Page 187

Inside “easy” Delay times for inputs and outputs

The time from reading the inputs and outputs to switching contacts in the circuit diagram can be set in “easy” via the delay time.

S1

0V

I1

This function is useful, for example, in order to ensure a clean switching signal despite contact bounce. “easy”-DC, “easy”-DA and “easy”-AC units function with different input voltages and therefore also have different evaluation methods and delay times. Debounce delay times for “easy”-DC basic units“easy”-DA The debounce for DC signals is 20 ms. 1 S1 0 1 B

B 0

A

C

An input signal S1 must therefore be 15 V for at least 20 ms on the input terminal before the switch contact will change from 0 to 1 (A). If applicable, this time must also include the cycle time (B) since “easy” does not detect the signal until the start of a cycle.

184

08/00 AWB2528-1304-GB

The same debounce delay (C) applies when the signal drops out from 1 to 0.

Page 188

Delay times for inputs and outputs If the debounce is switched off, “easy” responds to an input signal after just 0.25 ms. 1 S1 0 1

B

B

0 A

C

Typical delay times with the debounce delay switched off are:

On-delay for I1 to I12: 0.25 ms Off-delay for I1 to I6 and I9 to I12: 0.4 ms I7 and I8: 0.2 ms Check that there is no interference affecting the input signals when the debounce delay is switched off. “easy” will respond even to very short signals. Debounce delay times for “easy”-AC basic units The input debounce with AC voltage signals depends on the frequency:

08/00 AWB2528-1304-GB

Switch-on delay 80 ms at 50 Hz, 66 ms at 60 Hz. Off-delay for I1 to I6 and I9 to I12: 80 ms (66 ms) I7 and I8: 160 ms (150 ms) with EASY412-AC I7 and I8: 80 ms (66 ms) with EASY6..-AC

185

Page 189

Inside “easy” The corresponding values for 60 Hz are given in brackets. S1 1

2

1

A

2

B

If the debounce delay is switched on, “easy” checks at 40 ms (33 ms) intervals whether there is a halfwave present at an input terminal (1st and 2nd pulses in A). If “easy” detects two pulses in succession, the device switches on the corresponding input internally. If this is not the case, the input is switched off again as soon as “easy” does not detect two successive half-waves (1st and 2nd pulses in B). S1 1

1

A

1

2

B

If a button or switch bounces (A), the delay time may be extended by 40 ms (33 ms) (A).

Switch-on delay 20 ms (16.6 ms) Off-delay for I1 to I6 and I9 to I12: 20 ms (16.6 ms) Off-delay I7 and I8: 100 ms (100 ms) with EASY412-AC.

186

08/00 AWB2528-1304-GB

If the debounce delay is switched off, the delay time is reduced.

Page 190

Monitoring for short-circuit/ Overload with EASY..-D.-T.. I7 and I8: 20 ms (16.6 ms) with EASY EASY6..-AC-RC(X) S1

Monitoring for shortcircuit/Overload with EASY..-D.-T..

1

1

A

B

“easy” switches the contact as soon as it detects a pulse (A). If no pulse is detected, “easy” switches off the contact (B). The procedure for changing the delay times is described in chapter 7 on page 145.

Depending on the type of “easy” in use, it is possible to use the internal inputs I15 and I16, R15, R16 to monitor for short-circuits or overloads on an output. EASY412-D.-T..: I16 = Group fault signal for outputs Q1 to Q4. EASY62 .-D.-T..: I16 = Group fault signal for outputs Q1 to Q4. I15 = Group fault signal for outputs Q5 to Q8. EASY620-D.-TE:

08/00 AWB2528-1304-GB

R16 = Group fault signal for outputs S1 to S4. R16 = Group fault signal for outputs S5 to S8. State of outputs

Status I15 or I16, R15 or R16

No fault found

0 = switched off (make contact)

At least one output has a fault

1 = switched on (make contact)

187

Page 191

Inside “easy” Transfer EASY-D.-T.. ➞ Memory card ➞ EASY..-..-R... I16 is added during transfer of the circuit diagram into “easy” from the memory card. I16 appears as I16 and the logical state remains 0 = switched off (make contact). If I16 is changed in any way, only I1 to I8 can be entered. I16 can be deleted with the DEL button. Transfer EASY-D.-T.. ➞ EASY-SOFT (PC) EASY-SOFT, Version 1.0, cannot process input I16. I16 is deleted during the transfer to EASY-SOFT. EASY-SOFT, Version 1.1, tolerates I16 without editing being possible. I16 is transferred when the circuit diagram is downloaded.

