The text of a manual · part 12 of 28
User Manual EASY412, EASY600 Control Relay: 5 Drawing a Circuit Diagram with “easy”, pages 92 to 101
Pages 92 to 101 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 92
Timing relays Timing relays, flashing The relay closes and opens the relay contact alternately at the set flashing frequency. Ü
Flash frequency = -------------1 --------------2 set time
Example Set time: 0.2 s, Flash frequency = -----1----- = 2.5 Hz 0.4 s Signal diagram: on TRG on RES on t t t
The trigger coil switches the flashing on and off. The flashing period starts with switch position “off”. The reset coil has priority over the trigger coil and always resets the relay contact. If the time is set to zero, the flash frequency changes with the cycle time. The cycle time varies according to the length of the circuit diagram.
08/00 AWB2528-1304-GB
Typical applications Activating warning lamps
89
Page 93
Drawing a Circuit Diagram with “easy” Counter relays
“easy” works with counter relays C1 to C8. D
R
C
The counter relay increments or decrements signals and switches when the actual value is greater than or equal to the setpoint value. Values between 0000 and 9999 are possible.
A counter relay can be controlled via the counting pulse CCx, counting direction DCx and reset RCx relay functions. Signal diagram: on CCx on DCx on
A
B
C
D
RCx
8 7 6 5 4 3 2 1 0 on
The relay contact of a counter with setpoint value 6 switches when the actual value is 6 (A). If the counting direction is reversed (B), the contact switches back when the actual value is 5. Without a counting pulse, the current actual value is retained (C). The reset coil resets the counter to 0 (D). Possible applications include the counting of components, lengths or event frequency.
90
08/00 AWB2528-1304-GB
Cx
Page 94
Counter relays Wiring a counter relay You integrate a counter relay into your circuit in the form of a contact and coil. Counter relay C1 receives counting pulses via the count coil CC1. The counting direction can be changed via the direction coil DC1: DC1 = 0: relay C1 counts up DC1 = 1: relay C1 counts down The Reset coil RC1 is used to reset the counter to the actual value 0.
Contact C1 is used to process the result of the counter in the circuit diagram. To prevent unpredictable switching states, use each coil of a relay once only in the circuit diagram. 왘 Enter at least one contact and Task: a coil in your circuit diagram: Switch output Q1 after the 5th part in one A relay contact in the contact direction. I1 counter pulse field, in this case C1 I2 resets actual value A count coil in the coil field, in I3 determines direction this case CC1. You can wire up coils RC1 and DC1 as required.
Circuit diagram: I1-------CC1 I3------ DC1
왘 Select relay contact C1, move I2-------RC1 the cursor to 1 and press OK. C1-------ÄQ1
08/00 AWB2528-1304-GB
The parameter set for counter relay C1 is displayed.
Parameter display: f0005g sDIR n
Ä sCNT d Ä yRES b
C1
+
91
Page 95
Drawing a Circuit Diagram with “easy” Determining counter frequency The maximum counter frequency depends on the length of the circuit diagram in “easy”. The number of contacts, coils and circuit connections used determines the run time (cycle time) required to process the “easy” circuit diagram. Example: When using EASY412-DC-TC with only three circuit connections for counting, resetting and outputting the result via the output, the counter frequency may be 100 Hz. To determine the cycle time refer to chapter 9 on page 175. The maximum counter frequency depends on the maximum cycle time. Use the following formula to determine the maximum counter frequency: 1 0.8 fc = ---------------2 tc fc = maximum counter frequency tc = maximum cycle time 0.8 = correction factor Example The maximum cycle time is tc = 4000 s (4 ms). 1 0.8 = 100 Hz fc = ----------------------2 ms
Setpoint Direction coil Counter coil Reset
92 f0230g0000
Ä sDIR n Ä sCNT d
Ä yRES b
C1 +
Actual value Relay no. Parameter display
08/00 AWB2528-1304-GB
Parameter set for counters The parameter display for counters is used to change the counter setpoint value and to enable or disable parameter access.
Page 96
Time switch Values between 0000 and 9999 are possible. Parameter Coil function
Meaning
DIR
Counting direction
D
DCx=0: count up DCx=1: count down CNT
C
Counting pulse
RES
R
Reset
The contactor symbol “Ä” before DIR, CNT and RES indicates whether the coil function is wired in the circuit diagram. Parameter set displayed via the PARAMETER menu option +
Time switch
08/00 AWB2528-1304-GB
Access enabled
- Access disabled
The actual value is only displayed in Run mode. The parameter display can then be called up via the power flow display or via the PARAMETER option from the main menu. The coil symbol is not displayed if you select the parameter display via the PARAMETER menu option.
Versions of “easy” with the type suffix “-RC(X)” or “TC(X)” are equipped with a real-time clock which can be used in the circuit diagram as a 7-day time switch. The procedure for setting the time is described under chapter 7 on page 143. “easy” has four time switches “Ö1” to “Ö4”, providing a total of 32 switching times.
