“easy” circuit diagram cycle

Inside “easy”

In conventional control systems, a relay or contactor control processes all the circuit connections in parallel. The speed with which a contactor switches is thus dependent on the components used, and ranges from 15 to 40 ms for relay pick-up and dropout. With “easy” the circuit diagram is processed with a microprocessor that simulates the contacts and relays of the circuit concerned and thus processes all switching operations considerably faster. Depending on its size, the “easy” circuit diagram is processed cyclically every 4 to 40 ms. During this time, “easy” passes through five segments in succession. How “easy” evaluates the circuit diagram: Circuit conne ctions 1 2 3 4

08/00 AWB2528-1304-GB

..

Segment 1

2

3

4

5

I1-I4-Ö1-TT2 I2-I3----RT2 T2-u-----ÄQ1 P1-kêê êêê ...

I1-q1-j--ÄQ8

In the first three segments “easy” evaluates the contact fields in succession. As it does so, “easy” also checks whether contacts are connected in parallel or in series and stores the switching states of all the contact fields.

175

Page 179

Inside “easy” In the fourth segment, “easy” assigns the new switching states to all the coils in one pass. The fifth segment is outside the circuit diagram. “easy” uses this to “make contact” with the outside world: Output relays Q1 to Q.. are switched and inputs I1 to I.. are read once more. “easy” also copies all the new switching states to the status image register. “easy” only uses this status image for one cycle. This ensures that each circuit connection is evaluated with the same switching states for one cycle, even if the input signals I1 to I12 change their status several times within a cycle.

How does this affect the creation of the circuit diagram? “easy” evaluates the circuit diagram in these five segments in succession. You should therefore remember two points when you create your circuit diagrams:

176

08/00 AWB2528-1304-GB

The changeover of a relay coil does not change the switching state of an associated contact until the next cycle starts. Always wire forward or from top to bottom. Never work backwards.

Page 180

Determining the cycle time of “easy” circuit diagrams Example: Switching one cycle later This is the circuit diagram of a Circuit diagram: self-latching circuit. If I1 and I2 I1uI2----ÄQ1 are closed, the switching state of relay coil ÄQ1 is “latched” via Q1k contact Q1. 1st cycle: I1 and I2 are switched on. Coil ÄQ1 picks Start condition: I1, I2 switched on up. Q1 switched off. Contact Q1 remains switched off since “easy” evaluates from left to right. 2nd cycle: The self-latching function now becomes active. “easy” has transferred the coil states to contact Q1 at the end of the first cycle. Example: Do not wire backwards This example is shown in I1-Q4-i3o chapter 5. It was used in the z-----k section „Creating and modifying connections“ to hI2-I4-ÄQ2 illustrate how NOT to do it. In the third circuit connection, “easy” finds a connection to the second circuit connection in which the first contact field is empty. The output relay is not switched.

08/00 AWB2528-1304-GB

When wiring more than three contacts in series, use one of the marker relays.

Determining the cycle time of “easy” circuit diagrams

I1-Q4-i3-ÄM1

I2-I4-M1-ÄQ2

The maximum cycle time of a circuit diagram must be known in order to determine the maximum counter frequency or reaction time of “easy”.

177

Page 181

Inside “easy” EASY412 For EASY412 the cycle time can be calculated as follows: Basic pulse

Number Time duration

Total

1

–

210

Refresh

1

3500

–

Contacts and bridged contact fields

–

20

–

Coils

–

20

–

Circuit connections from the – first one to the last one, with empty ones in between

50

–

Connecting lines (only f,v,d)

–

20

–

Timing relays (see Table 1)

–

–

–

Counters (see Table 1)

–

–

–

Analog value function relays – (see Table 1)

–

–

Total

–

Table 1: List of times for processing function relays

178

1

2

3

4

Timing relays in s 20

40

80

120 160 200 240 280

5

6

7

8

Counters in s

20

50

90

130 170 210 260 310

Analog value processors in s

80

100 120 140 160 180 220 260

08/00 AWB2528-1304-GB

Number

Page 182

Determining the cycle time of “easy” circuit diagrams Example 1: parallel circuit Calculation of the maximum cycle time for the following circuit diagram:

Basic pulse

I3k

Number Time duration in s

Total

1

210

210

Refresh

1

3500

3500

Contacts and bridged contact fields

4

20

80

Coils

1

20

20

Circuit connections from the 2 first one to the last one, with empty ones in between

50

100

Connecting lines (only f,v,d)

–

20

–

Timing relays (see Table 1)

–

–

–

Counters (see Table 1)

–

–

–

Analog value function relays – (see Table 1)

–

–

Total

08/00 AWB2528-1304-GB

I2u------ÄQ4

3910

179

Page 183

Inside “easy” Example 2: Star/delta drive I1u------TT1 dt1----ÄQ1 dT1----TT2 hT2----ÄQ2

Number Time duration in s

Total

Basic pulse

1

210

210

Refresh

1

3500

3500

Contacts and bridged contact fields

9

20

180

Coils

4

20

80

Circuit connections from the 4 first one to the last one, with empty ones in between

50

200

Connecting lines (only f,v,d)

3

20

60

Timing relays (see Table 1)

2

40

40

Counters (see Table 1)

–

–

–

Analog value function relays – (see Table 1)

–

–

180

4270

08/00 AWB2528-1304-GB

Total

Page 184

Determining the cycle time of “easy” circuit diagrams Example 3: operating hours counter ---------TT8

T8um16----CC8 h------SM16 t8-------RM16 C8-------ÄQ4

I1------uRC8 hRT8

Number Time duration in s

Total

1

210

210

Refresh

1

3500

3500

Contacts and bridged contact fields

17

20

340

Coils

7

20

140

Circuit connections from the 7 first one to the last one, with empty ones in between

50

350

Connecting lines (only f,v,d)

2

20

40

Timing relays (see Table 1)

1

20

20

Counters (see Table 1)

1

20

20

Analog (see Table 1)

–

–

–

Basic pulse

08/00 AWB2528-1304-GB

Total

4620

181

Page 185

Inside “easy” EASY600 For EASY600 the cycle time can be calculated as follows:

Basic pulse

Number Time duration in s

Total

1

–

520

Refresh

–

5700

–

Contacts and bridged contact fields

–

40

–

Coils

–

20

–

Circuit connections from the – first one to the last one, with empty ones in between

70

–

Connecting lines (only f,v,d)

–

40

–

Timing relays (see Table 2)

–

–

–

Counters (see Table 2)

–

–

–

Analog value function relays – (see Table 2)

–

–

Total

–

Table 2: List of times for processing function relays

182

1

2

3

4

5

6

7

8

Timing relays in s 40

120 160 220 300 370 440 540

Counters in s

40

100 160 230 300 380 460 560

Analog value processors in s

120 180 220 260 300 360 420 500

08/00 AWB2528-1304-GB

Number

Page 186

Determining the cycle time of “easy” circuit diagrams Example: Operating hours counter ---------TT8

T8um16----CC8 h------SM16 t8-------RM16 C8-------ÄQ4

I1------uRC8 hRT8

Number Time duration in s Basic pulse

1

520

520

Refresh

–

5700

5700

Contacts and bridged contact fields

17

40

680

Coils

7

20

140

Circuit connections from the 7 first one to the last one, with empty ones in between

70

490

Connecting lines (only f,v,d)

2

40

180

Timing relays (see Table 2)

1

–

60

Counters (see Table 2)

1

–

40

Analog value function relays – (see Table 2)

–

–

Total

08/00 AWB2528-1304-GB

Total

7710