Page 154
8
Retention
It is a requirement of system and machine controllers for operating states or actual values to have retentive settings. What this means is that the values will be retained safely even after the supply voltage to a machine or system has been switched off and are also retained until the next time the actual value is overwritten.
Requirements
Permitted “easy” models Retentive actual values can be set with EASY412-D.-.. (via the SYSTEM menu) as well as EASY600 for the following markers and function relays. Permitted markers and function relays It is possible to retentively store (non-volatile memory) the actual values (status) of markers, timing relays and up/down counters. The following markers and function relays can be set to have retentive actual values: EASY412-D.-... Marker relays Timing relay Up/down counter
M13, M14, M15, M16 T8 C8
08/00 AWB2528-1304-GB
EASY600 Markers Text function relays Timing relays Up/down counters
M13, M14, M15, M16 D1 to D8 T7, T8 C5, C6, C7, C8
151
Page 155
Retention
The Retention setting always applies to all of the relays listed. Individual markers or function relays cannot be set retentively. The retentive data of EASY...-..-..X models with a fitted memory card is deleted when the power supply is switched on. Note The retentive data is kept every time the power supply is switched off. Data security is assured for 100 000 write cycles.
Setting retention
Requirement: In this case “easy” must be in Stop mode 왘 Switch to the System menu. If “easy” is protected by a password, the System menu will not be available until “easy” is unlocked (see chapter 7 from page 136). 왘 Switch on the Retention function (see figure on page 153 above). The menu item RETENTION ON/OFF is a toggle menu. The menu always displays the operating mode into which you can change.
152
08/00 AWB2528-1304-GB
The default setting of “easy” as it is supplied is the display RETENTION ON. With this setting “easy” runs without retentive actual value data, when a valid circuit diagram is present. When “easy” is in Stop mode or has been switched to a de-energized state, all actual values are cleared.
Page 156
Deleting retentive actual values and PASSWORD... SYSTEM
DEBOUNCE OFF
DEBOUNCE OFF
STOP MODE
RUN MODE
P ON
GB D F E I..
RETENTION ON
RETENTION
Retentive behaviour
Menu displayed
Behaviour: M13, M14, M15, M16, C8, T8, (D1 to D8, C5, C6, C7, T7) when the unit is switched off and on again
No retentive actual values
RETENTION ON
All actual values will be cleared when the unit changes from Run to Stop mode or when the power supply is switched off.
Retentive actual values
RETENTION
All actual values will be safely stored when the unit changes from Run to Stop mode or when the power supply is switched off. They can then be used or deleted.
Deleting retentive actual values
08/00 AWB2528-1304-GB
P ON
The retentive actual values are cleared if the following is fulfilled (applies only in Stop mode): When the circuit diagram is transferred from EASY-SOFT (PC) or from the memory card to “easy”, the retentive actual values are reset to 0 (marker = off). This also applies when there is no program on the memory card. In this case the old circuit diagram is retained in “easy”. When there is a changeover from retention activated (the display shows RETENTION OFF) to retention deactivated (the display shows RETENTION ON). When the circuit diagram is deleted via the DELETE PROG menu.
153
Page 157
Retention Transfer retentive behaviour
The setting for retentive behaviour is a circuit diagram setting; in other words, the setting of the retention menu may also under certain circumstances be transferred to the memory card or by uploading or downloading from the PC.
Circuit diagram transfer (behaviour) EASY-SOFT, V 1.0 ➞ EASY412-D.-.. When the circuit diagram is transferred (downloaded), the retentive behaviour must be set manually on the EASY412-DC... unit. In this version of the software, the relevant menu is not provided. EASY-SOFT, V 1.1 ➞ EASY412-D.-.. EASY-SOFT, V 1.1 does not support editing of the retentive behaviour. If an EASY412-DC.. circuit diagram with activated retention is loaded into EASY-SOFT, V 1.1, saved and then transferred back to the EASY412-DC.., the retentive behaviour setting will be retained. EASY412-D.-.. ➞ Memory card When transfer is in this direction, the actual values are retained in “easy”. The retention setting is transferred to the card. EASY412-D.-.. ➞ EASY-SOFT, V 1.0, V 1.1 The “easy” circuit diagram is stored. The actual values are retained in “easy”.
