Page 62
5
Drawing a Circuit Diagram with “easy”
By working through the example in chapter 4 you should now have gained an initial impression of just how simple it is to create a circuit diagram in “easy”. This chapter describes the full range of “easy” functions and provides further examples of how to use “easy”.
Operation of “easy”
Buttons for drawing circuit diagrams Delete circuit connection, contact, relay or empty line in the circuit diagram Toggle between break and make contact Connect contacts and relays Add circuit connections ÍÚ Change value Move cursor up and down ú í Change position Move cursor to left and right Cursor buttons set as P buttons: ú Input P1, Í Input P2 í Input P3, Ú Input P4 Undo settings from previous OK Exit current display
08/00 AWB2528-1304-GB
Change, add contact/relay Save setting
59
Page 63
Drawing a Circuit Diagram with “easy” Operation of “easy” The cursor buttons in the “easy” circuit diagram perform three functions. The current mode is indicated by the appearance of the flashing cursor. Move Enter Connect
In Move mode you can use ÍÚ ú í to move the â cursor around the circuit diagram in order to select a circuit connection, contact or relay coil. Use OK to switch to Enter mode so that you I1 can enter or change a value at the current cursor position. If you press ESC in Enter mode, “easy” will undo the most recent changes. Press ALT to switch to Connect mode for wiring contacts and relays. Press ALT again to return to Move. Press ESC to leave the circuit diagram and parameter display. “easy” performs many of these cursor movements automatically. For example, “easy” switches the cursor to Move mode if no further entries or connections are possible at the selected cursor position. Opening the parameter display If you specify the contact of a relay type in Enter mode, “easy” automatically switches from the contact number to the parameter display when you press OK. Press í to switch to the next contact or coil field without entering any parameters.
60
08/00 AWB2528-1304-GB l
Page 64
Operation of “easy” Contacts Contacts are used to modify the flow of current in the “easy” circuit diagram. Contacts such as make contacts carry a 1 signal when closed and 0 when open. Every contact in the “easy” circuit diagram can be defined as either a make contact or a break contact. Contact
“easy” representation
Make contact Open in the rest state
I,Q,M,A,Ö,C,T,P,D,S,:,R
Break contact Closed in the rest state i,q,m,a,ö,c,t,p,ì,ï,î
“easy” works with different contacts, which can be used in any order in the contact fields of the circuit diagram. Contact type
Make
Break
EASY412
EASY600
Page
“easy” input terminal
I i
I1...I8
I1...I12
65
0 signal
I13
Expansion status
I14
191
I16
I15...I16
187
P button contact (cursor buttons)
P p
P1...P4
P1...P4
70
“easy” output
Q q
Q1...Q4
Q1...Q8
65
Marker relay contact
M m
M1...M16
M1...M16
73
Counter relay contact
C c
C1...C8
C1...C8
90
Timing relay contact
T t
T1...T8
T1...T8
84
Time switch contact
Ö
ö
Ö1...Ö4
Ö1...Ö4
93
Analog comparator relay
A a
A1...A8
A1...A8
98
Text marker relay
D
ì
–
D1...D8
103
“easy” output (expansion or S auxiliary marker)
S
ï
–
S1...S8
73
Jump label
:
–
–
:1...:8
105
Expansion input terminal
R
î
–
R1...R12
65
Short circuit/overload with expansion
R
î
–
R15...R16
187
08/00 AWB2528-1304-GB
Short circuit/overload
61
Page 65
Drawing a Circuit Diagram with “easy” Relays “easy” has nine different types of relay for wiring in a circuit diagram. Relay type
“easy” symbol
EASY412
EASY600
Coil function
Parameters
“easy” output relay contact
Q
Q1...Q4
EASY618/619:
X
–
Q1...Q6
EASY620/621: Q1...Q8
Marker relay contact
M
M1...M16
M1...M16
X
–
Timing relay contact
T
T1...T8
T1...T8
X
X
Counter relay contact
C
C1...C8
C1...C8
X
X
Time switch contact
Ö
Ö1...Ö4
Ö1...Ö4
–
X
Analog comparator relay
A
A1...A8
A1...A8
–
X
Text marker relay
D
–
D1...D8
X
X
“easy” output relay expansion, S auxiliary marker
S
–
S1...S8
X
–
Conditional jump
:
–
:1...:8
X
–
The switching behaviour of these relays is set by the coil functions and parameters selected. The options for setting output and marker relays are listed with the description of each coil function. The coil functions and parameters are listed with the description of each function relay type.
In the “easy” circuit diagram, contacts and coils are connected up from left to right - from the contact to the coil. The circuit diagram is created on a hidden wiring grid containing contact fields, coil fields and circuit connections. It is then wired up with connections.
62
08/00 AWB2528-1304-GB
Circuit diagram display
Page 66
Operation of “easy” Insert relay contacts in the three contact fields. The first contact field is automatically connected to the voltage. Insert the relay coil to be controlled together with its function and designation in the coil field. Every line in the circuit diagram forms a circuit connection. EASY412 and EASY600 permit the connection of 41 and 121 circuit connections/ current paths respectively. Contact fields Coil field
Circuit connections/ Current paths
I1-I2uT1-ÄQ1
Q1-Ö1kêê êêê êê êê êê êêê êê êê êê êêê
Circuit connections
08/00 AWB2528-1304-GB
Circuit connections are used to produce the electrical contact between relay contacts and the coils. They can be created across several circuit connections. Each point of intersection is a connection. The circuit diagram display performs two functions: In Stop mode it is used to edit the circuit diagram In Run mode it is used to check the circuit diagram using the Power flow display
63
Page 67
Drawing a Circuit Diagram with “easy” Saving and loading circuit diagrams There are two ways of saving circuit diagrams in “easy” externally: By saving to a memory card By saving to a PC running EASY-SOFT.
