User Manual EASY412, EASY600 Control Relay: 5 Drawing a Circuit Diagram with “easy”, pages 82 to 91
Pages 82 to 91 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 82
Function relay L01+ L01–
“easy” wiring and circuit diagram
S1
S2
I5-------CC1 I6-------RC1 C1-------TT1
+24 V 0 V
T1-------ÄQ1
1
I5 I6 2
Q1 H1 L01–
You can use the circuit diagram form at the back of this manual for planning and preparing your “easy” circuit diagrams.
08/00 AWB2528-1304-GB
On the next two pages you will learn how to enter the example on the form.
79
Page 83
Drawing a Circuit Diagram with “easy”
“easy” Control Relay Circuit Diagram Customer: D^ZeY Date:
Program:
HRc_Z_X ]ZXYe
Page:
"
FO 98
80
: &
4 4 "
4`f_eVc GR]fV
: '
C 4 "
CVdVe 4`f_eVc
4 "
E E "
EcZXXVc 7]RdY S]Z_\ cV]Rj
E "
Ä B "
HRc_Z_X # d
08/00 AWB2528-1304-GB
(03/98) FO 98 DM. Printed in the Federal Republic of Germany (08/98)
Comment:
Page 84
Function relay
“easy” Control Relay Circuit Diagram Customer: D^ZeY Date:
FO 98
Program:
HRc_Z_X ]ZXYe
Page:
#
Timing relays Ü D +
# + ! !
Ä
+ T "
TRG
+ TRG
RES
+ T
+ TRG
RES
T
RES
Analog comparators ANALOG
ANALOG
A
ANALOG
A
A
(03/98) FO 98 DM. Printed in the Federal Republic of Germany (08/98)
08/00 AWB2528-1304-GB
Timing switches
Ÿ
Ÿ
Ÿ
ON
+
ON
+
ON
+
OFF
+
OFF
+
OFF
+
Up/down counters ! !
" !
DIR
Ä Ä
CNT RES
DIR C "
CNT RES
DIR C
CNT
C
RES
81
Page 85
Page 86
Function relay Each parameter set can be displayed using the power flow display for the circuit diagram. 왘 Move the cursor onto C1 and press OK. The parameter set for the counter is displayed with actual and setpoint values. 왘 Switch I5. The actual value changes. The coil terminal CNT is activated for as long as you press push-button actuator S1. This is represented in the “easy” parameter display.
f0010g0000 sDIR n
Ä sCNT d
C1
Ä yRES b
+ f0010g0002 sDIR n
Ä sCNT d
C1
Ä yRES b
+
If the actual and setpoint values are the same, the timing relay switches the warning light on and off every 2 seconds. Doubling the flashing frequency: 왘 Select T1 in the power flow display and change the setpoint time to 01.00. When you press OK, the warning light will flash at twice the frequency.
08/00 AWB2528-1304-GB
Ü w01.23g
Ä sTRG
S n01.00n yRES dT1 b +
You can also modify parameter settings via the PARAMETER menu option. If you want to prevent other people from modifying the parameters, change the access enable symbol from “+” to “–” when creating the circuit diagram and setting parameters and protect the circuit diagram with a password.
83
Page 87
Drawing a Circuit Diagram with “easy” Timing relays
“easy” provides eight different timing relays T1 to T8 for use as required. A timing relay is used to change the switching duration and the make and break times of a relay contact. The possible delay times range between 10 ms and 100 h.
Wiring a timing relay A timing relay is integrated into your circuit in the form of a contact. The function of the relay is defined via the parameter display. The relay is started via the trigger input TRG and can be reset via the reset input RES. To prevent unpredictable switching states, use each coil of a relay once only in the circuit diagram. Task: 왘 At least two elements are needed in the circuit diagram Switch on output Q1 1.5 min. after actuation for a timing relay: via I1, A relay contact in the contact Switch off T2 via I2. field, in this case T2 Circuit diagram: A trigger coil in the coil field, in I1-------TT2 this case TT2. You can also wire up the reset coil I2-------RT2 T2-------ÄQ1 RT2 if you wish.