EASY-SOFT, V 2.* ➞ EASY412-D.-.., EASY600 The transfer to EASY-SOFT is carried out according to the relevant settings.
154
08/00 AWB2528-1304-GB
EASY412-D.-.., EASY600 ➞ EASY-SOFT, V 2.* The “easy” circuit diagram is stored. The actual values are retained in “easy”. All “easy” circuit diagram settings are transferred to the “EAS” file.
Page 158
Transfer retentive behaviour Changing the operating mode or the circuit diagram When the operating mode is changed or the “easy” circuit diagram is modified, the retentive data is normally saved together with their actual values. The actual values of relays no longer being used are also retained. Changing the operating mode If you change from Run to Stop and then back to Run, the actual values of the retentive data will be retained. Modifying the “easy” circuit diagram If a modification is made to the “easy” circuit diagram, the actual values will be retained. Note Even when the retentive relays M13, M14, M15, M16 (D1 to D8) and the function relays C8, T8 (C5, C6, C7, T7) are deleted from the circuit diagram, the retentive actual values will be retained after the changeover from Stop to Run as well as after the power supply is switched off and on. Should these relays be used again in the circuit diagram, they will still have their former actual values.
Changing the startup behaviour in the SYSTEM menu
08/00 AWB2528-1304-GB
The retentive actual values in “easy” will be retained irrespective of the MODE RUN or MODE STOP settings.
155
Page 159
Retention Retentive auxiliary relays (markers)
How the retention works The retentive markers M13, M14, M15, M16, D1 to D8 should be used in conjunction with the following coil functions. Set Impulse relay Reset
S M.., D.. äM.., D.. R M.., D..
Note When the condition for resetting the marker is fulfilled, the marker is reset. It is essential that you note the following points: Due to the operation of “easy” the make contact will remain closed and the break contact will remain open. If the Reset condition is active when the power supply is switched on, the state of the contact before power on will be retained for one cycle. This behaviour can result in a flicker effect in a lamp or a solenoid valve. Be sure to pay close attention to the example circuits for the individual coil functions. The following coil functions are not permitted: ÄM13 to ÄM16, ÄD1 to ÄD8
S/R coil (break contact) Task: In your application you need to remember whether a screw has been inserted or not. When your installation switches on, it is important that a screw which has already been screwed in place is not screwed in again - otherwise there could be permanent damage to the workpiece or the production line even shut down.
156
08/00 AWB2528-1304-GB
Examples
Page 160
Retentive auxiliary relays (markers) Contacts and relays used: I3 Q2 M8 M14 M9
Screw detected Blow pulse to transport screw Blow screw command Screw present (retentive) Workpiece transported away, Reset M14
Circuit diagram (part): M8um14----ÄQ2 hI3----SM14
M9-------RM14
Signal diagram: It is always the contact state “Make contact” which is displayed.
U
M8
Q2
I3
M9
08/00 AWB2528-1304-GB
M14
U = Supply voltage
The break contact of the retentive marker M14 is used. No enabling time is required for output Q2.
157
Page 161
Retention Impulse relay Task: After a power failure the lights in a stairwell should resume their previous switching state. Contacts and relays used: T2 I1 Q1 M15
Enable after first cycle Push-button actuator Lamp output Impulse relay (retentive)
Circuit diagram:
Parameter display:
---------TT2
X f g
M15-T2----ÄQ1
Ä sTRG dT2
I1-------äM15
S n00.10n yRES b +
Signal diagram: U
I1
M15
Q1
T2
U = Supply voltage
158 t t B
C
08/00 AWB2528-1304-GB t A