Page 136

7

“easy” Settings

Settings can only be carried out on “easy” models provided with buttons and LCD display. EASY-SOFT from V 2.1 upwards can be used to set all models.

Password protection

The “easy” circuit diagram, function relay settings and system parameters can be password protected. In this case the password consists of a value between 0001 and 9999. The number combination 0000 is used to delete a password.

08/00 AWB2528-1304-GB

Password protection blocks access to the circuit diagram menu and System menu and thus offers protection against unauthorised starting or modification of the circuit diagram modification of function relay parameters via the circuit diagram transfer of a circuit diagram from and to the memory card modification of system parameters Set new password Debounce (input delay) ON/OFF P buttons ON/OFF Menu language selection Only parameters marked with “–” are passwordprotected. Parameters marked with “+” can still be modified via the PARAMETER menu.

133

Page 137

“easy” Settings The password does not offer protection against:

changing between operating modes Run or Stop. setting the clock access to the parameters of function relays marked with “+”. A password that has been entered in “easy” is transferred to the memory card together with the circuit diagram, irrespective of whether it was activated or not. If this “easy” circuit diagram is loaded from the memory card, the password will also be transferred to “easy” and become activated immediately.

Setting the password Passwords can be set in the System menu in both Run or Stop operating modes. If, however, a password is already activated, you cannot change to the System menu. 왘 Press DEL and ALT to call up the System menu. 왘 Select the menu option “PASSWORD...” to enter the password. ENTER PW Â

왘 Set the password using the cursor buttons: ú í move to the 4-digit entry field ú í select digit in password ÍÚ set a value between 0 and 9.

134

----

08/00 AWB2528-1304-GB

If a password has not been entered already, “easy” will switch directly to the password display and show four dashes: no password available.

Page 138

Password protection 왘 Save the new password by pressing OK. “easy” will hide a valid password with XXXX.

ENTER PW 1000

Press OK or ESC to exit the password display. The password is now valid but not yet activated.

Activating the password You can activate a valid password in three different ways: automatically when “easy” is switched on again automatically after loading a protected circuit diagram from the memory card via the password menu 왘 Press DEL and ALT to call up the System menu. 왘 Open the password menu via the menu option “PASSWORD...”. “easy” will only show this menu if a password is present.

08/00 AWB2528-1304-GB

CHANGE PW. ACTIVATE

Make a note of the password before you activate it. If the password entry is no longer known, “easy” can still be unlocked, however, the circuit diagram and other settings will be lost. 왘 Select “ACTIVATE” and press OK. The password is now active. “easy” will automatically return to the Status display.

135

Page 139

“easy” Settings You must unlock “easy” using the password before you can edit a circuit diagram or enter the System menu.

Unlocking “easy” Unlocking “easy” will deactivate the password. You can re-activate password protection later via the password menu or by switching the power supply off and on again. 왘 Press OK to switch to the main menu.

The “PASSWORD...” entry will flash.

PASSWORD...

왘 Press OK to enter the password entry menu.

PARAMETER

STOP

SET CLOCK..

If “easy” shows “PROGRAM...” in the main menu instead of “PASSWORD...” , this means that there is no password protection active. “easy” will display the password entry field. 왘 Set the password using the cursor buttons. 왘 Confirm with OK.

ENTER PW Â XXXX

If the password is correct, “easy” will switch automatically to the Status display.

The System menu is also accessible.

136

PROGRAM... STOP

PARAMETER

SET CLOCK..

08/00 AWB2528-1304-GB

The “PROGRAM...” menu option is now accessible so that you can edit your circuit diagram.

Page 140

Password protection Changing or deleting a password 왘 Press DEL and ALT to call up the System menu. 왘 Open the password menu via the menu option “PASSWORD...”. The “CHANGE PW” entry will flash. “easy” will only show this menu if a password is present. 왘 Press OK to enter password entry menu. 왘 Use ú í to move to the 4-digit entry field. 왘 Modify the four password digits using the cursor buttons. 왘 Confirm with OK.

CHANGE PW. ACTIVATE

ENTER PW Â ----

ENTER PW 1005

Press ESC to exit the password display. Deleting Use number combination 0000 to delete a password.

