User Manual EASY412, EASY600 Control Relay: 7 “easy” Settings, pages 145 to 153

Pages 145 to 153 of 228, from User Manual EASY412, EASY600 Control Relay

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Moeller 621-DC-TCX

Page 145

“easy” Settings Example: Changing switch times for outside lighting The outside lighting of a building is automatically switched on from 19:00 to 23:30 Mondays to Fridays in the “easy” circuit diagram. The parameter set for the time switch function relay 1 is saved in channel “A” and looks like this.

wMO-FRg n15:20dÖ1

ON s19:00n A OFFy23:30b +

The outside lighting is now required to switch on between 19:00 and 22:00 on Saturdays. 왘 Select PARAMETER from the main menu. The first parameter set is displayed.

왘 Use Í or Ú to scroll through the parameter sets until channel A of time switch 1 is displayed. 왘 Press Í to select the next wMO g empty parameter set, in this n15:21dÖ1 case channel B of time switch 1. ON s--:--n B 왘 Change the value for the day interval from MO to SA: ú í Move between the parameters ÍÚ Change value. 왘 Set the switching on time to 19:00.

OFFy--:--b + wSA g n15:21dÖ1

ON s--:--n B OFFy--:--b + wSA g n15:21dÖ1

ON s19:00n B OFFy--:--b +

142

08/00 AWB2528-1304-GB

The current time is 15:21.

Page 146

Setting the time 왘 Set the switching off time to 22:00. 왘 Press OK.

wSA g n15:21dÖ1

ON s19:00n B OFFy22:00b +

“easy” will save the new parameters. The cursor will remain in the contact field on channel identifier “B”. Press ESC to leave the parameter display.

wSA g n15:21dÖ1

ON s19:00n B

OFFy22:00b +

The time switch will now also switch on at 19:00 on Saturdays and switch off at 22:00.

Setting the time

“easy”-C models are fitted with a real-time clock. This allows the time switch function relay to be used for timed switching operations. If the clock is not set yet or if “easy” is switched on after the battery backup time has expired, the clock will start with the MO setting and the number of the current operating system, in this case 01:00 for EASY412 and 02:00 for EASY600. I12345678

######## MO ####

Q1234

01:00 STOP

............ MO 02:00

........STOP

08/00 AWB2528-1304-GB

The “easy” clock has a one-week cycle so that weekdays and times have to be set. 왘 Select SET CLOCK from the main menu.

143

Page 147

“easy” Settings This will open the menu for setting the time. 왘 Select SET CLOCK. 왘 Set the values for day and time. ú í Move between the parameters ÍÚ Change the value of a parameter OK Save day and time or ESC Retain previous setting. Press ESC to leave the time setting display.

Changing between winter/summer time (DST)

SET CLOCK

SUMMER TIME

WINTER TIME DAY

: MO

TIME : 01:00

WINTER TIME DAY

: WE

TIME : 09Â30

“easy”-C models are fitted with a real-time clock. The clock can be toggled between winter and summer time using the cursor buttons. 왘 Select SET CLOCK from the main menu. This will open the menu for setting the time. Select menu option “WINTER TIME” or “SUMMER TIME” as required.

SET CLOCK

WINTER TIME

왘 Otherwise select “WINTER TIME” and press OK. “easy” will set the clock one hour back, e.g. from 17:43 Sunday to 16:43 Sunday. The display will then switch to “SUMMER TIME”. 144

08/00 AWB2528-1304-GB

Changing to winter time “easy” will display “SUMMER TIME” as the next possible option if winter time is already set.

Page 148

Activating debounce (input delay) Changing to summer time 왘 Select “SUMMER TIME” and press OK. “easy” will set the clock one hour forward, e.g. from 12:30 Wednesday to 13:30 Wednesday.

Activating debounce (input delay)

SET CLOCK

SUMMER TIME

The display will then switch to “WINTER TIME”. With EASY412, operating system 1.0: The weekday is not changed automatically with the time. If you change the time around midnight you must change the weekday as well.

Input signals can be evaluated by “easy” with a debounce delay. This enables, for example, the trouble-free evaluation of switches and push-button actuators subject to contact bounce. In many applications, however, very short input signals have to be monitored. In this case, the debounce function can be switched off.

