The text of a manual · part 14 of 28

User Manual EASY412, EASY600 Control Relay: 5 Drawing a Circuit Diagram with “easy”, pages 112 to 121

Pages 112 to 121 of 228, from User Manual EASY412, EASY600 Control Relay

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Moeller 621-DC-TCX

Page 112

Example circuits Negation Negation means that the contact opens, rather than closes, when it is actuated (NOT circuit). In the “easy” circuit diagram, press the ALT button to toggle contact I1 between break and make contact.

i1-------ÄQ1

Logic table: I1

Q1

1 0

0 1

Permanent contact To energize a relay coil continuously, make a connection of all contact fields from the coil to the leftmost position.

---------ÄQ1

Logic table: ---

Q1

1

1

Series connection Q1 is controlled by a series circuit consisting of three make contacts (AND circuit).

08/00 AWB2528-1304-GB

Q2 is controlled by a series circuit consisting of three break contacts (NOR circuit).

I1-I2-I3-ÄQ1 i1-i2-i3-ÄQ2

In the “easy” circuit diagram, you can connect up to three make or break contacts in series within a circuit connection. Use “M” marker relays if you need to connect more than three make contacts in series.

109

Page 113

Drawing a Circuit Diagram with “easy” Logic table: I1

I2

I3

Q1

Q2

0 1 0 1

0 0 1 1

0 0 0 0

0 0 0 0

1 0 0 0

0 1 0 1

0 0 1 1

1 1 1 1

0 0 0 1

0 0 0 0

Parallel connection Q1 is controlled by a parallel circuit consisting of three make contacts (OR circuit). A parallel circuit of break contacts controls Q2 (NAND circuit).

I1u------ÄQ1 I2s I3k i1u------ÄQ2 i2s

I1

I2

I3

Q1

Q2

0 1 0 1

0 0 1 1

0 0 0 0

0 1 1 1

1 1 1 1

0 1 0 1

0 0 1 1

1 1 1 1

1 1 1 1

1 1 1 0

Changeover circuit A changeover circuit is made in “easy” using two series connections that are combined to form a parallel connection (XOR).

i3k

I1-i2u---ÄQ1 i1-I2k

XOR means that this circuit is an “Exclusive OR circuit”. Only if one contact switches, can the coil be energized. 110

08/00 AWB2528-1304-GB

Logic table:

Page 114

Example circuits Logic table: I1

I2

Q1

0 1 0 1

0 0 1 1

0 1 1 0

Latching circuit A combination of a series and parallel connection is used to wire a latching circuit. Latching is established by contact Q1 which is parallel to I1. If I1 is actuated and reopened, the current flows via contact Q1 until I2 is actuated.

S1 make contact on I1 S2 break contact on I2 I1uI2----ÄQ1 Q1k

Logic table: I1

I2

Contact Q1 Coil Q1

0 1 0 1

0 0 1 1

0 0 0 0

0 0 0 1

1 0 1

0 1 1

1 1 1

0 1 1

08/00 AWB2528-1304-GB

Latching circuits are used to switch machines on and off. The machine is switched on at the input terminals via make contact S1 and is switched off via break contact S2.

111

Page 115

Drawing a Circuit Diagram with “easy” S2 opens the connection to the control voltage in order to switch off the machine. This ensures that the machine can be switched off, even in the event of a wire break. I2 is always closed when not actuated. A self-latching circuit with wire break monitoring can alternatively be wired using the Set and Reset coil functions.

S1 make contact on I1 S2 break contact on I2 I1-------SQ1 i2-------RQ1

Relay Q1 is latched when I1 is switched on. I2 inverts the break contact signal from S2 and does not switch until S2 is actuated. In this way, the machine is switched off if or when a wire breaks. Make sure that both coils are wired up in the correct order in the “easy” circuit diagram: first wire the “S” coil and then the “R” coil. This means that the machine will be switched off when I2 is actuated, even if I1 is switched on. Impulse relay An impulse relay is often used for controlling lighting such as for staircase lighting.

S1 make contact on I1 I1-------äQ1

112

I1

State Q1

Q1

0 1 0 1

0 0 1 1

0 1 1 0

08/00 AWB2528-1304-GB

Logic table:

Page 116

Example circuits On-delayed timing relay The on-delay can be used to gate short pulses or to initiate another movement with a time delay when a machine is started. The parameter settings for T1 are: Timing function on-delayed: “ X” Time value and range: 10 seconds

S1 make contact on I1 I1-------TT1 T1-------ÄM1

X w g

Ä sTRG dT1

S n10.00n yRES b +

If I1 is switched on, coil T of T1 is energized. After 10 seconds, T1 switches the marker relay M1. If I1 is switched off, relay coils T1 and M1 drop out. Logic table: I1

T1

M1

0 1 1

0 0 1

0 0 1

Star-delta starting

08/00 AWB2528-1304-GB

You can implement two star-delta circuits with “easy”. The advantage of “easy” is that you can select any changeover time between star and delta contactors and any wait time between switching off the star contactor and switching on the delta contactor.

