Page 10
5.5
J540 ADAPTER In order to interface 500 Series l/O housings and modules with the 584, a J540 Adapter must be attached to each channel. On the front of the J540 are eight input switches and eight output switches used for selecting combinations of 500 Series modules. These will be described below. Also on the front of the J540 are four indicator lights (Figure 5-12): POWER -
On if DC power has been applied.
RUN - On if adapter is receiving a 584 scan at least once every 200 milliseconds. ERROR - On if an Input/Output communications error has been detected and cannot be corrected by error checking capabilities. TEST -
On if adapter is in internal test mode, and test is successful.
Figure 5-12
5-10
J540 Front View
Page 11
5.6
J540 I/O SWITCH SELECTION The 584 communicates with the J540 by sending or receiving 16 l/O points of information. Since each 500 Series l/O module utilizes only four l/O points, the J540 l/O switches address the sixteen Mainframe l/O points to a group of four 500 Series modules. Each J540 output switch will enable a group of four output modules, and each J540 input switch enables a group of four 500 Series input modules. Figure 5-13 shows typical J540 switch settings.
J540
1 outputs =
ON
Z u* 16 output Points (J540 Switch #l)
584
16 Input Points (J540 Switch #7)
4 4
16 l/O Point Communication between 564 and 5540
16 output Points (J540 Switch #2)
500 Series Strip No. 1
Figure 5-13
5-l 1 i I
I c
500 Series Strip No. 4
Typical J540 Switch
Settings
16 Input Points (J540 Switch #a)
Page 12
5.7
INPUT/OUTPUT CHANNEL CONFIGURATIONS The 584 mainframe unit is connected by cables to various l/O housings, containing input or output modules which control user field devices. Groups of housings are connected together, supplied with power, and cabled to the mainframe unit to form “Input/Output Channels” of data flow to and from the mainframe. The 584 is capable of communicating with up to 32 channels of l/O, with each channel controlling up to 128 discrete input points and 128 discrete output points. These channels are connected to the mainframe as either Local or Remote l/O channels. Local l/O channels, as the name implies, are located relatively close to the 584 mainframe. Typical distances from the 584 mainframe to the Local l/O channel housings are six feet or less. Local l/O is connected to the mainframe as Channels 1 through 4, with power for the housings being supplied by the mainframe to Channels 1 and 2, and by auxiliary power supply units to Channels 3 and 4. Remote l/O channels 5 through 32 can be located up to 15,000 feet (4545 metres) away from the 584 mainframe. Channels 5 through 32 communicate with the 584 through a J200 Remote I/O Driver unit connected to a Remote l/O port on the 584 mainframe. Auxiliary power supplies are necessary for these channels. Channels 1 and 2 can also be connected as Remote l/O channels if desired, using 1425 or 1427 Remote l/O Driver units. Auxiliary power supply units are also required. When connected as Remote l/O, these channels can be located up to 5000 feet (1515 metres) from the mainframe unit. Channels 3 and 4 can only be connected as Local I/O channels. There is no restriction as to which channels are used with the mainframe or in their order of placement. There is also no requirement to fully utilize all input or output field device connections to a channel of l/O before connecting devices to another channel.
5-l 2
Page 13
5.8
CHANNELS
1,2 CONFIGURATION Channels
1 and 2 - Local l/O
If Channels 1 and 2 are located six feet or closer to the 584 mainframe, they can serve as Local l/O. They can also serve as local l/O at a maximum distance of 75 feet from the mainframe if driven by an auxiliary power supply. They are connected directly to the appropriate Channel 1 port or Channel 2 port on the 584 mainframe, via a W600 cable to each port. The power to drive Channels 1 and 2 is provided by the 584 mainframe. Addressing of these two channels is fixed by connection the Channel 1 or Channel 2 ports on the 584 mainframe. Typical
Channels
1 and 2 Local I/O connections
Channel
L of the cables to are shown in Figure 5-14.
1 fi y
W600 Cable 6 Ft. Max.
x
\
Figure 5-14
5-13
P421 Cable 75 Ft. Max.
