Page 19
J200 Cablinn Remote l/O connections to the J200 use types CATV or CAC6 coaxial cable with associated coaxial Splitter, Tap, and Terminator devices. A Splitter is used at the J200 to split the cable layout into two directions. Taps are placed at points along the cable at which l/O channel connections are made to a P451 or P453. A Terminator connects to a cable end which is not terminated at a P451 or P453. No cable ends should be left “floating” without a termination. Typical part numbers for Connectors,
Taps and Terminators are as follows:
CATV Cable l l
Comm-Scope Co. Parameter III Model
No. P-3-75-500-JCA
Times Co. Lumifoam III Model
No. JT-4500
CAC-6 Cable l
Belden Model No. 9283
CATV Cable to Male “F” l
Male Connector
Taco-Jerrold Model No. F56
Coax Cable Splitter l with “F”
Connectors
Modicon Model No. MA-0185-000
Cable Terminator l
Connectors
Modicon Model No. MA-0186-000
Coax Cable Tap with “F” l
Adapter
Gilbert Engineering Model No. GRS-500-AFM-DUO3
Type “F” l
Connector
- 75 Ohm
Taco-Jerrold Model No. TR-75F
The user should ensure that ground currents are not conducted along the system’s cable run. The cable shield receives its ground connection at the J200. No grounds should be made at the cable splitter, taps, terminators, or other similar points.
5-19
Page 20
110channels can be located at up to 15,000 feet (4545 metres) of total cable length from the J200, provided there is not more than 35 db signal loss in the line between the J200 and each P451 or P453. Signal loss is caused by the splitter, each tap, and within the coaxial cable. Figure 5-20 shows a typical cable configuration and signal losses.
TAP 1 dB
TAP 1 dB -
75 OHMS CABLE TERMINATOR
EVEN CHANNEL
CRT
I
-
MAXIMUM dB LOSS AT ANY P451 IS 35 dB. MAXIMUM CABLE IS 15,000 EACH WAY. CATV CABLE LOSS IS .8 dB/lOOO FEET. CAC-6 CABLE LOSS IS 7 dB/lOOO FEET.
Figure 5-20
5-20
J200 Cabling
Page 21
Cable Configurations
Not Allowed
The Remote l/O cabling configurations shown in this manual are straight line linear configurations, either center fed or end fed at the J200. Because of the signal propagation and reflection complications of “star” configurations, these configurations must be avoided. Figure 5-21 shows some configurations to avoid:
- k 8
STAR
584
UJ ki 8
TREE OR BRANCHING
584
I r
I
- r
I
I
, c-
E
584
RING
I
I
I
I
Figure 5-21
5-21
I
Configurations
Not Allowed
I
’ I
Page 22
To replace a J200, perform the following steps: 1.
Remove AC power to the 584 mainframe.
2.
Disconnect the J200 cable at its connector on the 584 mainframe.
3.
Disconnect the coaxial cable from the bottom front connector on the J200.
4.
Remove the J200 mounting hardware.
5.
Install the replacement J200 using the mounting hardware. Connect the coaxial cable to the J200 and connect the J200 cable to its 584 mainframe connector.
6.
Restore power to the 584 mainframe.
7.
Check for proper communication to the I/O channels, shown by the absence of a COMM ERROR indication on the J200.
5-22
Page 23
5.12
P452 AUXILIARY POWER SUPPLY The P452 Auxiliary Power Supply is required for Channel 3, if both Channels 3 and 4 are used. The P452 drives power to Channel 3 I/O, decodes Channel 3 data, and decodes the data for Channel 4. On the bottom panel of the P452 unit are two connectors. The front connector, with cable attached, connects directly to the Channel 3,4 port on the 584 mainframe. The rear connector connects to a P421 Auxiliary Power Supply when Channel 4 is used. The P452 can be located up to 75 feet from the 584 mainframe. Indicator lights on the front panel show presence of AC power input and DC voltage output. A front panel circuit breaker opens if a power overload occurs, and can be manually reset. A front view of the unit, power specifications, and AC power connections are shown in the following illustrations. When troubleshooting the 584 system and it is determined that the P452 is defective, the P452 is replaced as a unit.
Figure 5-22
5-23
P452 Auxiliary
Power Supply
Page 24
Normal Voltage: Standard: Optional: (Jumper Selectable) Transient Voltage: Max. 10 Seconds:
Max. 17 mseconds:
115VRMS ~15%(100-130VRMS) 220V RMS 2 15% (187-253V RMS)
115V RMS -t30?‘0 (80-15OV RMS) 220V RMS + 30’%;‘155-285V RMS) 115V RMS * 100% (0-230V RMS) 220V RMS t- 100°:r(O-440V RMS) 1OOOVMax. (500 micro. sec. duration, 0.5% Max. duty cycle.)
