4. Note It is your responsibility as a programmer to make sure that each child has been uniquely addressed when the system is I/O mapped (see Modicon Micro Ladder Logic Manual, 890 USE 146 00, and your panel software documentation for more details). We recommend that you set the child PLCs to RUN mode or power them up before the parent. Individual child PLCs can be disconnected from the I/O expansion link without disrupting communications between the parent and other child PLCs as long as the disconnection does not break the cable link to the other child PLCs.
890 USE 145 00
Caution When a child PLC acts as an intelligent unit on an I/O expansion link - i.e., when the child uses some or all of its fixed I/O resources instead of giving them to the parent - servicing of the hardware interrupts by the child can disrupt predictable logic solving in the parent.
Terminating the Link 120 W termination is provided by tightening the screw labelled J2 on the front right of the PLC below the LED status display. Units are factory-delivered with the J2 screw tightened. The two units on the head and tail ends of an I/O expansion link require termination - i.e., the J2 screws must be tightened. All other units on the link are not terminated - i.e., their J2 screw must be loosened by one turn.
512/612 Modicon Micro PLCs
51
Page 52
A120 I/O Expansion On the right side of the PLC is a 30-pin connector that allows you to connect the unit to a secondary backplane (or rack) containing A120 I/O modules. This expansion capability can support up to 15 A120 I/O modules (depending on the modules’ combined power draw) in up to three DTA racks.
A 512/612 PLC in any operating mode - single, parent, or child - can use A120 I/O expansion. If a PLC using the A120 I/O is a child PLC on an I/O expansion link, the A120 I/O can be accessed only by that child, not by the parent on that expansion link.
A120 I/O tie point
Calculating Power Requirements in an A120 I/O Expansion System The PLC has a 250 mA internal power supply for A120 I/O expansion. When planning an expansion system, you must be aware of the power requirements of the A120 modules you want to use. To calculate these A120 power requirements, add up the maximum internal power draw specified for each module in your expansion system. Internal power specifications can be found in A120 Series I/O Modules User Guide 890USE10900 formerly (GM-A984-IOS).
Caution All internal power requirements for the A120 modules must be satisfied by the Modicon Micro PLC. A total internal power supply of 250 mA is available from the PLC for all modules in all racks. A120 modules such as the BDEP 216 DC input module and the BDAP 208 DC output module, which draw 15 mA each, enable you to power three fully loaded DTA 201 expansion racks. However, in applications that use A120 modules with large internal power draws - e.g., the BDEP 218 AC input module or the BDAP 210 AC output
52
512/612 Modicon Micro PLCs
890 USE 145 00
Page 53
module, which draw 60 mA and 88 mA, respectively - you could expend most of your available power with a few modules in a single DTA rack.
A120 I/O Expansion Racks The DTA 201 backplane is 213.4 mm wide x 142 mm high x 31 mm deep. It has an I/O expansion ribbon cable with 30-receptacle connector on its left side that connects it to the unit prior to it and a 30-pin expansion connector on its right side (the same as the one on the PLC) that enables extension to another backplane.
The DTA 202 backplane is 91.5 mm wide x 142 mm high x 31 mm deep. It also has an I/O expansion ribbon cable with 30-receptacle connector on its left side for connection to the unit prior to it. It does not have a connector on its right side - if the DTA 202 is used, it must be the last rack in the A120 I/O expansion. If you plan to use a DTA 202, remember that no more than one can be used and that it can be used only in a linear drop layout, not in a stacked (two-high) drop layout. Ribbon cable connector
Ribbon cable connector
DTA 202 Two-slot A120 I/O Backplane 30-pin A120 I/O expansion connector
DTA 201 Five-slot A120 I/O Backplane
890 USE 145 00
512/612 Modicon Micro PLCs
53
Page 54
512/612 PLC
DTA 202
Rack 1
Rack 2
512/612 PLC
DTA 201
Rack 1
Rack 2
512/612 PLC
DTA 201
DTA 202
Rack 1
Rack 2
Rack 3
512/612 PLC
DTA 201
DTA 201
Rack 1
Rack 2
Rack 3
512/612 PLC
DTA 201
DTA 201
DTA 202
Rack 1
Rack 2
Rack 3
Rack 4
512/612 PLC
Rack 1
DTA 201
Rack 2
DTA 201
Rack 3
DTA 201
Rack 4
Linear A120 I/O Expansion Layouts
54
512/612 Modicon Micro PLCs
890 USE 145 00
Page 55
Caution The connectors on the BXT 201 cable are polarized and must be connected properly - the A connector must be attached to the rightmost unit on the top DIN rail and the B connector must be attached to the rightmost unit on the bottom DIN rail.
The racks may also be stacked on two DIN rails and connected by a BXT 201 bus extension cable. There may be either one or two racks mounted on each DIN rail. Only DTA 201 backplanes can be used for A120 I/O in a stacked layout - DTA 202 (two-slot) backplanes are not allowed. PLC
PLC
A
A
Rack 1 DTA 201
DTA 201
Rack 1 BXT 201
DTA 201
BXT 201 B
B
Rack 2
PLC
Rack 3
Rack 3
DTA 201
PLC
DTA 201
A Rack 1
Rack 2
DTA 201
A Rack 1
BXT 201
DTA 201
Rack 2 DTA 201
BXT 201
B
Rack 3
Rack 4
B
Rack 4
Stacked A120 I/O Expansion Layouts
Note The rack numbers in a stacked layout are determined by the way the rack on the right side of the lower level is connected via BXT 201 cable to the PLC or to rack 1 above.
