Page 72
Working with contacts and relays Close the delete operation with ALT or by moving the cursor to a contact or coil field.
Inserting and deleting a circuit connection The “easy” circuit diagram shows four of the 41 or 121 circuit connections in the display at the same time. “easy” automatically scrolls up or down the display to show hidden circuit connections – even empty ones – if you move the cursor past the top or bottom of the display. A new circuit connection is added below the last connection or inserted above the cursor position: 왘 Position the cursor on the first contact field of the empty circuit connection. 왘 Press ALT.
08/00 AWB2528-1304-GB
The existing circuit connection with all its additional connections, will be “shifted” down. The cursor will then be positioned directly in the new circuit connection.
I2u------ÄQ4 I3k
I2u------ÄQ4 Â n
I3k
69
Page 73
Drawing a Circuit Diagram with “easy” Delete circuit connection “easy” will only remove empty circuit connections, i.e. those without contacts or coils. 왘 Delete all the contacts and relay coils from the circuit connection. 왘 Position the cursor on the first contact field of the empty circuit connection. 왘 Press DEL. The subsequent circuit connection(s) will be “pulled up” and any existing links between circuit connections will be retained.
Switching via the cursor buttons With “easy”, you can also use the four cursor buttons as hard-wired inputs in the circuit diagram. The buttons are shown in the circuit diagram as contacts P1 to P4. The P buttons can be activated and deactivated in the System menu.
P2 P1
P3 P4
70
08/00 AWB2528-1304-GB
The P buttons can also be used for testing circuits or manual operation. These button functions are also useful for servicing and commissioning purposes.
Page 74
Working with contacts and relays Example 1 A lamp at output relay Q1 is switched on and off via inputs I1 and I2 or using cursor buttons ÍÚ.
Example 2 Terminal I1 is used to control output relay Q1. Terminal I5 switches to Cursor button mode and deactivates circuit connection I1 via m1.
I1u------SQ1 P2k
I2u------RQ1 P4k
I5-------ÄM1 I1-m1u---ÄQ1 P1-M1k
The P buttons are only recognised as contacts in the Status menu, and not in the Power flow display. The Status menu display shows whether the P buttons are used in the circuit diagram. I12345678 P2 ######## MO ####
Q1234
P P2
08/00 AWB2528-1304-GB
P-
01:00 STOP
............ MO 02:00
P2
........STOP
Button function wired and active Button function wired, active and P2 button Í pressed Button function wired, not active Empty box: P buttons not used
71
Page 75
Drawing a Circuit Diagram with “easy” Checking the circuit diagram “easy” contains a built-in measuring device enabling you to monitor the switching states of contacts and relay coils during operation. 왘 Complete the small parallel connection and switch “easy” to Run mode via the main menu. 왘 Return to the circuit diagram display.
I2---u---ÄQ4 I3---k
You are now unable to edit the circuit diagram. If you switch to the circuit diagram display and are unable to modify a circuit diagram, first check whether “easy” is in Stop mode. The circuit diagram display performs two functions depending on the mode: STOP: Creation of the circuit diagram RUN: Power flow display 왘 Switch on I3. In the power flow display, energized connections are thicker than non-energized connections.
72
I3---k
You can follow a current-carrying connection across all circuit connections by scrolling the display up and down. The power flow display will not show signal fluctuations in the millisecond range. This is due to the inherent delay factor of LCD displays.
08/00 AWB2528-1304-GB
I2---u---ÄQ4
Page 76
Working with contacts and relays Coil functions You can set the coil function to determine the switching behaviour of relay coils. The following coil functions are available for relays Q, M, S, D, “:” Circuit diagram symbol
“easy” symbol Ä ä S R
08/00 AWB2528-1304-GB
Coil function Example Contactor function
ÄQ1,ÄD2, ÄS4,Ä:1 ÄM7
Impulse relay function
äQ3,äM4, äD8,äS7
Set (latching)
SQ8,SM2, SD3,SS4
Reset (unlatching)
RQ4,RM5, RD7,RS3
Marker relay M is used as a “flag”. The S relay can be used as the output of an expansion unit or as a marker if no expansion unit is connected. The only difference between them and the output relay Q is that they have no output terminals.
