Page 200
11
General
Technical Data
EASY... EASY200-EASY
EASY412
EASY600
[mm]
35.5 90 53
71.5 90 53
107.5 90 53
[inches]
1.4 3.54 2.08
2.81 3.54 2.08
4.23 3.54 2.08
Space units
2 space units wide
4 SU (space units) wide
6 SU (space units) wide
[g]
70
200
300
[lb]
0.154
0.441
0.661
Dimensions W H D
Weight
Mounting
DIN 50 022, 35 mm rail or screw mounting with 3 ZB-101-GF1 mounting feet (accessories); with EASY200-EASY only 2 mounting feet required.
08/00 AWB2528-1304-GB
45
110
90
4.5
M4 7.5 35.5
102
7.5
47.5 56.5 58
Figure 2: Dimensions of EASY200-EASY in mm (for dimensions in inches see Table 3)
197
Page 201
Technical Data
45
110
90
50
102
10.75
4.5
M4
47.5
35.75 71.5
56.5 58
198
08/00 AWB2528-1304-GB
Figure 3: EASY412-... dimensions in mm (for dimensions in inches see Table 3)
Page 202
General 16.25
75
16.25
45
110
90
102
M4
4.5 47.5
107.5
56.5 58
Figure 4: EASY600 dimensions in mm (for dimensions in inches see Table 3)
08/00 AWB2528-1304-GB
Table 3: Dimensions in inches mm inches mm inches
4.5
0.177
56.5
2.22
7.5
0.295
58
2.28
10.75
4.23
71.5
2.81
16.25
0.64
75
2.95
35.5
1.4
90
3.54
35.75
1.41
102
4.01
45
1.77
107.5
4.23
47.5
1.87
110
4.33
50
1.97
199
Page 203
Technical Data Ambient climatic conditions (Cold to IEC 60 068-2-1, Heat to IEC 60 068-2-2) Ambient temperature Installed horizontally/vertically
–25 to 55 °C, –13 to 131 °F
Condensation
Prevent condensation with suitable measures
LCD display (reliably legible)
0 to 55 °C, 32 to 131 °F
Storage/transport temperature
–40 to +70 °C, –40 to 158 °F
Relative humidity (IEC 60 068-2-30)
5 to 95 %, non-condensing
Air pressure (operation)
795 to 1080 hPa
Corrosion resistance IEC 60 068-2-42
SO2 10 cm3/m3, 4 days
IEC 60 068-2-43
H2S 1 cm3/m3, 4 days
Ambient mechanical conditions Pollution degree
2
Degree of protection (EN 50 178, IEC 60 529, VBG4)
IP 20
Oscillations (IEC 60 068-2-6)
10 to 57 Hz (constant amplitude 0.15 mm) 57 to 150 Hz (constant acceleration 2 g)
Shock (IEC 60 068-2-27)
18 shocks (semi-sinusoidal 15 g/11 ms)
Drop (IEC 60 068-2-31)
Drop height 50 mm
Free fall, when packed (IEC 60 068-2-32)
1m
Electrostatic discharge (ESD), (IEC/EN 61 000-4-2, severity level 3)
8 kV air discharge, 6 kV contact discharge
Electromagnetic fields (RFI), (IEC/EN 61 000-4-3)
Field strength 10 V/m
Radio interference suppression (EN 55 011, EN 55 022)
Class B
Burst (IEC/EN 61 000-4-4, severity level 3)
2 kV power cables, 2 kV signal cables
High-energy pulses (surge) “easy”-AC (IEC/EN 61 000-4-5)
2 kV power cable symmetrical
High-energy pulses (surge) “easy”-DC (IEC/EN 61 000-4-5, severity level 2)
0.5 kV power cable symmetrical
Line-conducted interference (IEC/EN 61 000-4-6)
10 V
200
08/00 AWB2528-1304-GB
Electromagnetic compatibility (EMC)
Page 204
General Dielectric strength Measurement of the air clearance and creepage distance
EN 50 178, UL 508, CSA C22.2, No 142
Dielectric strength
EN 50 178
Tools and cable cross-sections Solid min. 0.2 mm2, max. 4 mm2/AWG: 22 – 12
Flexible with ferrule min. 0.2 mm2, max. 2.5 mm2/ AWG: 22 – 12 Factory wiring: up to AWG 30
Slot-head screwdriver, width
3.5 0.8 mm, 0.14
Tightening torque
0.6 Nm
Backup/accuracy of real-time clock (only with “easy”-C) Clock battery back-up at 25 °C/77 °F
Normally 64 h at 40 °C/104 °F
Normally 24 h
Accuracy of the real-time clock
Normally - 5 s/day, ~ - 0.5 h/year
Repetition accuracy of timing relays Accuracy of timing relays
- 1 % of value
Resolution Range “s”
10 ms
Range “M:S”
1s
Range “H:M”
1 min.
Retentive memory Write cycles of the retentive memory
100 000
08/00 AWB2528-1304-GB
Circuit connections (basic units) EASY412
41
EASY600
121
201
Page 205
Technical Data Power supply
EASY412-AC-..., EASY61.-AC-R.. EASY412-AC-...
EASY61.-AC-R..
