Page 128
6
Loading and Saving Circuit Diagrams
You can either use the “easy” interface to save circuit diagrams to a memory card or use EASY-SOFT and a transmission cable to transfer them to a PC.
EASY...-..-..X “easy” models without buttons can be loaded with a circuit diagram via EASY-SOFT or automatically from the fitted memory card every time the power supply is switched on.
Interface The “easy” interface is covered.
08/00 AWB2528-1304-GB
DANGER of electric shock with “easy”-AC units If the voltage terminals for phase (L) and neutral conductor (N) are swapped over, the connected 230 V/115 V voltage will be present at the “easy” interface. There is a danger of electric shock if the plug is not properly connected or if conductive objects are inserted into the socket.
125
Page 129
Loading and Saving Circuit Diagrams
왘 Carefully remove the cover with a screwdriver. To close the slot again, push the cover back onto the slot.
Memory card
The “easy-M-8K” card for EASY412 or “easy-M16K” for EASY600 are available as accessories. Circuit diagrams containing all the relevant data can be transferred from the “easy-M-8K” memory card to the EASY600. A transfer, however, in the other direction is not possible.
Information stored on the memory card is “nonvolatile” (the information is not lost when the power is switched off), and thus you can use the card to make a backup copy of your circuit diagram and/or to transfer it to another “easy” device.
126
08/00 AWB2528-1304-GB
Each memory card can hold one “easy” circuit diagram.
Page 130
Memory card The following information is saved to the memory card: the circuit diagram all parameter settings of the circuit diagram all display texts with functions system settings debounce (input delay) P buttons password retention on/off 왘 Insert the memory card in the open interface slot. EASY412 (햳 = easy-M-8K):
EASY600 (햳 = easy-M-16K):
2
2 1
1
With “easy” you can insert and remove the memory card even if the power feed is switched on, without the risk of losing data.
08/00 AWB2528-1304-GB
Loading or storing the circuit diagram You can only transfer circuit diagrams in Stop mode. EASY...-..-..X models without buttons and LCD can be loaded with a circuit diagram automatically from the fitted memory card every time the power supply is switched on. If the circuit diagram on the memory card is not valid, the circuit diagram already in the “easy” unit is retained.
127
Page 131
Loading and Saving Circuit Diagrams 왘 Switch to Stop mode. 왘 Select “PROGRAM...” from the main menu. 왘 Select the “CARD...” menu PROGRAM option. The “Card...” menu option will only appear if you have inserted a functional memory card.
You can transfer a circuit diagram from “easy” to the card and from the card to the “easy” memory or delete the content of the card.
DELETE PROG CARD...
DEVICE-CARD CARD-DEVICE DELETE CARD
If the operating voltage fails during communication with the card, repeat the last procedure since “easy” may not have transferred or deleted all the data. After transmission, remove the memory card and close the cover. Saving a circuit diagram to the card 왘 Select “DEVICE-> CARD”. 왘 Confirm the prompt with OK to delete the contents of the REPLACE ? memory card and replace it with the “easy” circuit diagram.
128
08/00 AWB2528-1304-GB
Press ESC to cancel.
Page 132
Memory card Loading a circuit diagram from the card 왘 Select the “CARD-> DEVICE-CARD DEVICE” menu option. CARD-DEVICE 왘 Press OK to confirm the prompt if you want to delete DELETE CARD the “easy” memory and replace it with the card content. Press ESC to cancel. If a problem occurs during transmission, “easy” will display the message “PROG INVALID”.
INVALID PROG
This either means that the memory card is empty or that the circuit diagram on the card contains function relays that “easy” does not recognise. The “time switch” function relays only work with “easy” versions with a real-time clock (type EASY...-..-.C.). The “analog comparator” function relay is only used with “easy”-DC 24 V DC versions and “easy”-DA.
08/00 AWB2528-1304-GB
Relays with text display, jumps and “S”, “R” markers only work with EASY600 versions. If the memory card is password-protected, the password will also be transferred to the “easy” memory and will be active immediately. Deleting a circuit diagram from the card 왘 Select the “DELETE CARD” menu option. 왘 Press OK to confirm the DELETE ? prompt and to delete the card content. Press ESC to cancel.
129
Page 133
Loading and Saving Circuit Diagrams EASY-SOFT
EASY-SOFT is a PC program for creating, testing and managing “easy” circuit diagrams. You should only transfer data between the PC and “easy” using the special PC interface cable, which is available as an optional accessory EASY-PC CAB. DANGER of electric shock with “easy”-AC units ONLY the “EASY-PC CAB” cable will guarantee reliable electrical isolation from the interface voltage.
왘 Connect the PC cable to the serial PC interface. 왘 Insert the “easy” plug in the opened interface. 왘 Activate the Status display on the “easy”
“easy” cannot exchange data with the PC while the circuit diagram display is on screen.
EASY-SOFT provides extensive help on how to use the software. 왘 Start EASY-SOFT and click on Help.
130
08/00 AWB2528-1304-GB
Use EASY-SOFT to transfer circuit diagrams from your PC to “easy” and vice versa. Switch “easy” to Run mode from the PC to test the program using the current wiring.
Page 134
EASY-SOFT The on-line help provides all additional information about EASY-SOFT that you will need. If a problem occurs during transmission, “easy” will display the message “PROG INVALID”.
INVALID PROG
왘 Check whether the circuit diagram contains a function relay that “easy” does not recognise:
The “time switch” function relays only work with “easy” versions with a real-time clock (type EASY...-..-.C.). The “analog comparator” function relay is only used with “easy”-DC 24 V DC versions and “easy”-DA. Relays with text display, jumps and “S” markers only work with EASY600 versions. If the operating voltage fails during communication with the PC, repeat the last procedure. It is possible that not all the data was transferred between the PC and “easy”.
08/00 AWB2528-1304-GB
왘 After transmission, remove the cable and close the cover.
131
Page 135
08/00 AWB2528-1304-GB
132