SECTION 5 584 SYSTEM l/O CONFIGURATIONS

5.1

INTRODUCTION The 584 Programmable Controller’s Input/Output Section can contain either 200 or 500 Series l/O modules, or a combination of both. l/O modules are contained in groups of housings which are configured together as “l/O channels” to the mainframe. The 584 system can support a maximum of 4096 input and 4096 output points, configured as: l

Two local l/O channels, with power supplied from the mainframe l

Two local l/O channels, with auxiliary power supplies l

A remote l/O driver controlling 28 remote I/O channels, with auxiliary power supplies

This section describes configuration and maintenance techniques for 200 and 500 Series l/O modules, housings, Local l/O Channels, Remote l/O Channels, Auxiliary Power Supplies, and ASCII devices configured to the 584 controller. 5.2

200 AND 500 SERIES l/O MODULES Principal features of each series of l/O modules are: 200 Series Modules l l

16 points per module Echo check confirms data transmission. CPU must “refresh” data every 250 milliseconds or active light goes out and all outputs are turned off

500 Series Modules l

4 points per module l

Parity checking only

In addition to the features described above, both 200 and 500 Series modules have the following features: l

Conduit for user wiring l

Clamp terminals for one #12 or two #14 wires l

Module lights for l/O status and fuse condition l l

Individual 1500 Volt opto-isolation from affecting internal logic to prevent field wiring transients

Surge suppressors capable of sinking approximately 80 #5 starters or 350 small relays

5-l

Page 2

l

Can be removed or replaced controller’s scan without interrupting power or the

NOTE Full information on specific types of l/O modules is located in Appendix 6. 5.3

200 SERIES l/O CONFIGURATIONS The 200 Series l/O provides modules with up to 16 circuits each (Figure 5-l). Each module also contains an ACTIVE light which shows mainframe to l/O module communication, and status indicators for each circuit to show ON or OFF status of field terminal voltages.

Figure 5-l

Typical 200 Series I/O Module

Each 200 Series module is color coded (Figure 5-2). AC output modules contain a blown fuse indicator for each output circuit which lights if the fuse is blown. Fuse specifications are listed in Figure 5-3.

5-2

Page 3

%odule 8230 8231 8232 8233 8234 8235 B236 8237 8238 8239 8243 8244 8245 8246

B247

TYPO 115 VAC Output

115 VAC Input 24 Vdc Output 24 Vdc input 220 Vat Output 220 Vat input 5V T-TL Output 5V TTL Input 24 Vdc Output, 2.5A Dual Hi-Speed Counter Analog Input 220 Vat Output, Isolated 220 Vat Input, Isolated 115 Vat Output, Isolated

8266 8270 8271

115 Vat Input, Isolated lo-60 Vdc Output Analog MUX Analog Output (Voltage) Analog Output (4-20 ma) Reed Relay Output 48 Vat Outputs 48 Vat Inputs

B275 lo-60 Vdc Input

8248 8258 8260 8262

Pantone ‘

PMS Code 199 197 286 284 151 149 259 264 354

Color Red Pink Dark Blue Light Blue Orange Melon Violet Light Purple Green

515 109

Blue Yellow

465

Brown

465

Light Brown

233

Rhodamine Red

231 347 101

Dark Pink Green Yellow

380

Light Green

382 298 207 204

Green Silver Blue Dark Red Dark Rubine Red Blue

Module B230 8232 8234 8236 B238* 8243 8244 l B246* 8248 8258 8266 R770

314

Standard Size Pica Fuse 5 amps 7 amps 5 amps 2 amps 3 amps 114 amp 7 amps l/4 amp 7 amps 114 amp 3 amps 112 amp 3 amps 5 amps

Lntlefuse Part No. or Equivalent 275-005 275-007 275-005 275-002 275-003 275-250 275-007 275-250 275-007 275-250 275-003 276-500 2 12-003 275-005 tluantfty per Module 16 1 16 1 17 8 8 1 8 1 16 1 8 16

NOTE:Those modules indicated by an asterisk (*) are provided with one fuse for each output circuit plus one fuse for separate indicator lamp supply.

Figure 5-3

200 Series I10 Fuse Types

Matching System

Figure 5-2

200 Series I/O Color Codes

The modules are installed into a 6240 l/O standard housing which can take up to four modules or a 6241 l/O half housing which can take a maximum of two modules. Type 8242 l/O housings allow for special intrinsically safe modules, such as the B273 input module.

5-3

Page 4

B240 Standard Housings A single channel of l/O can support up to 128 input and 128 output points, which can be configured as up to eight input and eight output Series 200 modules. These sixteen modules can be mounted into four B240 housings - four modules to a housing. Each of the four module positions in a housing has an addressing slot pin that can be set to any address, one through eight. l/O modules that represent discrete (ON/OFF) conditions can be set up to reside at any address, one through eight. Additional addressing information is designed inside each module to identify it to the 584 mainframe as either an input or an output module. When replacing a housing, set the index pins on the new housing to correspond to the settings of the replaced housing. This will ensure that the user field devices will continue to be controlled properly by the user program. Figure 5-4 shows a typical B240 housing.

