Page 178
9
“easy” circuit diagram cycle
Inside “easy”
In conventional control systems, a relay or contactor control processes all the circuit connections in parallel. The speed with which a contactor switches is thus dependent on the components used, and ranges from 15 to 40 ms for relay pick-up and dropout. With “easy” the circuit diagram is processed with a microprocessor that simulates the contacts and relays of the circuit concerned and thus processes all switching operations considerably faster. Depending on its size, the “easy” circuit diagram is processed cyclically every 4 to 40 ms. During this time, “easy” passes through five segments in succession. How “easy” evaluates the circuit diagram: Circuit conne ctions 1 2 3 4
08/00 AWB2528-1304-GB
..
Segment 1
2
3
4
5
I1-I4-Ö1-TT2 I2-I3----RT2 T2-u-----ÄQ1 P1-kêê êêê ...
I1-q1-j--ÄQ8
In the first three segments “easy” evaluates the contact fields in succession. As it does so, “easy” also checks whether contacts are connected in parallel or in series and stores the switching states of all the contact fields.
175
Page 179
Inside “easy” In the fourth segment, “easy” assigns the new switching states to all the coils in one pass. The fifth segment is outside the circuit diagram. “easy” uses this to “make contact” with the outside world: Output relays Q1 to Q.. are switched and inputs I1 to I.. are read once more. “easy” also copies all the new switching states to the status image register. “easy” only uses this status image for one cycle. This ensures that each circuit connection is evaluated with the same switching states for one cycle, even if the input signals I1 to I12 change their status several times within a cycle.
How does this affect the creation of the circuit diagram? “easy” evaluates the circuit diagram in these five segments in succession. You should therefore remember two points when you create your circuit diagrams:
176
08/00 AWB2528-1304-GB
The changeover of a relay coil does not change the switching state of an associated contact until the next cycle starts. Always wire forward or from top to bottom. Never work backwards.
Page 180
Determining the cycle time of “easy” circuit diagrams Example: Switching one cycle later This is the circuit diagram of a Circuit diagram: self-latching circuit. If I1 and I2 I1uI2----ÄQ1 are closed, the switching state of relay coil ÄQ1 is “latched” via Q1k contact Q1. 1st cycle: I1 and I2 are switched on. Coil ÄQ1 picks Start condition: I1, I2 switched on up. Q1 switched off. Contact Q1 remains switched off since “easy” evaluates from left to right. 2nd cycle: The self-latching function now becomes active. “easy” has transferred the coil states to contact Q1 at the end of the first cycle. Example: Do not wire backwards This example is shown in I1-Q4-i3o chapter 5. It was used in the z-----k section „Creating and modifying connections“ to hI2-I4-ÄQ2 illustrate how NOT to do it. In the third circuit connection, “easy” finds a connection to the second circuit connection in which the first contact field is empty. The output relay is not switched.
08/00 AWB2528-1304-GB
When wiring more than three contacts in series, use one of the marker relays.
Determining the cycle time of “easy” circuit diagrams
I1-Q4-i3-ÄM1
I2-I4-M1-ÄQ2
The maximum cycle time of a circuit diagram must be known in order to determine the maximum counter frequency or reaction time of “easy”.
177
Page 181
Inside “easy” EASY412 For EASY412 the cycle time can be calculated as follows: Basic pulse
Number Time duration
Total
1
–
210
Refresh
1
3500
–
Contacts and bridged contact fields
–
20
–
Coils
–
20
–
Circuit connections from the – first one to the last one, with empty ones in between
50
–
Connecting lines (only f,v,d)
–
20
–
Timing relays (see Table 1)
–
–
–
Counters (see Table 1)
–
–
–
Analog value function relays – (see Table 1)
–
–
Total
–
Table 1: List of times for processing function relays
178
1
2
3
4
Timing relays in s 20
40
80
120 160 200 240 280
5
6
7
8
Counters in s
20
50
90
130 170 210 260 310
Analog value processors in s
80
100 120 140 160 180 220 260
08/00 AWB2528-1304-GB
Number
Page 182
Determining the cycle time of “easy” circuit diagrams Example 1: parallel circuit Calculation of the maximum cycle time for the following circuit diagram:
Basic pulse
I3k
Number Time duration in s
Total
1
210
210
Refresh
1
3500
3500
Contacts and bridged contact fields
4
20
80
Coils
1
20
20
Circuit connections from the 2 first one to the last one, with empty ones in between
50
100
Connecting lines (only f,v,d)
–
20
–
Timing relays (see Table 1)
–
–
–
Counters (see Table 1)
–
–
–
Analog value function relays – (see Table 1)
–
–
Total
08/00 AWB2528-1304-GB
I2u------ÄQ4
3910
179
Page 183
Inside “easy” Example 2: Star/delta drive I1u------TT1 dt1----ÄQ1 dT1----TT2 hT2----ÄQ2
Number Time duration in s
Total
Basic pulse
1
210
210
Refresh
1
3500
3500
Contacts and bridged contact fields
9
20
180
Coils
4
20
80
Circuit connections from the 4 first one to the last one, with empty ones in between
50
200
Connecting lines (only f,v,d)
3
20
60
Timing relays (see Table 1)
2
40
40
Counters (see Table 1)
–
–
–
Analog value function relays – (see Table 1)
–
–
180
4270
08/00 AWB2528-1304-GB
Total
Page 184
Determining the cycle time of “easy” circuit diagrams Example 3: operating hours counter ---------TT8
T8um16----CC8 h------SM16 t8-------RM16 C8-------ÄQ4
I1------uRC8 hRT8
Number Time duration in s
Total
1
210
210
Refresh
1
3500
3500
Contacts and bridged contact fields
17
20
340
Coils
7
20
140
Circuit connections from the 7 first one to the last one, with empty ones in between
50
350
Connecting lines (only f,v,d)
2
20
40
Timing relays (see Table 1)
1
20
20
Counters (see Table 1)
1
20
20
Analog (see Table 1)
–
–
–
Basic pulse
08/00 AWB2528-1304-GB
Total
4620
181
Page 185
Inside “easy” EASY600 For EASY600 the cycle time can be calculated as follows:
Basic pulse
Number Time duration in s
Total
1
–
520
Refresh
–
5700
–
Contacts and bridged contact fields
–
40
–
Coils
–
20
–
Circuit connections from the – first one to the last one, with empty ones in between
70
–
Connecting lines (only f,v,d)
–
40
–
Timing relays (see Table 2)
–
–
–
Counters (see Table 2)
–
–
–
Analog value function relays – (see Table 2)
–
–
Total
–
Table 2: List of times for processing function relays
182
1
2
3
4
5
6
7
8
Timing relays in s 40
120 160 220 300 370 440 540
Counters in s
40
100 160 230 300 380 460 560
Analog value processors in s
120 180 220 260 300 360 420 500
08/00 AWB2528-1304-GB
Number
Page 186
Determining the cycle time of “easy” circuit diagrams Example: Operating hours counter ---------TT8
T8um16----CC8 h------SM16 t8-------RM16 C8-------ÄQ4
I1------uRC8 hRT8
Number Time duration in s Basic pulse
1
520
520
Refresh
–
5700
5700
Contacts and bridged contact fields
17
40
680
Coils
7
20
140
Circuit connections from the 7 first one to the last one, with empty ones in between
70
490
Connecting lines (only f,v,d)
2
40
180
Timing relays (see Table 2)
1
–
60
Counters (see Table 2)
1
–
40
Analog value function relays – (see Table 2)
–
–
Total
08/00 AWB2528-1304-GB
Total
7710
183