Page 33

Installation Connect the inputs, for example, to push-button actuators, switches or relay/contactor contacts. Input signal voltage range: OFF signal: 0 V to 40 V ON signal: 79 V to 264 V Input current R1 to R12 I1 to I6, I9 to I12: I7, I8:

0.5 mA/0.25 mA at 230 V/115 V 6 mA/4 mA at 230 V/115 V

Cable lengths Severe interference to cables can cause inputs to signal 1 without a proper signal being applied. Observe therefore the following maximum cable lengths: R1 to R12, I1 to I6, I9 to I12: I7, I8:

40 m without additional circuit 100 m without additional circuit

30

08/00 AWB2528-1304-GB

For longer lengths connect in series a diode (e.g. 1N4007) for 1 A, min. 1000 V reverse voltage, to the “easy” input. Ensure that the diode is pointing towards the input as shown in the circuit diagram, otherwise “easy” will not detect 1 status.

Page 34

Connecting the inputs L N

L

N

N

I1

115/230 V h

“easy”-AC

Neon bulbs with a maximum residual current of 2 mA/1 mA at 230 V/115 V can be connected to I7 and I8. Always use neon bulbs that are operated with a separate N connection. Caution Do not use reed relay contacts on I7, I8. These may burn or melt due to the high inrush current of I7, I8. Two-wire proximity switches have a residual current on 0. If this residual current is too high, the input of “easy” may only detect the 1 signal.

08/00 AWB2528-1304-GB

Therefore use inputs I7, I8. An additional input circuit is required if more inputs are used.

31

Page 35

Installation Increasing the input current The following input circuit can be used in order to prevent interference and also when using two-wire proximity switches: L N

100 nF/275

L

N

N

I1

115/230 V AC

When using a 100 nF capacitor the drop-off time of the input increases by 80 (66.6) ms at 50 (60) Hz. A resistor can be connected in series upstream of the circuit shown in order to restrict the inrush current. L N

1 kΩ

N

N

32

I1

08/00 AWB2528-1304-GB

L

115/230 V AC

100 nF/275

Page 36

Connecting the inputs Complete devices for increasing the input current are available, for example, from Felten & Guilleaume. L N

L

N

N

I1

1

2

115/230 V AC

F&G Z7-JC/KO

08/00 AWB2528-1304-GB

The increased capacitance increases the dropout time by approx. 300 ms.

33

Page 37

Installation Connecting “easy”-DC and “easy”-DA inputs Use input terminals I1 to I12 to connect push-button actuators, switches or 3 or 4-wire proximity switches. Given the high residual current, do not use 2-wire proximity switches. Input signal voltage range OFF signal: 0 V to 5 V ON signal: 15 V to 28.8 V Input current “easy”-DC: I1 to I6, I9 to I12: R1 to R12

3.3 mA at 24 V,

I7, I8:

2.2 mA at 24 V

“easy”-DA: I1 to I6: I7, I8:

3.3 mA at 12 V, 1.1 mA at 12 V

+...V

0V l1

I2

I7

“easy”-DC, “easy”-DA

34

08/00 AWB2528-1304-GB

DC : +24 V DA : +12 V

Page 38

Connecting the inputs +24 V 0V

>1A

E+ E-

R1 R2 R3 R4

R5

R6

Input 24 V

R7 R8 R9

R10 R11 R12 +24V 0V 0V 24 V

EASY...-DC-.E

Connecting analog inputs Inputs I7 and I8 can also be used to connect analog voltages ranging from 0 V to 10 V.

08/00 AWB2528-1304-GB

Caution Analog signals are more sensitive to interference than digital signals. Consequently, more care must be taken when laying and connecting the signal lines. Incorrect switching states may occur if they are not connected correctly. Use screened twisted pair cables to prevent interference with the analog signals. For short cable lengths, ground the screen at both ends using a large contact area. If the cable length exceeds 30 m or so, grounding at both ends can result in equalisation currents between the two grounding points and thus in the interference of analog signals. In this case, only ground the cable at one end. Do not lay signal lines parallel to power cables. Connect inductive loads to be switched via “easy” outputs to a separate power feed, or use a 35

Page 39

Installation suppressor circuit for motors and valves. If loads such as motors, solenoid valves or contactors are operated with “easy” via the same power feed, switching may result in interference on the analog input signals.

The following four circuits contain examples of applications for analog value processing. Ensure that the reference potential is connected. Connect the 0 V of the power supply unit for the different setpoint potentiometers and sensors shown in the examples to the 0 V of the “easy” power feed. Setpoint potentiometers

~ 0V

+...V

0V

0V

+12 V

I7

DC : +24 V DA : +12 V

36

08/00 AWB2528-1304-GB

Use a potentiometer with a resistance of 1 e.g. 1 0.25 W.

Page 40

Connecting the inputs

1.3 kO/0.25 W 1 kO/0.25 W

+...V 0 V

0V

I7

DC : +24 V DA : +12 V

Light intensity sensors

~

12 V 0...10 V

0V

0V

+...V

0V

0V

+12 V

I7

08/00 AWB2528-1304-GB

DC : +24 V DA : +12 V

37

Page 41

Installation Temperature sensors

+24 V

–0 V Out 0...10 V

+...V

0V

–35...55 °C

I7

0V

DC : +24 V DA : +12 V

20 mA sensors 4 to 20 mA (0 to 20 mA) sensors can be connected easily without any problem using an external 500 resistor.

햲

4...20 mA

500 Ω

+...V

0V

0V

I7

DC : +24 V DA : +12 V

햲 Analog sensor

4 mA = 0.2 V 10 mA = 4.8 V 20 mA = 9.5 V (Based on V = R I = 478 10 mA 苲 4.8 V).

38

08/00 AWB2528-1304-GB

The following values apply: