User Manual EASY412, EASY600 Control Relay: 5 Drawing a Circuit Diagram with “easy”, pages 102 to 111

Pages 102 to 111 of 228, from User Manual EASY412, EASY600 Control Relay

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Moeller 621-DC-TCX

Page 102

Analog comparators I7 I8, I7 I8 I7 setpoint, I7 setpoint I8 setpoint, I8 setpoint Both the setpoint value and the actual value correspond to the measured voltages. Resolution of the voltage values: 0.0 to 10.0 V in 0.1 V steps From 10 V to 24 V the actual value stays at 10.0. You can enter the setpoint values for a comparison while you are creating the circuit diagram or in the parameter display in Run mode. Typical applications Evaluating the analog values of sensors, e.g. in order measure the pressure or temperature. Two-step controllers Example: I1uA1----SQ1 Analog comparator A1 latches hA2----RQ1 (sets) relay Q1 if the actual value drops below the lower setpoint value of 7.1 V. Comparator A2 unlatches (resets) the relay if it rises above the upper setpoint value of 7.5 V. Thus the difference (switching hysteresis) between the two voltage setpoint values is 0.4 V. The parameter settings are: ANALOG g

I7 w

7.1y b +

7.5y n §

08/00 AWB2528-1304-GB

ANALOG

I7 w dA1 n $ g dA2 b +

99

Page 103

Drawing a Circuit Diagram with “easy” Signal diagram: [V] 10 7,5 7,1 5

A

BC

D I7

A1

A2

A1 on

A1 sets relay output Q1 (A) up to a voltage of 7.1 V. The hysteresis (B) is between 7.1 V and 7.5 V. At 7.5 V, A2 causes the relay to reset (C). Q1 drops out and does not pick up again until A1 is set at 7.1 V (D). Analog signals of sensors typically fluctuate by several millivolts. For stable set and reset switching the setpoints should differ by at least 0.2 V (switching hysteresis).

100

08/00 AWB2528-1304-GB

Caution To prevent the uncontrolled switching of the relay coils only use the Set and Reset functions with the analog comparators.

Page 104

Analog comparators Wiring analog comparators You integrate an analog comparator into your circuit in the form of a contact. Use the parameter display to select one of six possible comparators and enter the setpoint values. 왘 Enter the relay contact for the Task: Output Q3 should analog comparator in the switch on at a certain contact field. value. The cursor is then located on the Circuit diagram: contact number of the comparator. A1-------SQ3 왘 Press OK to switch to the parameter display. The parameter set for the first comparator is displayed. 왘 Use ú í to move the cursor to the field . Use ÍÚ to select one of the comparator relays.

I7 I8

I7 setpoint

ANALOG

ANALOG

ANALOG

I7 w g

I7 w g

I7 w g

I8 y b +

0.0y b +

0.0y b + n $ dA1

I7 I8 n $ dA1

I8 setpoint

ANALOG n § dA1

I8 setpoint

ANALOG

ANALOG

I7 w g

I8 w g

I8 w g

I8 y b +

0.0y b +

0.0y b + n §

08/00 AWB2528-1304-GB

I7 setpoint dA1 n $ dA1 n § dA1

왘 Press OK to finish or enter another setpoint value. Press ESC to return to the circuit diagram display. 101

Page 105

Drawing a Circuit Diagram with “easy” Parameter sets for analog comparators The parameter display for analog comparators can be used to set the comparison “” or and to enable or disable the parameter access. ANALOG

Input I7 Compare fctn. Input I8

I7 w8.0 Vg n

§ dA1

I8 y4.2 Vb +

Actual value Relay no. Parameter display Curr. value

If you want to compare an input with a setpoint value, you must also set the setpoint value. ANALOG

Input I7/I8 Compare fctn. Setpoint

I7 w8.0 Vg n

3.2y

$ dA1 b +

Actual value Relay no. Parameter display

The actual values are only displayed in Run mode. Call up the parameter display in Run mode via the power flow display or via PARAMETER in the main menu. You cannot set parameters when comparing two values. Parameters

Function

Meaning

Compare fctn.

$

Greater than or equal to

§

Less than or equal to

0.0

Setpoint value, 0.0 to 9.9, 10.0 = overflow

Parameter set displayed via the PARAMETER menu option +

102

Access enabled

- Access disabled

08/00 AWB2528-1304-GB

Setpoint

Page 106

Text display Text display

EASY600 allows you to display eight user-defined texts which can be edited in EASY-SOFT from V. 2.0 upwards. The texts are saved in the EASY-SOFT file *.eas or on the “easy-M-16K” memory card for EASY600. Example THINK

FUTURE

SWITCH TO GREEN

Circuit diagram symbols for text display Contacts

Make contact

D

Break contact

ì

Numbers

1 to 8

Coils

D

Numbers

1 to 8

Coil functions

Ä,S,R,ä

08/00 AWB2528-1304-GB

LCD display Up to 12 characters per line and up to 4 lines can be displayed. Variables Actual values and setpoints of timing relays and counters, scaled actual values from analog input I7 or I8, as well as the current time are displayed automatically in lines 2 or 3, characters 5 to 8 (characters 5 to 9 for time display, see 13:51 in example below). If you have entered text at these locations, they will be overwritten by the variable values. Enter a blank space as the placeholder (at 13:51 in the example), in order to continue text after the variable display. Example: TIME13:51 103