Once they have been saved, programs can be reloaded into “easy”, edited and run. All circuit diagram data is saved in “easy”. In the event of a power failure the data will be retained until the next time it is overwritten or deleted. Memory card Each memory card contains a circuit diagram which is inserted into the “easy” interface. The way the memory card works and a description of how to transfer a program to the card is given in chapter 6, from page 126. EASY-SOFT EASY-SOFT is an optional PC program with which you can create, store, test (simulate) and manage “easy” circuit diagrams. Completed circuit diagrams are transferred between your PC and “easy” via the connecting cable. Once you have transferred a circuit diagram, simply run “easy” straight from your PC.
Working with contacts and relays
64
In “easy” circuit diagrams, the switches, buttons and relays of conventional circuit diagrams are connected up using input contacts and relay coils.
08/00 AWB2528-1304-GB
Details on the program and transferring circuit diagrams are given in chapter 6, from page 125.
Page 68
Working with contacts and relays Conventional circuit
S1
S2
K1
“easy” circuit diagram Connecting up “easy” Connect S1 to “easy” input terminal I1 Connect S2 to “easy” input terminal I3 Connect load H1 to “easy” output Q4 S1 or S2 switches on H1. “easy” circuit diagram I2u------ÄQ4
K1
H1
I3k
First specify which input and output terminals you wish to use in your circuit. Depending on the model concerned “easy” has 8 or 12 input terminals and 4, 6 or 8 outputs. The signal states at the input terminals are recorded in the circuit diagram using input contacts I1 to I12 or R1 to R12. In the circuit diagram, the outputs are switched using output relays Q1 to Q8 and S1 to S8. Entering and changing contacts and relay coils Define a contact in “easy” via I2 its name and number.
Contact number Contact name
08/00 AWB2528-1304-GB
A relay coil is defined by its coil ÄQ 4 function, name and number. Relay number Relay name Coil function
65
Page 69
Drawing a Circuit Diagram with “easy”
Enter mode is used to modify the value of contact fields and coil fields. The value to be modified value flashes.
If the field or section is empty, “easy” will enter contact I1 or the coil ÄQ1. 왘 Move the cursor using the buttons ú í ÍÚ to a contact or coil field. 왘 Press OK to switch to Enter mode. 왘 Use ú í to select the position you wish to change, or press OK to jump to the next position. 왘 Use Í Ú to modify the value of the position.
Change I1 to I2 in the contact field
Change ÄQ1 to ÄQ8 in the coil field
I1
ÄQ1
Q M Ö C T P D S : R
í or OK
I1
I1 2
3
Í
I2
ä
S
4
R
5 .
16
M
T C D S
. .
ú
ÄQ1
: í or OK
í or OK
ÄQ1 2
3
Ú
ÄQ8
. . . 8 í or OK
“easy” will leave Enter mode when you press ú í or OK to leave a contact field or coil field.
66
08/00 AWB2528-1304-GB
A full list of all the contacts and relays is given in the overview starting on page 61.
Page 70
Working with contacts and relays Delete all the contacts and relay coils from the circuit connection 왘 Move the cursor using the buttons ú í ÍÚ to a contact or coil field. 왘 Press DEL. The contact or the relay coil will be deleted, together with any connections. Changing make contacts into break contacts Every relay contact in the “easy” circuit diagram can be defined as either a make contact or a break contact. 왘 Switch to Enter mode and move the cursor over the contact name. 왘 Press ALT. The make contact will change to a break contact. 왘 Press 2 OK to confirm the change. I2u------ÄQ4 I3k
I2u------ÄQ4 i3k
I2u------ÄQ4 i3kê
Creating and modifying connections l
08/00 AWB2528-1304-GB
Contacts and relay coils are connected in Connect mode using the diagonal wiring arrow which is made available in this mode.
왘 Use ú í ÍÚ to move the cursor onto the contact field or coil field from which you wish to create a connection. Do not position the cursor on the first contact field. At this position the ALT button has a different function (Insert circuit connection).
67
Page 71
Drawing a Circuit Diagram with “easy” 왘 Press ALT to switch to Connect mode. 왘 Use ú í to move the diagonal arrow between the contact fields and coil fields and ÍÚ to move between circuit connections. 왘 Press ALT to leave Connect mode.
“easy” will leave Connect mode automatically when you move the diagonal arrow onto a contact field or coil field which has already been assigned. In a circuit connection, “easy” automatically connects relay contacts and the terminal to the relay coil if there are no empty fields in-between. Never work backwards. You will learn why wiring backwards does not work in chapter 9 on page 177. When wiring more than three contacts in series, use one of 16 marker relays M.
I1-Q4-i3o z-----k hI2-I4-ÄQ2
I1-Q4-i3-ÄM1
I2-I4-M1-ÄQ2
Deleting connections 왘 Move the cursor onto the contact field or coil field to the right of the connection that you want to delete. Press ALT to switch to Connect mode. 왘 Press DEL.
68
If several circuit connections are connected to one another, “easy” first deletes the vertical connection. If you press DEL again, it will delete the horizontal connection as well. You cannot delete connections that “easy” has created automatically.
08/00 AWB2528-1304-GB
“easy” will delete a connection. Closed connections that are lying adjacent will be retained.