08/00 AWB2528-1304-GB

If a password has not been entered already, “easy” will show four dashes:

ENTER PW Â ----

137

Page 141

“easy” Settings Password incorrect or not known If you no longer know the exact password, you can try to re-enter the password several times. Entered an incorrect password? 왘 Re-enter the password.

After the fourth entry attempt “easy” will ask whether you wish to delete the circuit diagram and data.

ENTER PW Â XXXX

DELETE ALL?

왘 Press ESC: No entry will be deleted. OK: Circuit diagram, data and password will be deleted.

“easy” will return to the Status display. If you no longer know the exact password, you can press OK to unlock the protected “easy”. The saved circuit diagram and all function relay parameters will be lost.

138

08/00 AWB2528-1304-GB

Pressing ESC will retain the circuit diagram and data. You can then make another four attempts to enter the password.

Page 142

Changing the menu language Changing the menu language

EASY412 provides five menu languages and EASY600 provides ten. These can be set as required via the System menu. Language

LCD display

Abbreviation

English

ENGLISH

GB

German

DEUTSCH

D

French

FRANCAIS

F

Spanish

ESPANOL

E

Italian

ITALIANO

I

Additional languages with EASY600

Portuguese

PORTUGUES

–

Dutch

NEDERLANDS

–

Swedish

SVENSKA

–

Polish

POLSKI

–

Turkish

TURKCE

–

Language selection is only possible if “easy” is not password-protected. 왘 Press DEL and ALT to call up the System menu. 왘 Select “GB D F E I..” as required to modify the menu language.

08/00 AWB2528-1304-GB

The language selection for the first entry “GB” is displayed.

ENGLISH

왘 Use Í or Ú to select the new menu language, e.g. Italian. 왘 Confirm with OK.

GB D F E I

“easy” will now show the new menu language.

PASSWORD...

Press ESC to return to the Status display.

P TASTO

RIT.INGR. ON ON

GB D F E I..

139

Page 143

“easy” Settings Changing parameters

“easy” allows you to change function relay parameters such as times and counter setpoints without having to call up the circuit diagram. This is possible regardless of whether “easy” is running a program or is in Stop mode. 왘 Press OK to switch to the main menu. 왘 Start the parameter display by selecting PARAMETER. A complete parameter set will be shown. In the example these are the parameters for a timing relay T1.

ü S

The following requirements must be fulfilled for a parameter set to be displayed and accessed:

w00.00g n30.00n sTRG yRES dT1 b + a function relay must have been included in the circuit diagram the parameter set has been enabled for access, indicated by the “+” character at the bottom right of the display.

You can enable or disable parameter access using the parameter “+” or “–” characters respectively in the circuit diagram. 왘 Use Í or Ú to scroll through the parameter sets. For this the cursor must be located on the identifier of the function relay, in this case T1.

140

ü S w00.00g n30.00n sTRG yRES dT1 b +

08/00 AWB2528-1304-GB

Use the PARAMETER menu to access and modify accessible parameter sets. Parameter sets for which access is not enabled are not displayed. “easy” therefore allows you to protect parameters with the use of a password.

Page 144

Changing parameters 왘 Change the values for a parameter set: ú í Move between the parameters ÍÚ Change the value of a parameter OK Save parameter or ESC Retain previous setting. The cursor should still be on the identifier T1.

Press ESC to leave the parameter display. The parameter display is opened via the PARAMETER menu. “Ä” coil terminals for counters and times are not displayed here, even if they have been wired. Variable parameters for function relays You can modify the relay parameters used in the circuit diagram in three different ways: All circuit diagram parameters can be adjusted in Stop mode via the circuit diagram. Setpoints can be modified in Run mode via the circuit diagram. Setpoints can be modified via the PARAMETER menu. The following setpoints can be modified:

08/00 AWB2528-1304-GB the time value for timing relays the counter setpoints of counter relays the day and ON/OFF times of time switches the comparison setpoint of analog comparators. In Run mode “easy” operates with a new setpoint as soon has it has been modified in the parameter display and saved with OK.

141