The text of a manual · part 8 of 28
User Manual EASY412, EASY600 Control Relay: 4 Commissioning
Pages 50 to 61 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 50
4
Switching on
Commissioning
Before switching on “easy”, check that you have connected the power supply terminals and inputs correctly: 24 V DC version: Terminal +24 V: Voltage +24 V Terminal 0 V: Voltage 0 V Terminals I1 to I12, R1 to R12: Actuation via +24 V 230 V AC version Terminal L: Phase conductor L Terminal N: Neutral conductor Terminals I1 to I12, R1 to R12: Actuation via phase conductor L If you have already integrated “easy” into a system, secure any parts of the system connected to the working area to prevent access and ensure that noone can be injured if, for example, motors start up unexpectedly.
08/00 AWB2528-1304-GB
Setting the menu language
When you switch on “easy” for the first time, you will be asked to select the menu language. 왘 Use the cursor buttons Í or Ú to select the language required. GB English D German F French E Spanish I Italian
ENGLISH GB D F E I
47
Page 51
Commissioning EASY600 also supports the following languages: Portuguese Dutch Swedish Polish Turkish
“easy” operating modes
You can change the language setting at a later date, if you wish, see chapter 7, page 133. If you do not set the language, “easy” will display this menu and wait for you to select a language every time you switch on.
“easy” has two operating modes - Run and Stop. In Run mode “easy” continuously processes a stored circuit diagram until you select Stop or disconnect the power. The circuit diagram, parameters and the “easy” settings are retained in the event of a power failure. All you will have to do is reset the real-time clock after the back-up time has elapsed. Circuit diagram entry is only possible in Stop mode. Caution In Run mode “easy” will immediately run the saved circuit diagram in the unit when the power supply is switched on. This will happen unless Stop mode was set as startup mode. In Run mode outputs are activated according to the switch logic involved. In the case of “easy” models with an LCD display, a circuit diagram on a fitted memory card is not run
48
08/00 AWB2528-1304-GB
왘 Press OK to confirm your choice or press ESC to exit the menu. “easy” will then switch to the Status display.
Page 52
Creating your first circuit diagram automatically. The circuit diagram must first be transferred from the memory card to the “easy” unit. In Run mode “easy”-X models load the circuit diagram on the memory card automatically and run it immediately.
Creating your first circuit diagram
The following small circuit diagram takes you step by step through wiring up your first “easy” circuit diagram. In this way you will learn all the rules, quickly enabling you to use “easy” for your own projects. As with conventional wiring, you use contacts and relays in the “easy” circuit diagram. With “easy”, however, you no longer have to connect up components individually. At the push of a few buttons, the “easy” circuit diagram produces all the wiring. All you have to do is then connect any switches, sensors, lamps or contactors you wish to use. L01+ F1
S1
K1
S2
08/00 AWB2528-1304-GB
K1
H1 L01-
49
Page 53
Commissioning In the following example, “easy” carries out all the wiring and performs the tasks of the circuit diagram highlighted above. L01+ L01F1
S1
+24V 0V
S2
I1 I2
Q1 1
2
H1 L01-
50
The examples were written without the use of expansion units. If an expansion unit is connected, the Status display will first show the status of the basic unit and then the status of the expansion unit before showing the first selection menu.
08/00 AWB2528-1304-GB
Starting point: the Status display When you switch on “easy”, it opens the Status display immediately to show the switching state of the inputs and outputs. It also indicates whether “easy” is already running a circuit diagram.
Page 54
Creating your first circuit diagram EASY412:
EASY600:
I12345678
............
######## MO ####
Q1234
13:24 STOP
MO 02:00
........STOP
왘 Press OK to switch to the main menu.
Press OK to move to the next menu level, and press ESC to move one level back. OK has two other functions: Press OK to save modified settings. In the circuit diagram, you can also press OK to insert and modify contacts and relay coils. In this case “easy” must be in Stop mode 왘 Press 2 OK to enter the circuit diagram display via menu points “PROGRAM...” -> PROGRAM. This is where you will create the circuit diagram.
Circuit diagram display The circuit diagram display is currently empty. The cursor is flashing at the top left, which is where you will start to create your diagram.
08/00 AWB2528-1304-GB
Using the cursor buttons ÍÚ ú í move across the hidden grid lines Circuit diagram grid lines.
ê
êê ↑ êê êê êêê
← →
êê êê êê êêê êê ↓ êê êê êêê êê êê êê êêê
51
Page 55
Commissioning The first three double columns are the contact fields and the right-hand columns form the coil field. Each line is a circuit connection. “easy” will add the first contact automatically. 왘 Now try to wire up the I1-I2----ÄQ1 following “easy” circuit diagram. Switches S1 and S2 are at the input. “I1” and “I2” are the contacts for the input terminals. Relay K1 is represented by the relay coil “ÄQ1”. The symbol “Ä” identifies the coil's function, in this case a relay coil acting as a contactor. Q1 is one of up to eight “easy” output relays.
From the first contact to the output coil With “easy”, you work from the input to the output. The first contact is I1. 왘 Press OK. “easy” inserts the first contact I1 at the cursor position.