93
Page 97
Drawing a Circuit Diagram with “easy” Each time switch has four channels which you can use to set four on and off times. The channels are set via the parameter display. The timer has a back-up battery. This means that it will continue to run in the event of a power failure, although the time switch relays will not switch. When the timer is disconnected from the power supply, the contacts remain open. Information on the battery back-up time are provided in chapter 11, page 197. Example 1 Time switch “Ö1” switches on Monday to Friday between 6:30 and 9:00 and between 17:00 and 22:30. fMO-FRg n dÖ1
ON s06:30n A
OFFy09:00b + fMO-FRg n dÖ1
ON s17:00n B
OFFy22:30b +
Signal diagram:
Example 2 Time switch “Ö2” switches at 16:00 on Friday and switches off at 6:00 on Monday. n g dÖ2
ON s16:00n A
OFFy--:--b +
94 fMO n g dÖ2
ON s--:--n B
OFFy06:00b +
08/00 AWB2528-1304-GB fFR
Page 98
Time switch Signal diagram:
Example 3 Time switch “Ö3” switches on overnight at 22:00 on Monday and switches off at 6:00 on Tuesday. fMO n g dÖ3
ON s22:00n D
OFFy06:00b +
Signal diagram:
If the Off time is before the On time, “easy” will switch off on the following day. Example 4 The time settings of a time switch overlap. The clock switches on at 16:00 on Monday, whereas on Tuesday and Wednesday it switches on at 10:00. On Monday to Wednesday the switching-off time is 22:00.
08/00 AWB2528-1304-GB fMO-WEg n dÖ4
ON s16:00n A
OFFy22:00b + fTU-WEg n dÖ4
ON s10:00n B
OFFy00:00b +
95
Page 99
Drawing a Circuit Diagram with “easy” Signal diagram:
Switch-on and switch-off times always follow the channel which switches first. Example 5 The power is removed between 15:00 and 17:00. The relay drops out and remains off, even after the power returns, since the first switching-off time was at 16:00. fMO-SUg n dÖ4
ON s12:00n A
OFFy16:00b + fMO-SUg n dÖ4
ON s12:00n B
OFFy18:00b +
When it is switched on, “easy” always updates the switching state on the basis of all the available switching time settings. Example 6 The time switch is to switch for 24 hours. Switch-on time at 0:00 on Monday and switch-off time at 0:00 on Tuesday. g dÖ1
ON s00:00n A
OFFy--:--b +
96 fDI n g dÖ1
ON s--:--n B
OFFy00:00b +
08/00 AWB2528-1304-GB fMO n
Page 100
Time switch Wiring a time switch A time switch can be integrated into your circuit in the form of a contact. Use the parameter display to set the switching-on and switching-off times. 왘 Enter the relay contact for the Task: Switch output Q3 on at time switch in the contact 6:00 on Monday to field. Friday and switch off at The cursor is over the contact number of the time switch.
22:30. Circuit diagram:
왘 Press OK to set the switching Ö1-------ÄQ3 times. The parameter set for the first channel is displayed. 왘 Set the switching times for the Parameter display: parameter set. fMO-FRg n dÖ1
ON s06:00n A
OFFy22:30b +
08/00 AWB2528-1304-GB
Parameter set for the time switch A time switch has four sets of parameters, one for each channel (A, B, C and D). These are used to set the day of the week and the switching-on and switching-off times for the desired channels and to enable or disable parameter access. Changing the switching times is described under chapter 7 from page 142. You can only change the setting “+”/“–” for displaying the parameters via the PARAMETER menu option when you are editing the circuit
97
Page 101
Drawing a Circuit Diagram with “easy”
Week day(s) from - to Current time On time Off time fMO g n01:00dÖ1
ON s--:--n A OFFy--:--b +
Relay no. Channel Parameter display
The time only appears in the parameter display in Run mode. Call up the parameter display in Run mode via the power flow display or via PARAMETER in the main menu. Switching-on and switching-off times Parameters
Meaning
Valid setpoint times
Weekday
Monday to Sunday
MO, TU, WE, TH, FR, SA,
On time
Hours: Minutes: No time set at “--:--”
00:00 to 23:59, --:--
Off time
Hours: Minutes: No time set at “--:--”
00:00 to 23:59, --:--
Parameter set displayed via the PARAMETER menu option +
Analog comparators
Access enabled
- Access disabled
Analog comparators are only available with 24 V “easy”-DC models. They monitor the voltages of sensors that are connected to terminals I7 and I8.
A comparator can perform six different types of comparison. The relay contact switches if the comparison conditions are fulfilled.
98
08/00 AWB2528-1304-GB
“easy” provides eight analog comparators “A1” to “A8” for use as required.