Page 170

Retentive timing relay Signal diagram: U

I2/T6

Q1

I3

M16

T8 t1 t2 t 1 + t 2 = 30 s

08/00 AWB2528-1304-GB

U = Supply voltage

167

Page 171

Retention Single-pulse timing relays, retentive Single-pulse timing relays are suitable for metering adhesives, liquids etc. Task: A lubricating device is to dispense at all times a constant quantity of oil. Contacts and relays used: I1 Q1 T8

Start lubrication Oil valve Oil time

Circuit diagram:

Parameters entered:

I1-------TT8

ü

T8-------ÄQ1 f

S g n30.00n

Ä sTRG yRES dT8 b +

Signal diagram: U

I1

T8

Q1 t1 t2 A t B t 1 + t 2 = 30 s

Range A: In this case the power supply is interrupted. When the power supply is restored, the remaining pulse time runs on until finished. Range B: The time period runs down in this range without interruption. 168

08/00 AWB2528-1304-GB

U = Supply voltage

Page 172

Retentive timing relay Flashing switch operation, retentive Task: A flasher function is used to lower an ink stamp at identical time intervals to print an area and then to raise the stamp for areas where no printing is required. Contacts and relays used: Q1 T8

Valve Time

Circuit diagram:

Parameters entered:

---------TT8

Ü

T8-------ÄQ1 f

S g n10.00n

Ä sTRG yRES dT8 b +

Signal diagram: U

T8

Q1 t t1

A t2 t t1 + t2 = t

08/00 AWB2528-1304-GB

U = Supply voltage

Range A: In this case the power supply is interrupted. Following another switch-on, the remaining time runs on until finished.

169

Page 173

Retention Retentive Up/down counters C7, C8

How the retention works The actual value of counter C7, C8 is retentive. When the condition for resetting the counter is satisfied, the actual value of the counter will be reset. Examples Counting parts Task 1 Parts are packed automatically in a shipping carton. Even if there is a power outage the correct number should still be packed into the carton. When the carton is full, the carton is removed manually and the counter reset. Contacts and relays used: I5 I6 Q1 C8

Count parts Reset counter Stop parts, signal lamp Up counter

Circuit diagram: I5-------CC8 C8-------ÄQ1

I6-C8----RC8

Parameters entered: f0042g0036 sDIR n

Ä sCNT dC8 yRES b +

Signal diagram:

햲

햲

햲 The numerical value 36 is retained even after a power outage. U = Supply voltage

170

08/00 AWB2528-1304-GB

U

Page 174

Retentive Up/down counters C7, C8 Operating hours counter for maintenance intervals Task 2 Every 1000 hours the system or machine must be checked for possible defects. Filters and transmission oil must be changed and the bearings lubricated. Contacts and relays used: T8 M16 Q4 C8 I1

Clock pulse Block double pulse Warning light, 1000 h reached Up counter Reset

Circuit diagram:

Parameters entered:

---------TT8

Ü h------SM16

Ä

T8um16----CC8 t8-------RM16 C8-------ÄQ4

I1------uRC8 hRT8 f18:38g

M:Sn30.00n Ä sTRG yRES dT8 b + f1000g0107 sDIR n

Ä sCNT dC8

Ä yRES b +

Function of the “easy” circuit diagram:

08/00 AWB2528-1304-GB

T8 provides the clock pulse. When a time of t = 30 min. is selected the counting period amounts to 2 t = 60 min. Every hour one impulse is counted. The up counter C8 triggers a warning message at 1000 by means of Q4. For the clock pulse to be correct when there is a power outage, T8 must be retentive.

171

Page 175

Retention M16 prevents C8 from accidentally receiving a counter pulse when the power is switched back on if there was a power outage during the counting period. Both M16 and C8 must retain their actual values at power outage so that the 1000 hours of operating with interruptions in the power supply can be counted. I1 (for example, a key-operated switch) is used to reset the counter. Signal diagram: U

T8

M16

Q4

I1

A

U = Supply voltage

Range A: Value before power outage: 107 Value after power restored: 107

172

08/00 AWB2528-1304-GB

The timing relay T8 terminates the counting period after power is restored.

Page 176

Retentive Up/down counters C7, C8 Automatic lubrication at constant intervals and with a constant quantity of lubricant Task 3: 60 minutes after the last lubrication the bearings of a machine must be lubricated for 30 seconds. Contacts and relays used: T1 M15 Q1 T8 C8

Clock pulse Lubricate Valve Lubrication time Up counter

Circuit diagram:

Parameters entered:

---------TT1

Ü

C8-------SM15

Ä

T1-m15----CC8

M15------uTT8 hRC8

M15-t8----ÄQ1

S f g n00.50n sTRG yRES dTI b +

Parameter display:

T8-------RM15 f3600 g Ä Ä sDIR n yRES b + sCNT dC8

Parameters entered: X f g

Ä sTRG dT8

08/00 AWB2528-1304-GB

S n30.00n yRES b +

173

Page 177

Retention Function of the “easy” circuit diagram: T1 provides the clock pulse. When a time of t = 0.5 seconds is selected the counting period amounts to 2 t = 1 s. One impulse is counted every second. The up counter C8 switches on valve Q1 via M15 at 3600 counting pulses (3600 s = 1 h). M15 resets C8 and prepares C8 for the next hour. To stop C8 continuing to count, the break contact of M15 blocks the counting pulses. T8 is actuated by means of M15. Once T8 has timed out, M15 and T8 will be reset. In order that both the time elapsed since the last lubrication (counter C8) and also the lubrication pulse remains constant in the event of a power outage, C8, M15 and T8 must be retentive. Signal diagram: U

T1

C8

M15

Q1 t1

U = Supply voltage

174 t2 t 1 + t 2 = 30 s

08/00 AWB2528-1304-GB

T8