The text of a manual · part 7 of 28
User Manual EASY412, EASY600 Control Relay: 3 Installation, pages 42 to 49
Pages 42 to 49 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 42
Connecting the outputs Connecting the outputs
The Q output terminals function inside “easy” as isolated contacts.
Q1 1
2
In the “easy” circuit diagram the relay coils are controlled via the corresponding output relays Q1 to Q4 or Q1 to Q8 (Q6). You can use the signal states of the output relays as make or break contacts in the “easy” circuit diagram to provide additional switching conditions. The relay or transistor outputs are used to switch loads such as fluorescent tubes, filament bulbs, contactors, relays or motors. Check the technical thresholds and output data before installing such devices (see chapter 11, from page 197).
Connecting relay outputs
EASY412-..-R.. 1 Q1 10 000 000
2
1 Q2
2
1 Q3
2
1 Q4
2
R
L
24 V 8A 115 V 8 A 230 V 8 A
2A 2A 2A
1000 W 0V
,N
10 58 W
25.000
8 A/B 16
08/00 AWB2528-1304-GB
L1, L2, L3 (115/230 V + 24 V
39
Page 43
Installation EASY61.-..-R.. 1 2 Q1 10 000 000
1 2
1 2
Q2
1 2
1 2
Q3
Q4
Q5
1 2 Q6
R 24 V 8A 115 V 8 A 230 V 8 A
2A 2A 2A
1000 W 0V
,N
10 58 W
25.000
8 A/B 16 L1, L2, L3 (115/230 V + 24 V
EASY618-..-RE 1 2 S1 F 10 000 000
1 2 S2
1 2 S3
1 2
1 2 S4
S5
1 2 S6
R 24 V 8A 115 V 8 A 230 V 8 A
2A 2A 2A
1000 W 0V
,N
10 X 58 W
F 25.000
F 8 A/B 16 L1, L2, L3 (115/230 V + 24 V
Unlike the inputs, the outputs can be connected to different lines.
40
08/00 AWB2528-1304-GB
Do not exceed the maximum voltage of 250 V AC on a relay contact. If the voltage exceeds this threshold, flashover may occur at the contact, resulting in damage to the device or a connected load.
Page 44
Connecting transistor outputs Connecting transistor outputs
EASY412-..-T..
+24 VQ
0 VQ
Q1 Q2
Q3 Q4
10 A
0V
2.5 A + 24 V 20.4–28.8 V
24 V
R
L
0.5 A
0.5 A
5 W/24 V
EASY62.-..-T..
+24 VQ
0 VQ
Q1 Q2
+ 24 V (20.4–28.8 V
24 V
Q3 Q4
Q5 Q6
Q7 Q8
F10 A
0V
R f 2.5 A
0.5 A
0.5
)
08/00 AWB2528-1304-GB
5 W/24 V
41
Page 45
Installation EASY620-..-TE
S1 S2
S3 S4
S5 S6
S7
S8
+24 VQ
0VQ
F10 A
0V R + 24 V (20.4–28.8 V
24 V
0.5 A
0.5 f 2.5 A
) 5 W/24 V
Parallel connection: Up to four outputs can be connected in parallel in order to increase the power. The output current will increase in this case to a maximum of 2 A.
Caution Please note the following when switching off inductive loads. Suppressed inductive loads cause less interference in the entire electrical system. For optimum suppression the suppressor circuits are best connected directly to the inductive load.
42
08/00 AWB2528-1304-GB
Caution Outputs may only be connected in parallel within a group (Q1 to Q4 or Q5 to Q8, S1 to S4 or S5 to S8), such as Q1 and Q3 or Q5, Q7 and Q8. Outputs connected in parallel must be switched at the same time.
Page 46
Connecting transistor outputs If inductive loads are not suppressed, only one inductive load should be switched off at any one time so as to prevent the driver blocks from possibly overheating. If in the event of an emergency stop the +24 V DC power supply is to be switched off by means of a contact, and if this would mean switching off more than one controlled output with an inductive load, then you must provide suppressor circuits for these loads (see the following diagrams). Q..
+ 24 V U emax < U z < 33 V Q..
0V
0V
Behaviour in the event of short-circuits/overload Should a short circuit or overload occur on a transistor output, this output will switch off. The output will switch on up to maximum temperature after the cooling time has elapsed. This time depends on the ambient temperature and the current involved. If the fault condition persists, the output will keep switching off and on until the fault is corrected or until the power supply is switched off.
08/00 AWB2528-1304-GB
Monitoring for short-circuit/overload see chapter 9, from page 175.
43
Page 47
Installation Expanding inputs/ outputs
You can add expansion units to the following “easy” models in order to increase the number of inputs and outputs: Expandable “easy” basic units
Expansion units
EASY619-..-R.. EASY621-..-T..
EASY618-..-RE
12 inputs AC, 6 relay outputs
EASY620-..-TE
12 inputs DC, 8 transistor outputs
Special expansion units see current catalogue
Local expansion Local expansion units are connected directly next to the basic unit. 왘 Connect the “easy” expansion unit via the “EASY-LINK” plug connector. EASY-LINK
44
EASY6....-RE EASY6....-TE EASY200-EASY
08/00 AWB2528-1304-GB
EASY619-... EASY621-...
Page 48
Expanding inputs/outputs The following electrical separation is implemented between the EASY6..-..-.C. basic unit and the expansion device (separation always in local connection of expansion unit) Simple isolation 400 V AC (+10 %) Safe isolation 240 V AC (+10 %)
Units may be destroyed if the value 400 V AC +10 % is exceeded, and may cause the malfunction of the entire system or machine! Basic unit and expansion unit can be provided with different DC power supplies.
Remote expansion Remote expansion units can be installed and run up to 30 m away from the basic unit.
08/00 AWB2528-1304-GB
Warning The two-wire or multi-core cable between units must have the necessary insulation voltage required for the installation environment concerned. In the event of a fault (earth leakage, short-circuit) serious damage or injury to persons may otherwise occur. A cable such as NYM-0 with a rated operational voltage of Ue = 300/500 V AC is normally sufficient.
45
Page 49
Installation
E+ E-
EASY619-... EASY621-...
EASY6.. RE/TE EASY200EASY
E+ E-
Ue = 300/500 V EASY...-AC-...E
46
08/00 AWB2528-1304-GB
Terminals “E+” and “E-” of the EASY200-EASY are protected against short-circuits and polarity reversal. Functionality is only ensured if “E+” is connected with “E+” and “E-” with “E-”.