The text of a manual · part 21 of 28
User Manual EASY412, EASY600 Control Relay: 8 Retention, pages 170 to 177
Pages 170 to 177 of 228, from User Manual EASY412, EASY600 Control Relay
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moeller 621-DC-TCX
Page 170
Retentive timing relay Signal diagram: U
I2/T6
Q1
I3
M16
T8 t1 t2 t 1 + t 2 = 30 s
08/00 AWB2528-1304-GB
U = Supply voltage
167
Page 171
Retention Single-pulse timing relays, retentive Single-pulse timing relays are suitable for metering adhesives, liquids etc. Task: A lubricating device is to dispense at all times a constant quantity of oil. Contacts and relays used: I1 Q1 T8
Start lubrication Oil valve Oil time
Circuit diagram:
Parameters entered:
I1-------TT8
ü
T8-------ÄQ1 f
S g n30.00n
Ä sTRG yRES dT8 b +
Signal diagram: U
I1
T8
Q1 t1 t2 A t B t 1 + t 2 = 30 s
Range A: In this case the power supply is interrupted. When the power supply is restored, the remaining pulse time runs on until finished. Range B: The time period runs down in this range without interruption. 168
08/00 AWB2528-1304-GB
U = Supply voltage
Page 172
Retentive timing relay Flashing switch operation, retentive Task: A flasher function is used to lower an ink stamp at identical time intervals to print an area and then to raise the stamp for areas where no printing is required. Contacts and relays used: Q1 T8
Valve Time
Circuit diagram:
Parameters entered:
---------TT8
Ü
T8-------ÄQ1 f
S g n10.00n
Ä sTRG yRES dT8 b +
Signal diagram: U
T8
Q1 t t1
A t2 t t1 + t2 = t
08/00 AWB2528-1304-GB
U = Supply voltage
Range A: In this case the power supply is interrupted. Following another switch-on, the remaining time runs on until finished.
169
Page 173
Retention Retentive Up/down counters C7, C8
How the retention works The actual value of counter C7, C8 is retentive. When the condition for resetting the counter is satisfied, the actual value of the counter will be reset. Examples Counting parts Task 1 Parts are packed automatically in a shipping carton. Even if there is a power outage the correct number should still be packed into the carton. When the carton is full, the carton is removed manually and the counter reset. Contacts and relays used: I5 I6 Q1 C8
Count parts Reset counter Stop parts, signal lamp Up counter
Circuit diagram: I5-------CC8 C8-------ÄQ1
I6-C8----RC8
Parameters entered: f0042g0036 sDIR n
Ä sCNT dC8 yRES b +
Signal diagram:
햲
햲
햲 The numerical value 36 is retained even after a power outage. U = Supply voltage
170
08/00 AWB2528-1304-GB
U
Page 174
Retentive Up/down counters C7, C8 Operating hours counter for maintenance intervals Task 2 Every 1000 hours the system or machine must be checked for possible defects. Filters and transmission oil must be changed and the bearings lubricated. Contacts and relays used: T8 M16 Q4 C8 I1
Clock pulse Block double pulse Warning light, 1000 h reached Up counter Reset
Circuit diagram:
Parameters entered:
---------TT8
Ü h------SM16
Ä
T8um16----CC8 t8-------RM16 C8-------ÄQ4
I1------uRC8 hRT8 f18:38g
M:Sn30.00n Ä sTRG yRES dT8 b + f1000g0107 sDIR n
Ä sCNT dC8
Ä yRES b +
Function of the “easy” circuit diagram:
08/00 AWB2528-1304-GB
T8 provides the clock pulse. When a time of t = 30 min. is selected the counting period amounts to 2 t = 60 min. Every hour one impulse is counted. The up counter C8 triggers a warning message at 1000 by means of Q4. For the clock pulse to be correct when there is a power outage, T8 must be retentive.
171
Page 175
Retention M16 prevents C8 from accidentally receiving a counter pulse when the power is switched back on if there was a power outage during the counting period. Both M16 and C8 must retain their actual values at power outage so that the 1000 hours of operating with interruptions in the power supply can be counted. I1 (for example, a key-operated switch) is used to reset the counter. Signal diagram: U
T8
M16
Q4
I1
A
U = Supply voltage
Range A: Value before power outage: 107 Value after power restored: 107
172
08/00 AWB2528-1304-GB
The timing relay T8 terminates the counting period after power is restored.
Page 176
Retentive Up/down counters C7, C8 Automatic lubrication at constant intervals and with a constant quantity of lubricant Task 3: 60 minutes after the last lubrication the bearings of a machine must be lubricated for 30 seconds. Contacts and relays used: T1 M15 Q1 T8 C8
Clock pulse Lubricate Valve Lubrication time Up counter
Circuit diagram:
Parameters entered:
---------TT1
Ü
C8-------SM15
Ä
T1-m15----CC8
M15------uTT8 hRC8
M15-t8----ÄQ1
S f g n00.50n sTRG yRES dTI b +
Parameter display:
T8-------RM15 f3600 g Ä Ä sDIR n yRES b + sCNT dC8
Parameters entered: X f g
Ä sTRG dT8
08/00 AWB2528-1304-GB
S n30.00n yRES b +
173
Page 177
Retention Function of the “easy” circuit diagram: T1 provides the clock pulse. When a time of t = 0.5 seconds is selected the counting period amounts to 2 t = 1 s. One impulse is counted every second. The up counter C8 switches on valve Q1 via M15 at 3600 counting pulses (3600 s = 1 h). M15 resets C8 and prepares C8 for the next hour. To stop C8 continuing to count, the break contact of M15 blocks the counting pulses. T8 is actuated by means of M15. Once T8 has timed out, M15 and T8 will be reset. In order that both the time elapsed since the last lubrication (counter C8) and also the lubrication pulse remains constant in the event of a power outage, C8, M15 and T8 must be retentive. Signal diagram: U
T1
C8
M15
Q1 t1
U = Supply voltage
174 t2 t 1 + t 2 = 30 s
08/00 AWB2528-1304-GB
T8