890 USE 145 00
512/612 Modicon Micro PLCs
55
Page 56
PLC
PLC
A Rack 1 DTA 201
A Rack 1
BXT 202
DTA 201
BXT 202
DTA 201 B
B
Rack 2
PLC
Rack 3
Rack 2
DTA 201
DTA 201
PLC
A Rack 1 DTA 201
A Rack 1
Rack 2
Rack 2
BXT 202 DTA 201
B
BXT 202
DTA 201 B
Rack 3
Rack 4
Rack 3
Stacked A120 I/O Expansion Layouts
56
512/612 Modicon Micro PLCs
890 USE 145 00
Page 57
Connecting the PLC to a Programming Panel A programming panel - for example, the 520VPU19200 Hand-held Programmer* (HHP) or a personal computer running
Modsoft programming software - can be connected to the PLC at one of its two RS-232 ports, comm 1 or comm 2. RJ45 Connectors at the RS-232 Ports
Front of the unit
Back of the unit
RS-232 Port Locations on the Bottom of a PLC
RS-232 Cable Cables
RS-232 Cable Connectors
Standard eight-position, foil-shielded, flat telephone cables with male RJ45 connectors on each end are used to connect the units. Three premade cable assemblies are available:
Two female D-shell adapters are available from Modicon for PLC-to-computer connections - a (110XCA20300) 9-pin adapter for PC-AT type computers and a (110XCA20400) 25-pin adapter for PC-XT type computers.
RS-232 Communications Cables Length
Part Number
1 m (3 ft)
110XCA28201
3m
(10 ft)
110XCA28202
6m
(20 ft)
110XCA28203
These adapters come equipped with an RJ45 jack that allows them to clip directly onto a cable assembly. Details are shown on the following page.
* Does not support the 61204.
890 USE 145 00
512/612 Modicon Micro PLCs
57
Page 58
110XCA20300 9-pin Female Adapter
Micro
9-pin D-shell
1*
1
DCD
TXD 3
2
RXD
RXD 4
3
TXD
DSR 2
4
DTR
GND 5
5
GND pin 1 pin 9
4--40 screw threads
RJ45 jack (8x8)
PC-AT Pinouts
RJ45 Connector
6
DSR
CTS
7
7
RTS
RTS
6
8
CTS
9
RI chassis ground
8 case of the connector
* CAUTION: Pin 1 receives 5 V from the Micro 50.8 mm (2 in)
pin 1
110XCA20400 25-pin Female Adapter
Micro RJ45 Connector
4--40 jack screws
1
RXD 4
2
TXD
TXD 3
3
RXD
CTS 7
4
RTS
RTS 6
5
CTS
6
DSR
7
GND
8
DCD
GND
RJ45 jack (8x8)
25-pin D-shell
1* pin 1 pin 25
PC-XT Pinouts
5
DSR
2
20
DTR chassis ground
8
1 chassis ground
* CAUTION: Pin 1 receives 5 V from the Micro
39.6 mm (1.56 in)
58 pin 1
512/612 Modicon Micro PLCs
890 USE 145 00
Page 59
Index Numbers 115 VAC input specifications, 24, 25 24 VDC (FET) output specifications, with 512/612, 37 24 VDC digital output specifications, 32, 35 512 controller A120 I/O expansion with, 51 base unit specifications, 13 fixed I/O specifications, 18 general hardware characteristics, 3 hardware overview, 6 installation, 43 optional battery/battery capacitor, 48 parent/child concept, 4 PLC status display, 9 serial I/O expansion link with, 49 612 controller A120 I/O expansion with, 51 base unit specifications, 13 fixed analog I/O with, 11 fixed I/O specifications, 18 general hardware characteristics, 3 hardware overview, 6 installation, 43 optional battery/battery capacitor, 48 parent/child concept, 4 PLC status display, 9 serial I/O expansion link with, 49
A A120 I/O expansion power requirements with, 51 racks for, 52 with 512/612, 51 analog inputs, characteristics of, 39 analog outputs, characteristics of, 41
B battery/battery capacitor, with 512/612, 48
C connecting PLC to a programming panel, 55
F fixed analog I/O, 11
I I/O specifications digital inputs, 24, 25, 29, 31 digital outputs, 32, 35 FET outputs, 37 input specifications 115 VAC, 24, 25 interrupt inputs, 29, 31 interrupt input specifications, 29, 31
890 USE 145 00
Index
59
Page 60
O output specifications 115/230 VAC triacs, 35 24 VDC, 32, 35 24 VDC (FET), 37 relays, 32
P parent/child concept with 512/612, 4 with 512/612 serial I/O, 49
R relay output specifications, 32
S specifications base unit, 13 fixed I/O, 18
T triac output specifcations, 35
60
Index
890 USE 145 00
PR