10

What Happens If ...?

You may sometimes find that “easy” does not do exactly what you expect. If this happens, read through the following notes which are intended to help you solve some of the problems you may encounter. You can use the power flow display in “easy” to check the logic operations in the “easy” circuit diagrams with reference to the switching states of contacts and relays.

08/00 AWB2528-1304-GB

Only qualified persons should test “easy” voltages while the device is in operation.

193

Page 197

What Happens If ...? Message from the “easy” system “easy” system Explanation messages on the LCD

Remedy

No display

Power supply interrupted

Switch on the power supply

“easy” LCD faulty

Replace “easy”

Self-test aborted

Replace “easy”

Memory card removed or not inserted correctly before saving

Insert memory card

Memory card faulty

Replace memory card

“easy” is faulty

Replace “easy”

“ERROR: EEPROM”

The memory for storing the retentive values or the “easy” circuit diagram memory is faulty.

Replace “easy”

“ERROR: CLOCK”

Clock error

Replace “easy”

“ERROR: LCD”

LCD is faulty

Replace “easy”

“ERROR: ACLOW”

Incorrect AC voltage

Test the voltage

“easy” is faulty

Replace “easy”

Continuous display “TEST: AC” “TEST: EEPROM” “TEST: DISPLAY” “ERROR: I2C”

194

08/00 AWB2528-1304-GB

“TEST: CLOCK”

Page 198

Possible situations when creating circuit diagrams Possible situations when creating circuit diagrams Possible situations when creating circuit diagrams Cannot enter contact or relay in circuit diagram Time switch switches at wrong times Cannot select analog comparator “Ax”

Explanation

Remedy

“easy” is in Run mode

Select Stop mode

Check time and parameters “easy” AC versions have no analog inputs Use “easy”-DC, “easy”DA for comparing analog values Cannot select time switch contacts “easy” has no clock Use “easy”-C versions for time switch functions When using a memory card “easy” “easy” memory card contains no circuit Change the version of will display the message “PROG Circuit diagram on the memory card uses “easy” or change the INVALID” circuit diagram on the contacts/relays that “easy” does not memory card – Use “easy”-C versions for time switch functions Current flow display does not show “easy” is in Stop mode Select Run mode changes to the circuit connections Operation / connection not performed Check the circuit diagram and parameter Relay does not activate coil sets and modify as Incorrect parameter values / time required – Analog value comparison is incorrect – Time value of timing relay is incorrect – Function of timing relay is incorrect Relay coil has been wired up several times Check coil field entries Relay Q or M does not pick up Input not detected Loose terminal contact Check installation instructions, check No voltage to switch/button external wiring Broken wire

08/00 AWB2528-1304-GB

Incorrect time or time switch parameters

“easy” input is faulty Relay output Q does not switch and “easy” in Stop mode activate the load No voltage at relay contact “easy” power supply interrupted “easy” circuit diagram does not activate relay output Broken wire “easy” relay is faulty

Replace “easy” Select Run mode Check installation instructions, check external wiring

Replace “easy”

195

Page 199

What Happens If ...? Event Event

Explanation

Remedy

The actual values are not being stored retentively.

Retention has not been switched Switch on retention in the on. SYSTEM menu. EASY412-AC.. does not recognize Use EASY412-D. the function. EASY412-DC.. does not recognize the function.

Use EASY412-D with retention

The “easy” circuit diagram has been loaded with an EASY-SOFT version which does not support the function.

Switch on retention in the SYSTEM menu.

The RETENTION ON/OFF menu is This “easy” model does not have Use EASY412-D. not displayed in the SYSTEM menu. this function. “easy” is in Run mode

Stop mode

“easy” starts only in operating mode STOP

No circuit diagram in “easy”

Load, input circuit diagram

Startup behaviour is set to the function "Startup in operating mode STOP".

Set the startup behaviour in the SYSTEM menu.

LCD display showing nothing

EASY412, EASY600 No power supply

Switch on the power supply

“easy” is faulty

Press the cursor OK button. If no menu appears, replace the “easy”.

EASY600 Text displayed with too many spaces

Enter text or do not select

196

08/00 AWB2528-1304-GB

The SYSTEM menu is not displayed. This “easy” model does not have Exchange “easy” if you need this menu. retention