The functions of timer and counter relays are explained in the relevant relay description. The coil function Ä (contactor) should only be used once for each coil. Otherwise the last coil in the circuit diagram will determine the status of the relay.
73
Page 77
Drawing a Circuit Diagram with “easy” To ensure a clear overview of all relay states only assign the same coil function once to a relay (ä, S, R). However, retentive coil functions such as ä, S, R can be used several times if required by the circuit diagram logic. Exception: The coil function can be used properly several times when using jumps to structure the circuit diagram. Rules for wiring relay coils Use the contactor or “impulse relay” function once only for each relay coil. Only use the “latch” (S) and “unlatch” (R) functions once to control each relay in order to ensure greater clarity in the circuit diagram. Relays with contactor function The output signal follows immediately after the input signal and the relay acts as a contactor. Signal diagram: on on
74
Output relay Q:
ÄQ1...ÄQ8
Marker relay M: Text display relay D: Relay S: Jumps:
(depending on type) ÄM1...ÄM16 ÄD1...ÄD8 (EASY600) ÄS1...ÄS8 (EASY600) Ä:1...Ä:8 (EASY600)
08/00 AWB2528-1304-GB
Representation in “easy”
Page 78
Working with contacts and relays Impulse relay The relay coil switches whenever the input signal changes from 0 to 1. The relay behaves like an impulse relay. Signal diagram: on on
Representation in “easy” Output relay Q:
08/00 AWB2528-1304-GB
ÄQ1...ÄQ8
(depending on type) äM1...äM16 Marker relay M: äD1...äD8 (EASY600) Text display relay D: äS1...äS8 (EASY600) Relay S: A coil is automatically switched off if the power fails and if “easy” is in Stop mode. Exception: Retentive coils retain signal 1 (see chapter 8, page 151).
75
Page 79
Drawing a Circuit Diagram with “easy” Latching relay The “latch” and “unlatch” relay functions are used in pairs. The relay picks up when latched and remains in this state until it is reset by the “unlatch” function. Signal diagram: on S on R on
A
B
C
C = Supply voltage switched off
Representation in “easy” Output relay Q:
SQ1...SQ8,RQ1...RQ8
Marker relay M: Function relay (Text) D: Relay S:
(depending on type) SM1...SM16,RM1...RM16 SD1...SD8,RD1...RD8 (EASY600) SS1...SS8,RS1...RS8 (EASY600)
76
08/00 AWB2528-1304-GB
Use each of the two relay functions S and R once only per relay.
Page 80
Function relay
Function relay
If both coils are triggered at the same time, priority is given to the coil further down in the circuit diagram. This is shown in the above signal diagram in section B.
I1-I2----SQ1 ... ...
I2-------RQ1
A latched relay is automatically switched off if the power fails or if the device is in Stop mode. Exception: Retentive coils retain signal 1 (see chapter 8, page 151). The function relays are used to simulate some of the devices used in conventional control systems. “easy” provides the following function relay types: Circuit diagram symbol
Function relays Timing relay, on-delayed Timing relay, on-delayed with random switching Timing relay, off-delayed Timing relay, off-delayed with random switching Timing relay, single pulse Timing relay, flashing
D
C
R
Counter relay, up/down counter
Time switch, weekday/time (only in “easy” models with clock)
08/00 AWB2528-1304-GB
Analog comparator relay (only in “easy” 24 V DC models) Text (only EASY600)
77
Page 81
Drawing a Circuit Diagram with “easy”
A function relay is started via its relay coil or by evaluating a parameter. It switches the contact of the function relay according to its function and the set parameters. Current actual values are cleared if the power supply is switched off or if “easy” is switched to Stop mode. Exception: Retentive coils retain their state (see chapter 8, page 151). In timing and counter relays, it is also possible to change the switching behaviour via the coil functions.
Example with timing and counter relays A warning light flashes when the counter reaches 10. The following example shows function relays C1 and T1. L01+
Hard-wiring with relays P1
S2
S1
C
K1T
R
P1
H1
K1T
L01–
78
2s
08/00 AWB2528-1304-GB
Counter Value 10