Line Spike: Frequency: Standard: Optional: Normal Load:
60 Hz _f5 Percent (57-63 Hz) 50 Hz -t 5 Percent (47.5-52.5 Hz) 10 Volt-amps (min.) 100 Volt-amps (max.) 4 amp peak on Transient (2 amps at 220 Vat.)
Figure 5-23
P452 Power Specifications
230 VAC OPERATION ONLY 4l lo 1
HOT
GND
NEUT.
1
\I15
Figure 5-24
I
I
VAC OPERATION ONLY
P452 AC Power Connections
To replace a P452 unit, perform the following steps: 1.
Remove AC power from both the 584 mainframe and the P452 unit.
2.
Remove cables from the P452 and cam the l/O housing away from the unit. Remove the P452.
3.
Loosely mount the new P452 in place, and cam the l/O housing carefully. Then tighten the mounting hardware and reconnect cables to the unit.
4.
Restore AC power to the P452 and 584 and check for proper communication to the l/O channel.
5-24
Page 25
5.13
P421 AUXILIARY
POWER SUPPLY The P421 Auxiliary Power Supply is used to drive power for up to one full channel of l/O. The P421 does not have the switching capabilities to decode data for any other channel of l/O. The P421 can be connected directly to the 584 mainframe for I/O Channel 3 when Channel 4 is not used, or connected for Channel 4 to the P452. For remote l/O the unit can be used for any even numbered channel when connected to a P451, which handles the previous odd numbered channel. On the bottom of the P421 is a cable and connector attached for direct connection to the 584 mainframe, P451 or P452. The P421 can be located up to 75 feet from the mainframe, P451, or P452. Indicator lights on the front panel show presence of AC power input and DC voltage output. A front panel circuit breaker opens if a power overload occurs, and can be manually reset. A front view of the unit, power specifications, and AC power connections are shown in the following illustrations. When troubleshooting the 584 system and it is determined defective, the P421 is replaced as a unit.
Figure 5-25
5-25
P421 Auxiliary
Power Supply that the P421 is
Page 26
Normal Voltage: Standard: Optional: (Jumper Selectable) Transient Voltage: Max. 10 Seconds:
Max. 17 mseconds:
115VRMS ~15%(100-130VRMS) 220V RMS it_15% (167-253V RMS)
115V RMS r+_ 30% (80-l 50V RMS) 220V RMS f 30°%;ri 55-265V RMS) 115V RMS -C100% (0-230V RMS) 220V RMS 2 1OO”:;O-440V RMS) 1OOOVMax. (500 micro. sec. duration, 0.5% Max. duty cycle.)
Line Spike: Frequency: Standard: Optional: Normal Load:
60 Hz + 5 Percent (57-63 Hz) 50 Hz f 5 Percent (47.5-52.5 Hz) 10 Volt-amps (min.) 100 Volt-amps (max.) 4 amp peak on Transient (2 amps at 220 Vat.)
Figure 5-26
P421 Power Specifications
230 VAC OPERATION
ONLY /
HOT
GND
NEUT.
OPERATION ONLY
Figure 5-27
P421 AC Power Connections
To replace a P421 unit, perform the following steps: 1.
Remove AC power from P421 unit. If the unit connects to the 584, remove 584 power also.
2.
Remove cables from the P421 and cam the l/O housing away from the unit. Remove the P421.
3.
Loosely mount the new P421 in place, and cam the I/O housing carefully. Then tighten the mounting hardware and reconnect cables to the unit.
4.
Restore AC power to the P421 and 584 and check for proper communication to the l/O channel.
5-26
Page 27
5.14
P451 AUXILIARY
POWER SUPPLY The P451 Auxiliary Power Supply is used to drive power for up to one full channel of l/O. The P451 is addressed by internal switches to decode data for its own l/O channel, and also for one additional channel. Power for this additional channel of l/O is driven by a P421 connected to the P451. The P451 is connected to the P421 by a connector located on its bottom panel, which also contains a coaxial connector for cable to the J200. The P451 can be located up to 15,000 feet (4545 metres) away from the J200. Indicator lights on the front panel show presence of AC power input and DC voltage output. A front panel circuit breaker opens if a power overload occurs, and can be manually reset. Additional indicators show the status of communications to the J200 and the attached l/O channels. Front views of the unit, l/O channel address switches, power specifications, and AC power connections are shown in the following illustrations. When troubleshooting the 584 system and it is determined defective, the P451 is replaced as a unit.
Figure 5-28
5-27
P451 Auxiliary
Power Supply that the P451 is