Rated value (sinusoidal)
115/120/230/240 V AC
100/110/115/120/230/240 V AC
+10/–15 % 90 to 264 V AC
+10/–15 % 85 to 264 V AC
50/60 Hz, - 5 %
50/60 Hz, - 5 % at 115/120 V AC 60 Hz
Normally 40 mA
Normally 70 mA at 230/240 V AC 50 Hz
Normally 20 mA
Normally 35 mA
20 ms, EN 61131-2
20 ms, EN 61131-2 at 115/120 V AC
Normally 5 VA
Normally 10 VA at 230/240 V AC
Normally 5 VA
Normally 10 VA
Operating range Frequency, rated value, tolerance Input current consumption
Voltage dips Power loss
EASY412-DA-..., EASY412-DC-..., EASY61.-DC-R.., EASY62.-DC-T.. EASY412-DA-...
EASY412-DC-...
EASY61.-DC-R.., EASY62.-DC-T..
12 V DC, +30 %, –15 %
24 V DC, +20 %, –15 %
Rated value Permissible range
10.2 to 15.6 V DC
20.4 to 28.8
20.4 to 28.8
Residual ripple
-5%
Input current at 24 V DC (with EASY412-DA-... 12 V DC)
Normally 140 mA
Normally 80 mA
Normally 140 mA
Voltage dips
10 ms, EN 61131-2
Power dissipation at 24 V DC (with EASY412-DA-... 12 V DC)
Normally 2 W
Normally 2 W
Normally 3,5 W
202
08/00 AWB2528-1304-GB
Rated voltage
Page 206
Inputs Inputs
EASY-412-AC-..., EASY61.-AC-R.. EASY-412-AC-...
EASY61.-AC-R..
Digital inputs 115/230 V AC Number
8
12
Status display
LCD (if provided)
LCD (if provided)
To power supply
No
No
Between each other
No
No
To the outputs
Yes
Yes
0 to 40 V AC
0 to 40 V AC
Electrical isolation
Rated voltage L (sinusoidal) 0 signal
79 to 264 V AC
79 to 264 V AC
Rated frequency
1 signal
50/60 Hz
50/60 Hz
Input current with 1 signal R1 to R12, I1 to I6 (EASY61. also I9 to I12)
6 0.5 mA at 230 V AC 50 Hz, 10 (12) 0.5 mA at 230 V AC, 6 0.25 mA at 115 V AC 60 Hz 50 Hz 10 0.25 mA at 115 V AC, 60 Hz
Input current on 1 signal I7, I8
2 6 mA at 230 V AC 50 Hz, 2 4 mA at 115 V AC 60 Hz
2 6 mA at 230 V AC 50 Hz, 2 4 mA at 115 V AC 60 Hz
Delay time for 0 to 1 and 1 to 0 for I1 to I6, I9 to I12 Debounce ON
80 ms (50 Hz), 66n ms (60 Hz) 80 ms (50 Hz), 66n ms (60 Hz)
Debounce OFF (also R1 to R12)
20 ms (50 Hz), 16n ms (60 Hz) 20 ms (50 Hz), 16n ms (60 Hz)
Delay time I7, I8 for 1 to 0 Debounce ON
160 ms (50 Hz), 150 ms (60 Hz) 80 ms (50 Hz),66n ms (60 Hz)
Debounce OFF
100 ms (50 Hz/60 Hz)
20 ms (50 Hz), 16n ms (60 Hz)
Delay time I7, I8 for 0 to 1 Debounce ON
80 ms (50 Hz), 66n ms (60 Hz) 80 ms (50 Hz), 66n ms (60 Hz)
Debounce OFF
20 ms (50 Hz), 16n ms (60 Hz) 20 ms (50 Hz), 16n ms (60 Hz)
08/00 AWB2528-1304-GB
Max. permissible cable length (per input) I1 to I6, R1 to R12 (with EASY61. also I9 to I12)
Normally 40 m
Normally 40 m
I7, I8
Normally 100 m
Normally 100 m
203
Page 207
Technical Data EASY412-DA-..., EASY412-DC-..., EASY6..-DC-... EASY412-DA-...
EASY412-DC-...
EASY6..-DC-...
8
8
12
Digital inputs Number
2 inputs (I7, I8) usable as analog inputs Status display
LCD (if provided)
Electrical isolation To power supply
No
No
No
Between each other
No
No
No
To the outputs
Yes
Yes
Yes
Rated value
12 V DC
24 V DC
24 V DC
0 signal
4 V DC (I1 to I8)
5 V DC (I1 to I8)
5 V DC (I1 to I12, R1 to R12)
1 signal
8 V DC (I1 to I8)
8 V DC (I7, I8)
8 V DC (I7, I8)
Rated voltage
15 V DC (I1 to I6)
15 V DC (I1 to I6, I9 to I12, R1 to R12)
3.3 mA at 12 V DC (I1 to I6)
3.3 mA at 24 V DC (I1 to I6, R1 to R12)
3.3 mA at 24 V DC (I1 to I6, I9 to I12, R1 to R12)
1.1 mA at 12 V DC
2.2 mA at 24 V DC
2.2 mA at 24 V DC
Debounce ON
20 ms
20 ms
20 ms
Debounce OFF
Normally 0.3 ms (I1 to I6)
Normally 0.25 ms (I1 to I12)
Debounce ON
20 ms
20 ms
Debounce OFF (with EASY412-DC-... and EASY6..-DC-... also R1 to R12)
Normally 0.3 ms (I1 Normally 0.4 ms (I1 Normally 0.4 ms to I6) to I6) (I1 to I6, I9 to I12) Normally 0.15 ms (I7, Normally 0.2 ms (I7, Normally 0.2 ms (I7,
Input current on 1 signal
I7, I8 Delay time for 0 to 1
Delay time for 1 to 0
204
100 m
100 m
100 m
08/00 AWB2528-1304-GB
Cable length (unshielded)
20 ms