The text of a manual · part 20 of 28
User Manual EASY412, EASY600 Control Relay: 8 Retention, pages 162 to 169
Pages 162 to 169 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 162
Retentive auxiliary relays (markers) Range A: Q1 is switched on. The power supply is switched off. I1 is switched off. After the I1 is switched on, M15 is switched on and remains on. If the switching of I1 would switch off M15, the opposite would apply in the same way, and M15 would remain switched off. Range B: The power supply is switched off. I1 is switched on. After the switch on in the first “easy” cycle M15 is on. The fact that M15 and T2 are connected in series (enable time) prevents a flickering pulse on Q1.
08/00 AWB2528-1304-GB
Range C: M15 is switched on and remains set until the next time I1 switches on.
159
Page 163
Retention S/R function Task: After a power failure the lights in a stairwell should resume their previous switching state. Contacts and relays used: T2 I1 M1
Enable after first cycle Push-button actuator Push-button actuator pulse (rising edge detection) M2 Pulse limitation (one cycle) Q1 Lamp output M15 Impulse relay (retentive) Circuit diagram:
Parameter display:
---------TT2
X f g h------ÄM2
Ä sTRG dT2
I1um2----ÄM1 M1-m15----SM15
M1-M15----RM15
S n00.10n yRES b +
160
08/00 AWB2528-1304-GB
M15-T2----ÄQ1
Page 164
Retentive timing relay Signal diagram: U
I1
M1
M15
Q1
T2 t
U = Supply voltage
The circuit above functions in the same way as an impulse relay switch. The make contact will remain switched on in the first “easy” cycle if a coil is actuated by the make contact of a retentive marker (series and parallel connection both apply here too) and when the power is switched on, the reset condition for this retentive marker is on. The enable time T2 prevents Q1 from flickering.
08/00 AWB2528-1304-GB
Retentive timing relay
How the retention works The retentive timing relays T7, T8 can be operated retentively in all six different switching functions. The retention setting only makes sense under certain conditions for the switching functions. These can be subdivided into groups 1 and 2.
161
Page 165
Retention If these conditions are not fulfilled, the actual value will be cleared when the power is restored. If the R coil is actuated, the actual value will also be cleared. Group 1
On-delayed (example page 163) On-delayed switching with random range (example page 163) Single-pulse (example page 168)
Group 2
Flashing (example page 169) Off-delayed (example page 166) Off-delayed switching with random time range (example page 166)
Retention with group 1 Requirement: When the supply voltage is switched on, actuated trigger coils TT7, TT8 retain their “1” state (switched on) until the set time period has elapsed. This can be implemented using retentive markers or inputs connected to the power.
162
08/00 AWB2528-1304-GB
Retention with group 2 Requirement: When the supply voltage is switched on, actuated trigger coils TT7, TT8 retain their “0” state (switched off) until the set time period has elapsed. This can be implemented using retentive markers or inputs connected to the power.
Page 166
Retentive timing relay Examples
On-delayed, switching on-delayed with random range, retentive Task 1 (on-delayed): A drive motor must start up 30 seconds after the unit is first switched on. This task is implemented using the input which retains the 1 state on switch-on. Contacts and relays used: I1 Q2 T8
Switch on Motor Delay time
Circuit diagram:
Parameter display:
I1u------TT8
X f g
Ä sTRG dT8 hT8----ÄQ2
S n30.00n yRES b +
Signal diagram: U
I1
T8 t1 t2 t 1 + t 2 = 30 s
08/00 AWB2528-1304-GB
U = Supply voltage
I1 must be switched on when the voltage is switched back on.
163
Page 167
Retention
Task 2 A conveyor belt is to be run empty. This no-load running is implemented by using a timing relay to keep the belt running following the STOP BELT command until the preset time has elapsed. If this procedure is interrupted by an interruption to the power supply, the belt is only permitted to run empty after switch-on for the remainder of the preset time period. This task is implemented using retentive markers. Contacts and relays used: T6/T7 Single pulse timers I2 Start conveyor belt Q1 Conveyor belt motor I3 Stop conveyor belt M16 Stop selected T8 Remaining time Circuit diagram:
Parameters entered:
I2-------TT6
X f g
M16k
Ä sTRG dT8
T6u------SQ1 i3-------TT7
T7-------SM16 M16-------TT8 T8------uRQ1£
S n30.00n yRES b +
Setting T6, T7 ü Time: 00.00 s
I2 and I3 are converted to cycle pulses by T6 / T7. Only the pressing of the push-button actuators is
164
08/00 AWB2528-1304-GB hRM16
Page 168
Retentive timing relay recognized. Should they remain constantly depressed, malfunctions would ensue. In the above example T7 does not have to be retentive. Signal diagram: U
I2/T6
Q1
I3
M16
T8 t1 t2 t 1 + t 2 = 30 s
U = Supply voltage
08/00 AWB2528-1304-GB
The make contact of T8 closes for one “easy” cycle and resets M16, Q1.
165
Page 169
Retention Off-delayed, off-delayed switching with random time range, retentive Task: No-load running of a conveyor belt. Contacts and relays used: T6/T7 Single pulse timers I2 Start conveyor belt Q1 Conveyor belt motor I3 Stop conveyor belt M16 Stop selected T8 Remaining time Circuit diagram:
Parameters entered:
I2-------TT6
â f g
M16k
Ä sTRG dT8
T6uT8----SQ1 i3-------TT7
T7-------SM16 M16-------TT8 T8------uRQ1£
S n30.00n yRES b +
Setting T6, T7 ü Time: 00.00 s hRM16
166
In the above example T7 does not have to be retentive. 08/00 AWB2528-1304-GB
I2 and I3 are converted to cycle pulses by T6 / T7. Only the pressing of the push-button actuators is recognized. Should they remain constantly depressed, malfunctions would ensue.