왘 Enter the number of the relay contact T2 and press OK.
왘 Specify the function of the relay.
X w g
Ä sTRG dT2
M:Sn01.50n Ä
84 yRES b +
08/00 AWB2528-1304-GB
The parameter set for timing relay Parameter display: T2 is displayed.
Page 88
Timing relays Parameter set for times The parameter display for a timing relay is used to modify the switching function, setpoint time and time range and to enable or disable parameter access. Switch function Time units Trigger (connected) Reset coil (not connected)
ü
S Ä w00.00g n30.00n sTRG yRES dT1 b +
Act. time Setpoint Relay no. Parameter display
A contactor symbol “Ä” in front of TRG or RES indicates whether the relay function is wired in the circuit diagram. The coil terminals are not shown if you access the parameters via the PARAMETER menu option. The actual time is only displayed in Run mode. To view the actual time, call up the parameter display via the power flow display or using the PARAMETER option.
08/00 AWB2528-1304-GB
Switch function parameters
X
Switch with on-delay
?X
Switch with on-delay and random time range
â
Switch with off-delay
?â
Switch with off-delay and random time range
ü
Switch with single-pulse
Ü
Switch with flashing
Minimum time setting with EASY412: 40 ms EASY600: 80 ms A time value less than the maximum “easy” cycle time may cause uncontrolled switching states.
85
Page 89
Drawing a Circuit Diagram with “easy” Time range and setpoint time parameters S
Resolutio n
00.00 00.00 ... 99.99
10 ms
M:S 00:00 Minutes: Seconds, 00:00 ... 99:59
1s
H:M 00:00 Hours: Minutes, 00:00 ... 99:59
1 min.
Parameter set displayed via the PARAMETER menu option +
- Access disabled
Access enabled
Timing relays, on-delayed, without and with random switching The relay switches a contact after the setpoint delay has elapsed. X
?X
With random switching, the relay contact switches randomly at any time up to the specified time value (shown shaded in figure).
Signal diagram: on TRG on RES on
A t B t C
The trigger input starts the time (t). If the trigger input disconnects after the time has elapsed, the contact is reset (A). If the trigger coil drops out before the time has elapsed, the contact is not switched (B). The reset coil has priority over the trigger coil and always 86
08/00 AWB2528-1304-GB t
Page 90
Timing relays resets the relay contact (C). If the time is set to zero, the contact follows immediately after the trigger signal. Typical applications Switching conveyor belts on or off after a delay Detecting gaps in the switching of sensors in the event of a fault Automatic window shutter control with random switching times Timing relays, off-delayed with and without random switching The relay switches a contact immediately and then resets it after the setpoint delay has elapsed. â
?â
With random switching, the relay contact switches randomly at any time up to the specified time value (shown shaded in figure).
Signal diagram: on TRG on RES on
08/00 AWB2528-1304-GB t A
B t C
The trigger coil switches the contact. If the trigger coil (A) drops out, the setpoint time starts and resets the contact after the time has elapsed. The reset coil has priority over the trigger coil and always resets the 87
Page 91
Drawing a Circuit Diagram with “easy” relay contact (B, C). If the time is set to zero, the contact follows immediately after the trigger signal. Typical applications Activating the deceleration of motors or fans Automatic lighting control for vacant buildings with random switching times Timing relays, single pulse The relay switches a contact for a time equal to the delay time set, regardless of the length of the trigger signal. ü
Signal diagram: TRG on on RES on t t
The reset coil has priority over the trigger coil and resets the relay contact before the time has elapsed. If the time is set to zero, the contact is set for the duration of one cycle.
Typical applications Adjusting switching signals to a defined pulse length Shortening pulses to the duration of a cycle 88
08/00 AWB2528-1304-GB
The cycle time varies according to the length of the circuit diagram.