Manual · Modicon
Section 5: 584 System I/O Configurations
Manual51 pagesPDF 1.7 MB
Manual section on 584 programmable controller I/O configurations: 200 and 500 Series I/O modules, housings, channels and power supplies.
What this file really is
The old site listed this file as a manual for the AEG B573, Gould B573 and 2 more models. The file is named as a B573 user manual, but it is Section 5 (System I/O Configurations) of a 584 Programmable Controller manual and does not mention the B573.
Filed with · 4 models
Also filed with these models on the old site
Summary
What is in it
Section 5 of a manual for the 584 Programmable Controller, describing how its input/output section is configured and maintained. It covers 200 and 500 Series I/O modules with their color codes and fuses, the B240, B241, B242, B545 and B546 housings, the J540 adapter and its switch settings, local and remote I/O channel configurations, the J200 remote I/O driver, the P452, P421 and P451 auxiliary power supplies, ASCII devices and the telephone interface.
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is Section 5 of a manual for the Modicon 584 programmable controller, on configuring and maintaining the 584 system's I/O: 200 and 500 Series I/O modules, housings, local and remote I/O channels, auxiliary power supplies and ASCII devices. The site files it under the B573, which the document does not name. It explains addressing, cabling, power loading and the replacement of units such as the J200, J540 and P453.
- I/O capacity
- 584 system: up to 4096 input and 4096 output points p. 1
- I/O channels
- Up to 32 channels, each with up to 128 discrete inputs and 128 discrete outputs p. 12
- Module series
- 200 Series: 16 points per module, echo check; 500 Series: 4 points per module, parity checking only p. 1
- Remote I/O reach
- Channels 5 to 32: up to 15,000 feet (4545 metres) through a J200 Remote I/O Driver; channels 1 and 2: up to 5000 feet (1515 metres) with a 1425 or 1427 driver p. 12
- Local I/O
- Channels 1 to 4, typically six feet or less from the mainframe; channels 1 and 2 up to 75 feet with an auxiliary power supply p. 12, 13
- Remote I/O cable
- CATV or CAC6 coaxial cable with Type F connectors; at most 35 db loss from the J200 to each P451 or P453 p. 17, 19, 20
- Coax parts
- Modicon MA-0185-000 coax cable splitter; Modicon MA-0186-000 cable terminator p. 19
- Isolation
- Individual 1500 Volt opto-isolation on 200 and 500 Series modules p. 1
- Field wiring
- Clamp terminals for one #12 or two #14 wires p. 1
- 200 Series housings
- B240 standard housing holds four modules; B241 half housing holds two p. 4, 5
- 500 Series housings
- B545 holds up to eight modules, B546 up to four; a J540 Adapter is needed on each channel p. 7, 10
- 500 Series fuses
- Type 3AG, normal blow: 5 ampere in AC output modules, 3 ampere in DC modules p. 6
- P453 models
- AS-P453-511 (50 Hz) / -611 (60 Hz): two remote I/O channels; -521 / -621: two RS-232-C ports; -531 / -631: both; -541 / -641: four RS-232-C ports p. 31
- P453 AC power
- 120 V RMS standard, 220 V RMS optional (jumper selectable); 520 to 1050 volt-amps p. 32
What this manual walks you through
- Addressing 200 Series housings with index pins p. 4, 5
- Setting the address switches on B545 and B546 housings p. 7, 8
- Setting the J540 input and output switches p. 10, 11
- Connecting channels 1 and 2 as local or remote I/O p. 13, 14
- Powering channels 3 and 4 with P452 and P421 supplies p. 15
- Laying out the coaxial cable for remote channels 5 to 32 p. 16, 19, 20, 21
- Replacing a J200 Remote I/O Driver p. 22
- Replacing a P453 board or the whole unit p. 37, 38
- Checking I/O power supply loading p. 38
- Troubleshooting the J478 modem by its indicators p. 50, 51
Good to know
- Star, tree and ring layouts of the remote I/O cable must be avoided; the layouts shown are straight lines fed at the J200. p. 21
- The cable shield is grounded at the J200 only, never at the splitter, taps or terminators. p. 19
- 200 Series modules turn all outputs off if the CPU does not refresh their data every 250 milliseconds. p. 1
- The total units of load on a channel must not exceed what its power supply can deliver. p. 38
- A modem cannot simply be plugged into a P453; it needs the RS-232-C wiring shown to the J478. p. 49
Questions this manual answers
How far can remote I/O be from a Modicon 584?
Channels 5 to 32 can be up to 15,000 feet (4545 metres) away through a J200 Remote I/O Driver; channels 1 and 2 up to 5000 feet with a 1425 or 1427 driver. p. 12
How many I/O points does a 584 support?
Up to 4096 input and 4096 output points. p. 1
What is the J540 adapter for?
It connects 500 Series I/O housings and modules to the 584; one J540 is attached to each channel. p. 10
What cable does the J200 remote I/O use?
CATV or CAC6 coaxial cable, with splitters, taps and terminators. p. 19
What fuses do 500 Series I/O modules use?
Type 3AG normal blow fuses: 5 ampere in AC output modules and 3 ampere in DC modules. p. 6