Channels 1,2 Local Configuration
Page 14
Channels 1 and 2 - Remote l/O In addition to serving as local l/O, Channels 1 and 2 can also be used as remote l/O. This allows the 584 mainframe to be located up to 5000 feet (1515 metres) away from the Channels 1 and 2 l/O housings. Each channel requires an 1425 or 1427 Remote l/O Driver unit, and each housing requires a P421 or P431 Auxiliary Power Supply unit. The 1425 or 1427 can each drive a maximum of one channel. Typical Channels 1 and 2 Remote l/O connections are shown in Figure 5-15.
v v lew)
=‘==s=
-e-L= ----
_\AIRl-lA
Il+CiFG!e
I
12 Ft. Max.
b
-W604 r
I
Belden #I8227 Cable or eauivalent 5000 Ft. Max. (User Suppiied)
To Housing 1 Tvniral
A x 1425 Cable 12 Ft. Max. L Belden #8227 Cable or equivalenl 2000 Ft. Max. (User Supplied)
Figure 5-15
Channels 1,2 Remote Configuration
5-14
Page 15
5.9
CHANNELS 3,4 CONFIGURATION Channels 3 and 4 are always used as Local l/O and are connected to one common port on the 584 mainframe. Power to these channels must be supplied by auxiliary power supplies. Two kinds of auxiliary power supplies are used with Channels 3 and 4. The P452 is capable of driving power to one channel of l/O, and also is used to decode and split data to Channel 3 and 4 when both channels are present. The P421 also is capable of driving power to one channel of l/O, but cannot split the data to another channel. The P421 is used for Channel 3 when Channel 4 is not connected, or for Channel 4 when the P452 is used on Channel 3. Typical Channels 3 and 4 connections are shown in Figure 5-16.
Channel 3
[I ----- ti Channel 4
-e--m
=====
MainFrame (Side View)
\ n
/
P452xable 75 Ft. Max.
‘ \ n
P421 Cable ‘ 75 Ft. Max.
Figure 5 16
5-l 5
Channels
3,4 Configuration
/
Page 16
5.10
CHANNELS 5 THROUGH 32 CONFIGURATION In addition to the four channels of l/O previously described, up to 28 additional remote channels of l/O (Channels 5 through 32) can be connected to a common coaxial cable. This cable connects to a J200 Remote l/O Driver which in turn is connected to a Remote l/O port on the 584 mainframe. The total length of the coaxial cable can be up to 15,000 feet (4545 metres). Along this length of cable can be placed up to 14 cable taps, each connected to a P451 Auxiliary Power Supply. The P451 drives power to one l/O channel, and splits the data further to a second l/O channel receiving power from a P421 Auxiliary Power Supply. A P453 Remote l/O Interface unit is used for channels which connect to an ASCII device, such as a printer or badge reader. The P453 can drive power to two channels of l/O. A typical configuration of Remote l/O for Channels 5 and up is shown in Figure 5-I 7.
CHANNEL 8
CHANNEL 7 Controller
J200 I?
Mainframe (Side View)
To Other Channels I c;nanners
L P421 Cable 75 Ft. Max.
Figure 5-l 7
Channels 5 and Up Configuration
5-16
Page 17
5.11
J200 REMOTE l/O DRIVER Channel 5 through 32 data is conducted through a single connector on the 584 mainframe. Attached to this connector is a J200 Remote I/O Driver, which receives its operating power from the mainframe. The J200 transfers data between the mainframe and Channels 5 through 32 through a coaxial cable using Type “F” connectors, connected to the bottom panel of the J200 unit. A defective J200 is replaced as a unit. A replacement later in this section. A typical view of the J200 Remote
Figure 5-18
5-17 procedure l/O Driver unit is shown
J200 Remote l/O Driver is provided in Figure 5-18.
Page 18
The J200 has four front panel indicator lights (Figure 5-19). Their purposes are: COMM ERROR - Blinks if a communication error exists between the J200 and a Remote l/O Channel. RCVR ACTIVE -
Blinks when receiving data.
XMTR ACTIVE -
Blinks when transmitting data.
POWER OK mainframe.
Remains lit when operating power is being received from the
COMM
4 ERROR RCVR 4 ACTIVE XMTR -1 ACTIVE POWER
-t0,
Figure 5-19
J200 indicator Lights
A communication error between the J200 and a Remote l/O Channel connected to the J200 could be caused by a faulty coaxial cable or cable connection at any point along the cable length. Bad connections (crimped or cold solder points) along the cable should be suspected when troubleshooting in the area of the Remote l/O Channels.