Page 107

Drawing a Circuit Diagram with “easy” Scaling The value ranges of the analog inputs I7, I8 (0 to 10 V) can be displayed in the following way. Analog value, range

Selectable display range

Example

0 to 10 V

0 to 9999

0000 to 0100

0 to 10 V

- 999

–025 to 050

0 to 10 V

- 9.9

–5.0 to 5.0

Function The marker relays D = Display function in the circuit diagram as normal M markers. All eight markers can be used retentively. If a text is assigned to a marker, it will be displayed in the “easy” LCD if the coil is set to 1. For this to happen “easy” must be in Run mode and the Status display must be showing before the text is activated. The following conditions apply to D2 to D8: When activating several texts, they will be displayed automatically every 4 s in succession. This process will be repeated until

The following applies to D1: D1 is designed as an alarm text. If D1 is activated, the text assigned to it will be displayed until the coil D1 is reset to 0. Stop mode is selected. the “easy” power supply is switched off. 104

08/00 AWB2528-1304-GB none of the display markers are set to 1. Stop mode is selected. the “easy” power supply is switched off. the OK or DEL + ALT buttons are used to switch to a menu. the text for D1 is displayed.

Page 108

Jumps the OK or DEL + ALT buttons are used to switch to a menu. Text entry Text entry is only possible using EASY-SOFT, from version V 2.0 upwards Character set All ASCII characters in upper and lower case are permissible. ABCDEFGHIJKLMNOPQRST UVWXYZ abcdefghijklmnopqrstuvwxyz The following special characters are permissible: ! “” # $ % & ’ ( ) * + , – . / 0 1 2 3 4 5 6 7 8 9 Examples Counter with Analog values scaled as actual value and setpoint temperature values

D1 as error message on fuse failure

QUANTITY

TEMPERATURE

FUSE

SETP0500 PCE

I

HOUSE 1

QTY.0042

!COUNTING!

08/00 AWB2528-1304-GB

Jumps

A

-010DEG. +018DEG.

HEATING

FAULT

FAILED!

Jumps can be used to optimize the structure of a circuit diagram or to implement the function of a selector switch. Jumps can be used for example to select whether manual/automatic operation or other machine programs are to be set. Jumps consist of a jump location and a jump destination (label).

105

Page 109

Drawing a Circuit Diagram with “easy” Circuit diagram symbols for jumps Contact

Make contact

:

(can only be used as first leftmost contact) Numbers

1 to 8

Coils

Ä

Numbers

1 to 8

Coil function

Ä

Function If the jump coil is triggered, the circuit connections coming directly after it will not be processed. The states of the coils before the jump will be retained, unless they are overwritten in circuit connections that were not missed by the jump. Jumps are always made forwards, i.e. the jump ends on the first contact with the same number as that of the coil. Coil = jump when 1 Contact only at the first leftmost contact = Jump destination

106

Backward jumps are not possible with “easy” due to the way it operates. If the jump label does not come after the jump coil, the jump will be made to the end of the circuit diagram. The last circuit connection will also be skipped. If a jump destination is not specified, the jump will be made to the end of the circuit diagram. Multiple use of the same jump coil and jump contact is possible as long as this is implemented in pairs, i.e. Coil Ä:1/jumped range/Contact :1, Coil Ä:1/jumped range/Contact :1 etc.

08/00 AWB2528-1304-GB

The Jump contact point will always be set to 1

Page 110

Jumps Attention The states of jumped circuit connections are retained. The time value of timing relays that have been started will continue to run.

Power flow display Jumped ranges are indicated by the coils in the power flow display. All coils after the jump coil are shown with the symbol of the jump coil. Example A selector switch allows two different sequences to be set. Sequence 1: Switch on Motor 1 immediately. Sequence 2: Switch on Guard 2, Wait time, then switch on Motor 1. Contacts and relays used: I1 I2 I3 I12

08/00 AWB2528-1304-GB

Q1 Q2 T1 D1

Sequence 1 Sequence 2 Guard 2 moved out Motor-protective circuit-breaker switched on Motor 1 Guard 2 Wait time 30.00 s, on-delayed Text “Motor-protective circuit-breaker tripped”

107

Page 111

Drawing a Circuit Diagram with “easy” Circuit diagram:

Power flow display: I1 selected:

I1-------Ä:1

I1-------Ä:1

:1

:1

I2-------Ä:2 --------uÄQ1 hRQ2

I2--------:1 --------uÄQ1 hRQ2

---------Ä:8

---------Ä:8

Q2-I3----TT2

Q2-I3-----:8

:2-------ÄQ2 T2-------ÄQ1 :8 i12------ÄD1

Example circuits

Range from jump label 1 processed.

:2--------:8

Jump to label 8. Range to jump label 8 skipped.

T2--------:8 :8 i12------ÄD1

Jump label 8, circuit diagram processed from this point on.

Basic circuits The “easy” circuit diagram is created using ladder diagrams. This section contains a few circuits intended to demonstrate the possibilities for your own circuit diagrams. The values in the logic table have the following meanings for contacts: 0 = make contact open, break contact closed 1 = make contact closed, break contact open for relay coils Qx:

108

08/00 AWB2528-1304-GB

0 = coil not energized 1 = coil energized