113

Page 117

Drawing a Circuit Diagram with “easy” L S1 S2

K1M

K3M

K1M

K1T

K1M

K1T

K5M

K3M

K3M

K5M

N

L N S1

K1M

S2

I1

L N

Q2

Q1 1 K1M

2 K3M

1

2 K5M

114

08/00 AWB2528-1304-GB

N

Page 118

Example circuits Function of the “easy” circuit diagram: Start/Stop of switching using external push-button actuators S1 and S2. The mains contactor starts the “easy” timing relay. I1 Q1 Q2 T1 T2

I1u------TT1 dt1----ÄQ1 dT1----TT2 hT2----ÄQ2 Mains contactor switched on Star contactor ON Delta contactor ON Star-delta changeover time (10 to 30 s, X) Wait time between star off, delta on (30, 40, 50, 60 ms, X)

If your “easy” has an integral time switch, you can combine star-delta starting with the time switch function. In this case, use “easy” to switch the mains contactor as well.

4x shift register You can use a shift register for storing an item of information, such as the sorting of parts into good and bad two, three or four transport steps further on. A shift pulse and the value (0 or 1) to be shifted are needed for the shift register. The shift register's Reset input is used to clear any values that are no longer needed. The values in the shift register pass through the register in the following order. 08/00 AWB2528-1304-GB

1st, 2nd, 3rd, 4th storage position.

115

Page 119

Drawing a Circuit Diagram with “easy” Block diagram of the 4x shift register: PULSE VALUE RESET

1 2 3 4 Storage positions

Function: Pulse

Value Storage location 1

2

3

4

1

1

1

0

0

0

2

0

0

1

0

0

3

0

0

0

1

0

4

1

1

0

0

1

5

0

0

1

0

0

0

0

0

0

Reset = 1

I1 I2

M1 M2 M3 M4

Shift pulse (PULSE) Information (good/bad) to be shifted (VALUE) Clear content of the shift register (RESET) 1st storage position 2nd storage position 3rd storage position 4th storage position

M7 M8

Marker relay for cyclical pulse Cyclical pulse for shift pulse

I3

116

08/00 AWB2528-1304-GB

Assign the contents “bad” to the value 0. This ensures that no bad parts will be reused if the shift register is accidentally deleted.

Page 120

Example circuits

I1um7----ÄM8 h------ÄM7

M8uM3----SM4 dm3----RM4 dM2----SM3 dm2----RM3 dM1----SM2 dm1----RM2 dI2----SM1 hi2----RM1

I3------uRM1 dRM2

Generate shift pulse Set 4th storage position Clear 4th storage position Set 3rd storage position Clear 3rd storage position Set 2nd storage position Clear 2nd storage position Set 1st storage position Clear 1st storage position Clear all storage positions dRM3 hRM4

How does the shift register work? The shift pulse is switched on for exactly one cycle. To do this, the shift pulse is generated by evaluating the change from I1 “off” to I1 “on” – the rising edge. In this way, therefore, the cyclical processing of “easy” is used to trigger the shift pulse.

08/00 AWB2528-1304-GB

When I1 is switched on for the first time, marker relay contact M7 is switched off and the break contact is closed during the first pass through the cycle. Thus, the series circuit consisting of I1, break contact M7 (closed) and M8 is switched on. Although M7 is switched on, this does not yet affect contact M7. The contact of M8 (make contact) was still open during the first cycle so a shift pulse cannot yet be generated. When the relay coil M8 is activated, “easy” transfers the result to the contacts. In the second cycle, break contact M7 opens. The series circuit is now open. The contact M8 is switched on from the result of the first cycle. Now, all 117

Page 121

Drawing a Circuit Diagram with “easy” the storage positions are either set or reset in accordance with the series circuit. If the relay coils were activated, “easy” transfers the result to the contacts. M8 is now open once more. No new pulse can be formed until I1 has opened, since M7 is open for as long as I1 is closed. How does the value reach the shift register? When shift pulse M8 = “on”, the state of I2 (value) is transferred to storage position M1. If I2 is switched on, M1 is set. If I2 is switched off, M1 is switched off via break contact I2. How is the result shifted? “easy” activates the coils in accordance with the circuit connection and its result, from top to bottom. M4 assumes the value of M3 (value 0 or 1) before M3 assumes the value of M2. M3 assumes the value of M2, M2 the value of M1 and M1 the value of I2. Why are the values not constantly overwritten? In this example, the coils are controlled only by the “S” and “R” functions, i.e. the values are retained in on or off states even though the coil is not constantly switched on. The state of the coil changes only if the circuit connection up to the coil is switched on. In this circuit, the marker relay is therefore either set or reset.

How are all the storage positions cleared? When I3 is switched on, all the “R” coils of storage positions M1 to M4 are reset, i.e. the coils are switched off. Since the reset was entered at the end of the circuit diagram, the reset function has priority over the set function.

118

08/00 AWB2528-1304-GB

The circuit connections of the coils (storage positions) are only switched on via M8 for one cycle. The result of activating the coils is stored in “easy” until a new pulse changes the state of the coils.