_ Addressing Index Pin

- Socket For l/O Module

Figure 5-4

5-4

8240 Housing

Page 5

110 modules that use numerical values rather than discrete (ON/OFF) conditions can represent more that one index pin location. See Figure 5-5 for a list of these modules and their requirements. MODULE TYPE

DESCRIPTION

CIRCUITS INPUT

CIRCUITS OUTPUT

INDEX PIN ASSIGNMENT

8239

Dual Hi-Speed Counter (l/O)

2

2

193,597

B243

Analog

Input

4

0

1 or 5

8258

Analog

Multiplexer

0

1

Any

B260

Analog

Voltage

0

4

1 or 5

B262

Analog

Current

0

4

1 or 5

Figure 5-5

Addressing Numerical Value Modules

8241 Half Housings The 8241 housing is addressed in the same manner as B240 housings except that it carries only two modules per housing. The B241 can be used where space problems exist. When replacing a housing, set the index pins on the new housing to correspond to the settings of the replaced housing. This will ensure that the user field devices will continue to be addressed properly by the user program. B242 Housings There are two types of B242 housings. The type B242-004 housing accepts four modules of the intrinsically safe type (B273 input modules). The type 8242-002 accepts two of the intrinsically safe modules. These housings are addressed in the same manner as the 8240 and B241 housings. When replacing a housing, set the index pins on the new housing to correspond to the settings of the replaced housing. This will ensure that the user field devices will continue to be addressed properly by the user program. 200 Series l/O housings are provided with conduits for user wiring and wire clamp terminals to accomodate one AWG #12 or two AWG #14 wires (Fiaure 5-6).

FLEXIBLE (partly rel

HOUSING (bottom view) Figure 5-6

5-5

Series 200 Wire Terminals

Page 6

5.4

500 SERIES l/O CONFIGURATIONS The 500 Series I/O provides modules with four circuits Each 500 Series module is color coded (Figure 5-8).

each (Figure

5-7).

Input and output status lights are provided to show the ON or OFF status of field terminal voltages. All output modules contain blown fuse indicators for each circuit, except B556 5V TTL. 500 Series l/O fuses are type 3AG, normal blow. AC output modules use 5 ampere fuses, and DC modules 3 ampere fuses.

Figure 5-7

Typical 500 Series II0 Module

MODULE TYPE

DESCRIPTION

PMS* CODE

COLOR

8550 B551 8552 8553 8554 B555 B556 B557 8558 B559 8560 B561

115 VAC Output 115 VAC Input DC True High Output DC True High Input 220 VAC Output 220 VAC Input 5v TTL output 5V TTL Input DC True Low Output DC True Low Input 120 VDC Output 120 VDC Input

199 197 286 284 151 149 259 264 314 311 307 305

Red Pink Dark Blue Light Blue Orange Melon Violet Light Purple Turquoise Blue Blue Blue

*Pantone Matching System

Figure 5-8

5-6

500 Series Color Codes

Page 7

The modules are installed into either a B545 l/O housing which can take up to eight modules or a B546 l/O housing which can take a maximum of four modules. A J540 Adaptor is necessary to interface the 500 Series modules with the 584 and is installed between the housings and the 584.

B545 Standard Housings A single Channel of l/O can support up to 128 input and 128 output points, which can be configured as 32 input and 32 output Series 500 modules. These 64 modules can be plugged into eight 8545 housings-eight modules to a housing. Each housing has a set of four STRIP SELECT switches which can be set to select any housing address, one through four. Since there may be up to eight B545 housings present on the l/O channel, a pair of housings may share the same address if one housing contains only input and the other only output modules. Additional addressing information is designed inside each module to identify it to the 584 mainframe as either an input or an output module. When replacing a housing, set the switches on the new housing to correspond to the settings of the replaced housing. This will ensure that the user field devices will continue to be addressed properly by the user program. The location of housing address switches is shown in Figure 5-9.

110 HOUSING ADDRESS SELECTION

Figure 5-9

5-7

B545 Housing Switches

Page 8

6546 Half Housings 8546 half housings are used in locations in which four or less l/O modules will be installed in a housing, or where space is restricted. Each housing has a set of four STRIP SELECT switches which can be set to select any housing address, one through four. Since there may be up to sixteen B546 housings present on the I/O channel, up to four housings may share the same address with two housings containing eight input modules and the other pair of housings containing eight output modules. Additional switches are used to address the modules contained in a housing. In each housing, an UPPER BYTE SELECT switch is set to provide an address for the top two modules, and a LOWER BYTE SELECT switch is set to address the bottom two modules. When replacing a housing, set the switches on the new housing to correspond to the settings of the replaced housing. This will ensure that the user field devices will continue to be addressed properly by the user program. Figure 5-10 illustrates the 8546 housing.

Figure 5-10

5-8

8546 Half Housing

Page 9

500 Series l/O housings are provided with conduits for user wiring and wire clamp terminals to accomodate one AWG #12 or two AWG #I4 wires. The housings are connected across the top with a wiring duct containing the data bus ribbon cable (Figure 5-11).

Figure 5-71

5-9

Series 500 Wire Terminals and Bus Cab/e