왘 Press DEL and ALT to call up the System menu. 왘 Select the SYSTEM menu. If “easy” is password-protected you cannot open the System menu until you have “unlocked” it. Set the Debounce mode using the menu options “DEBOUNCE OFF”/ “DEBOUNCE ON”.

DEBOUNCE OFF P

ON

STOP MODE

08/00 AWB2528-1304-GB

RETENTION ON

145

Page 149

“easy” Settings Deactivating debounce (input delay) If “easy” is showing “DEBOUNCE ON” in the display, this means that Debounce mode has already been deactivated. 왘 Otherwise select “DEBOUNCE OFF” and press OK. If Debounce mode is deactivated the display will show “DEBOUNCE ON”. Activating debounce (input delay) 왘 Select “DEBOUNCE ON” DEBOUNCE ON and press OK. If Debounce mode is activated the display will show “DEBOUNCE OFF”.

Activating and deactivating P buttons

ON

STOP MODE

RETENTION ON

Press ESC to return to the Status display. How “easy” input and output signals are processed internally is explained in chapter 9, from page 175.

Even though the cursor buttons (P buttons) have been set as push-button actuator inputs in the circuit diagram, this function is not activated automatically. This prevents any unauthorised use of the cursor buttons. The P buttons can be activated in the System menu. If “easy” is password-protected you cannot open the System menu until you have removed the password. The P buttons are activated and deactivated via the “P ON/P OFF” menu option.

146

08/00 AWB2528-1304-GB

P

Page 150

Startup behaviour 왘 Press DEL and ALT to call up the System menu. 왘 Select the SYSTEM menu. 왘 Move to the “P ” menu option

DEBOUNCE OFF P

ON

STOP MODE

RETENTION ON

Activating the P buttons If “easy” is showing P OFF, this means that the P buttons are already active. 왘 Otherwise select “P ON” and press OK.

DEBOUNCE OFF

The P buttons are now active.

STOP MODE

P

OFF

왘 Press ESC to return to the RETENTION ON Status display. The P buttons are only active in the Status display. In this display you can use the P buttons to activate inputs in your circuit diagram.

Deactivating the P buttons 왘 Select “P OFF” and press OK.

08/00 AWB2528-1304-GB

Startup behaviour

The P buttons are now deactivated. The P buttons are automatically deactivated when loading a circuit diagram from the memory card or via EASY-SOFT to “easy”, or when deleting a circuit diagram in “easy”.

The startup behaviour is an important help during the commissioning phase. The circuit diagram which “easy” contains is not as yet fully wired up or the system or machine is in a state which “easy” is not

147

Page 151

“easy” Settings permitted to control. The outputs should not be controlled when “easy” is switched on.

Setting the startup behaviour The EASY...-..-..X models can only be started in Run mode. Requirement: “easy” must contain a valid circuit diagram. 왘 Switch to the System menu. If “easy” is protected by a password, the System menu will not be available until “easy” is unlocked (see the section Unlocking easy from page 136). 왘 Specify in which operating mode “easy” should start when the power supply is switched on (see the figure at the top of page 149). MODE: RUN/STOP is a toggle menu. The menu always displays the operating mode into which you can change.

148

08/00 AWB2528-1304-GB

The default setting for “easy” is for STOP MODE to be displayed. In other words, “easy” starts in Run mode when the power is switched on.

Page 152

Behaviour when the circuit diagram is deleted and PASSWORD... SYSTEM

GB D F E I..

DEBOUNCE OFF

DEBOUNCE OFF

STOP MODE

RUN MODE

P ON

RETENTION ON

Startup behaviour

P ON

RETENTION ON

Menu displayed

“easy” starts in Stop RUN MODE mode “easy” starts in Run mode

“easy” is in Stop mode “easy” is in Run mode

Behaviour when the circuit diagram is deleted

The setting for the startup behaviour is an “easy” device function. When the circuit diagram is deleted this does not result in the loss of the setting selected.

Behaviour during uploading and downloading to the card or PC

When a valid circuit diagram is transferred from “easy” to a memory card or the PC or vice versa, the setting is still retained.

08/00 AWB2528-1304-GB

STOP MODE

Status of “easy” after startup

Possible faults

The EASY...-..-..X models can only be started in Run mode.

“easy” will not start in Run mode “easy” does not contain a circuit diagram. You have selected MODE: STOP in the MODE RUN/STOP menu (the menu displayed is thus MODE: RUN). 149

Page 153

08/00 AWB2528-1304-GB

150