Page 24
3
Installation
“easy” must only be installed and wired up by trained electricians or other persons familiar with the installation of electrical equipment. Danger of electric shock Never carry out electrical work on the device while the power supply is switched on. Always follow the safety rules: Switch off and isolate Secure against reclosing Ensure that the device is no longer live Cover adjacent live parts “easy” is installed in the following order: Mounting Wiring up the inputs Wiring up the outputs Connecting the power supply
08/00 AWB2528-1304-GB
Mounting
Install “easy” in an enclosure, switch cabinet or distribution board so that the power feed and terminal connections cannot be touched accidentally during operation.
Clip “easy” onto a DIN EN 50 022 top-hat rail or fix “easy” in place using mounting feet. “easy” can be mounted either vertically or horizontally. When using “easy” with expansion units, connect the expansion concerned before mounting (see page 24).
21
Page 25
Installation
30
For ease of wiring, leave a gap of at least 3 cm between “easy” terminals and the wall or adjacent devices.
30
30
30
1
2
왘 Check that “easy” is seated firmly. “easy” is mounted vertically on a top-hat rail in the same way.
22
08/00 AWB2528-1304-GB
Mounting on top-hat rail 왘 Hook “easy” to the top edge of the top-hat rail and hinge into place while pressing down slightly as shown by the arrows. Press down lightly on both the device and the top-hat rail until “easy” snaps over the lower edge of the tophat rail. “easy” will clip into place and will be secured by the built-in spring mechanism without needing screws.
Page 26
Mounting Mounting on a mounting plate For a screw fixing, use a mounting plate that can be fitted on the back of “easy”. Mounting feet can be ordered as an accessory.
08/00 AWB2528-1304-GB
EASY200-EASY: EASY412:
EASY600:
23
Page 27
Installation Connecting the expansion device
1 2
3
24
08/00 AWB2528-1304-GB
4
Page 28
Terminals Terminals
Tools Slot-head screwdriver, width 3.5 mm, tightening torque 0.6 Nm. Cable cross-sections Solid 0.2 to 4 mm2 Flexible with ferrule: 0.2 (AWG 24) to 2.5 mm2 (AWG 12)
Connecting the power supply
For the technical data of both versions, “easy”DC with 24 V DC and “easy”-AC with standard voltages of 100 V to 240 V AC, refer to chapter 11 from page 197. The EASY600 models run a system test for five seconds after the power supply has been switched on. Either Run or Stop mode will be activated after these five seconds, depending on the default setting.
AC units L N
08/00 AWB2528-1304-GB
F1
L N N 115/230 V ~
25
Page 29
Installation EASY...-AC-.E L N F1
E+ E-
R1
...
R12 L N N 115/230 V ~
DANGER of electric shock with “easy”-AC units! With “easy” NEVER swap over the live (L) and neutral conductor (N) terminals as the interface will then carry the live (L) potential power of 230 V/115 V. There is a danger of electric shock if the plug is not properly connected or if conductive objects are inserted into the socket.
26
08/00 AWB2528-1304-GB
Attention A short current surge will be produced when switching on for the first time. Do not switch on “easy” via Reed contacts since these may burn or melt.
Page 30
Connecting the power supply DC and DA models
F1
+...V 0 V
0V
DC : +24 V DA : +12 V
EASY...-DC-.E L01+ L01F1
E+ E-
08/00 AWB2528-1304-GB
R1
...
R12 24V 0V 0V 24 V
“easy” DC is protected against polarity reversal. To ensure that “easy” works correctly, ensure that the polarity of each terminal is correct.
27
Page 31
Installation
Connecting the inputs
Cable protection Both “easy” AC and DC versions require cable protection (F1) rated for at least 1 A (slow). When “easy” is switched on for the first time, its power supply circuit behaves like a capacitor. Use an appropriate device for switching on the power supply and do not use any reed relay contacts or proximity switches.
“easy” inputs switch electronically. Once you have connected a contact via an input terminal, you can reuse it as a contact in your “easy” circuit diagram as often as you like. L +24 V S1
N 0V
Ι1
Ι1
− Ι1
Connect contacts such as push-button actuators or switches to “easy” input terminals.
Caution For “easy”-AC, connect the inputs to the same line as the power feed in accordance with VDE, IEC, UL and CSA safety regulations. Otherwise, “easy” will not detect the switching level or may be damaged by overvoltage.
28
08/00 AWB2528-1304-GB
Connecting “easy”-AC inputs
Page 32
Connecting the inputs L N
L N N 230 V AC l1
R1 R2 R3 R4
R5
I2
I7
“easy”-AC L N
>1A
E+ E-
R6
R7 R8 R9
Input 115/230 V
R10 R11 R12
L
N
N
115/230 V
08/00 AWB2528-1304-GB
EASY...-AC-.E
29