I16 should be evaluated in accordance with the individual application. I15, I16 can only be edited with “easy” versions which have transistor outputs. The following examples are for I16 = Q1 to Q4. I15 indicates in the same way short-circuits and overloads on Q5 to Q8. Example 1: Output with fault indication I1-m16----ÄQ1

I16-------SM16 êê êê êê êêê

188

08/00 AWB2528-1304-GB

êê êê êê êêê

The above circuit diagram functions as follows:

Page 192

Monitoring for short-circuit/ Overload with EASY..-D.-T.. If a transistor output reports a fault, M16 is set by I16. The break contact of M16 switches off output Q1. M16 can be cleared by resetting the “easy” power supply. Example 2: Output of operating state I1-m16----ÄQ1

I16-------SM16 M16-------ÄQ4 êê êê êê êêê

The above circuit functions as described in Example 1. An additional feature is that when an overload is detected the indicator light at Q4 is actuated. If Q4 has an overload, it would 'pulse'. Example 3: Automatic reset of error signal I1-m16----ÄQ1

I16-------SM16 M16-------TT8

T8-------RM16 M16-------ÄQ4

08/00 AWB2528-1304-GB

The above circuit diagram functions in the same way as Example 2. In addition the marker M16 is reset every 60 seconds by timing relay T8 (on-delayed, 60 s). Should I16 remain at 1, M16 will continue to be set. Q1 is set briefly to 1 until I16 switches off again.

189

Page 193

Inside “easy” Expanding EASY600

You can expand “easy” models EASY619/621-... locally using the expansion units EASY618-..-RE or EASY620-D.-TE or remotely – using the EASY200EASY coupling module. For this first install the units and connect the inputs and outputs (see chapter 3, Installation). Incorporate the inputs of the expansion units as contacts in the “easy” circuit diagram like the inputs in the basic unit. The input contacts possible are R1 to R12. R15, R16 are the group fault inputs of the transistor expansion unit (see also Monitoring Short-circuit/ Overload on page 187).

The outputs are processed as relay coils or contacts like the outputs in the basic unit. The output relays are S1 to S8. EASY618-..-RE provides the outputs S1 to S6. The other outputs S7, S8 can be used as markers.

How is an expansion unit recognised? When at least one R contact or S contact/coil is used in the circuit diagram, the basic unit assumes that an expansion unit is connected.

The input and output data of the expansion units is transferred serially in both directions. Take into account the modified reaction times of the inputs and outputs of the expansion units:

190

08/00 AWB2528-1304-GB

Transfer behaviour

Page 194

Expanding EASY600 Input and output reaction times of expansion units The debounce setting has no effect on the expansion unit. Transfer times for input and output signals: Local expansion Time for inputs R1 to R12: 30 ms + 1 cycle Time for outputs S1 to S6 (S8): 15 ms + 1 cycle time Remote expansion Time for inputs R1 to R12: 80 ms + 1 cycle Time for outputs S1 to S6 (S8): 40 ms + 1 cycle time

Function monitoring of expansion units If the power supply of the expansion unit is not present, no connection can be established between it and the basic unit. The expansion inputs R1 to R12, R15, R16 are incorrectly processed in the basic unit and show status 0. It cannot be assured that the outputs S1 to S8 are transferred to the expansion unit.

08/00 AWB2528-1304-GB

Warning Ensure the continuous monitoring of the “easy” expansion in order to prevent switching faults in machines or systems. The status of the internal input I14 of the basic unit indicates the status of the expansion unit: I14 = 0: I14 = 1:

Expansion unit is functional Expansion unit is not functional

191

Page 195

Inside “easy” Example Power can be applied to the expansion unit later than the basic unit. This therefore means that the basic unit is switched to Run with the expansion unit missing. The “easy” circuit diagram below detects if the expansion unit is operational or not. I14-m1----Ä:8 ---------SM1 I14--------Ä:8

I1uI2----ÄQ1 Q1k

As long as I14 is 1, the remaining circuit diagram is skipped. If I14 is 0, the circuit diagram is processed. If the expansion unit drops out for any reason, the circuit diagram is skipped. M1 detects whether the circuit diagram was processed for at least one cycle after the power supply is switched on. If the circuit diagram is skipped, all the outputs retain their previous state. The next example should be used if this is not desired. Example with LCD output and reset of the outputs I14-m1----Ä:1 ---------SM1 I14--------Ä:1

I2uI3----ÄQ1 Q1k

I14-------ÄD1 I14--------Ä:8

:8

192 hRQ1

08/00 AWB2528-1304-GB

:8------uÄD1