I1 êê êê êêê
왘 ...Press 2 OK to move the cursor across the 1 to the next contact field. You could also move the cursor to the next contact field using the cursor button í.
52
08/00 AWB2528-1304-GB
The I flashes and can be changed, for example, to a P for a button input using the cursor buttons Í or Ú. However, nothing needs to be changed at this point, so...
Page 56
Creating your first circuit diagram 왘 Press OK. Again, “easy” creates a contact I1 at the cursor position. Change the contact number to I2 so that break contact S2 can be connected to input terminal I2.
I1 I1 êê êêê
왘 Press OK so that the cursor jumps to the next position and press cursor button Í or Ú to change the number to 2. Press DEL to delete a contact at the cursor position. 왘 Press OK to move the cursor to the third contact field. You do not need a third relay contact, so you can now wire the contacts directly to the coil field.
I1-I2 Â
Wiring “easy” displays a small arrow when creating the circuit diagram.
08/00 AWB2528-1304-GB
Press ALT to activate the arrow and press the cursor buttons ÍÚ ú í to move it. ALT also has two other functions depending on the cursor position: From the left contact field, press ALT to insert a new, empty circuit connection. Then press ALT to set the contact currently under the cursor to either a make or break contact.
53
Page 57
Commissioning
The wiring arrow works between contacts and relays. When you move the arrow onto a contact or relay coil, it changes back to the cursor and can be reactivated with ALT if required.
← l→
êê↓
êêê
“easy” automatically wires adjacent contacts in a circuit connection up to the coil. 왘 Press ALT to “wire” the cursor from I2 through to the coil field. The cursor changes into a flashing wiring arrow and automatically jumps to the next possible wiring position.
êê↑ êê êêê
I1-I2l
êê êê êê êêê êê êê êê êêê
êê êê êê êêê 왘 Press the cursor button í. Contact I2 will be connected up to the coil field. Press DEL to delete a wiring at the cursor or arrow position. Where connections intersect, the vertical connections are deleted first, then, if you press DEL again, the horizontal connections are deleted.
왘 Press the cursor button í again. The cursor will move to the coil field.
“easy” will insert relay coil Q1. The specified coil function “Ä” and the output relay Q1 are correct and do not have to be changed.
54
I1-I2----ÄQ1
08/00 AWB2528-1304-GB
왘 Press OK.
Page 58
Creating your first circuit diagram Your first working “easy” circuit diagram now looks like this:
I1-I2----ÄQ1
Press ESC to leave the circuit diagram display. The diagram will be automatically saved. Once you have connected buttons S1 and S2, you can test your circuit diagram straight away.
Testing the circuit diagram 왘 Switch to the main menu and select the RUN menu option. Toggle between RUN and STOP to set the operating mode required, Run or Stop.
PROGRAM... RUN
PARAMETER
SET CLOCK..
“easy” is in Run mode if the STOP menu option is displayed. Menu options that toggle between two functions always show the next possible setting. The Status display shows the current mode and the switching states of the inputs and outputs. 왘 Change to the Status display and press pushbutton actuator S1. EASY412:
EASY600:
I12345678
12..........
08/00 AWB2528-1304-GB
ââ###### MO
â### 12:50
Q1234
RUN
MO 02:00
1........RUN
The contacts (boxes) for inputs I1 and I2 are activated and relay Q1 picks up.
55
Page 59
Commissioning Power flow display “easy” allows you to check circuit connections in Run mode. This means that you can check your circuit diagram via the built-in power flow display while it is being processed by “easy”. 왘 Change to the Circuit diagram display and press push-button actuator S1.
1 -I2----ÄQ1
The relay picks up and “easy” shows the flow of current. 왘 Press push-button actuator S2, that has been connected as a break contact.
I1-I2----ÄQ1
The circuit connection is interrupted and relay Q1 drops out.
Press ESC to return to the Status display. A circuit diagram does not have to be completed before you can test parts of it with “easy”. “easy” simply ignores any incomplete wiring that is not yet working and only uses the finished wiring.
Deleting the circuit diagram 왘 Switch “easy” to Stop mode.
56
“easy” must be in Stop mode in order to extend, delete or modify the circuit diagram. 08/00 AWB2528-1304-GB
The RUN option is displayed.
Page 60
Creating your first circuit diagram 왘 Use “PROGRAM...” to switch from the main menu to the next menu level. 왘 Select “DELETE PROG” “easy” will display the prompt “DELETE?”.
PROGRAM
DELETE PROG
왘 Press OK to delete the program or ESC to cancel. Press ESC to return to the Status display.
Fast circuit diagram entry You can create a circuit diagram in several ways. The first option is to enter the elements in the circuit diagram and then wire all the elements together. The other option is to use the enhanced operator guidance of “easy” and create the circuit diagram in one go, from the first contact through to the last coil. If you use the first option, you will have to select some of the elements in order to create and connect up your circuit diagram.
08/00 AWB2528-1304-GB
The second, faster option is what you learned in the example. In this case you create the entire circuit connection from left to right.
57
Page 61
08/00 AWB2528-1304-GB
58