Page 208
Inputs EASY412-D.-...
EASY6..-DC-...
2
2
To power supply
No
No
To the digital inputs
No
No
Analog inputs Number Electrical isolation
Yes
Yes
Input type
To the outputs
DC voltage
DC voltage
Signal range
0 to 10 V DC
0 to 10 V DC
Resolution analog
0.1 V
0.1 V
Resolution digital
0.1
0.1
U[V] 9.9
5.0
0
Input impedance
5.0
9.9
11.2
11.2
Two “easy” devices
- 3% of actual value
- 3% of actual value within a single device
- 2 % of actual value (I7, I8), - 0.12 V
Accuracy of
08/00 AWB2528-1304-GB
Conversion time, analog/digital
Debounce ON: 20 ms Debounce OFF: Each cycle time
Input current
1 mA
1 mA
Cable length (shielded)
30 m
30 m
205
Page 209
Technical Data Relay outputs
EASY412-...-R..., EASY618/619... EASY412-...-R...
EASY618/619...
4
6
Type of outputs
Relay
Relay
In groups of
1
1
Connection of outputs in parallel to increase the output
Not permissible
Not permissible
Protection for an output relay
Miniature circuit-breaker B16 or 8 A fuse (slow)
Potential isolation to mains supply, inputs
Yes 300 V AC (safe isolation) 600 V AC (basic isolation)
Yes 300 V AC (safe isolation) 600 V AC (basic isolation)
Mechanical lifespan (switching cycles)
10 106
10 106
8 A (10 A UL)
8 A (10 A UL)
Number
Contacts relays Conventional thermal current Recommended for load
500 mA, 12 V AC/DC
500 mA, 12 V AC/DC
Protected against short-circuit cos = 1
16 A characteristic B (B16) at 600 A
Protected against short-circuit cos = 0.5 to 0.7
16 A characteristic B (B16) at 900 A
Rated impulse withstand voltage Uimp contact coil
6 kV
6 kV
Rated insulation voltage Ui Rated operational voltage Ue
250 V AC
250 V AC
Safe isolation to EN 50 178 between coil and contact
300 V AC
300 V AC
Safe isolation to EN 50 178 between two contacts
300 V AC
300 V AC
AC-15 250 V AC, 3 A (600 Ops/h)
300 000 switching operations
300 000 switching operations
DC-13 L/R 150 ms 24 V DC, 1 A (500 Ops/h)
200 000 switching operations
200 000 switching operations
AC-15 250 V AC, 3 A (600 Ops/h)
300 000 switching operations
300 000 switching operations
DC-13 L/R 150 ms 24 V DC, 1 A (500 Ops/h)
200 000 switching operations
200 000 switching operations
Breaking capacity
206
08/00 AWB2528-1304-GB
Making capacity
Page 210
Relay outputs EASY412-...-R... Filament lamp load
EASY618/619...
1000 W at 230/240 V AC/25 000 operations 500 W at 115/120 V AC/25 000 operations
Fluorescent tube with ballast
10 58 W at 230/240 V AC/25 000 operations
Conventional fluorescent tube, compensated
1 58 W at 230/240 V AC/25 000 operations
Fluorescent tube, uncompensated
10 58 W at 230/240 V AC/25 000 operations
Operating frequency, relays Mechanical switching operations
10 million (107)
10 million (107)
Mechanical switching frequency
10 Hz
10 Hz
Resistive lamp load
2 Hz
2 Hz
Inductive load
0.5 Hz
0.5 Hz
UL/CSA Uninterrupted current at 240 V AC/24 V DC
10/8 A
AC
Control Circuit Rating Codes (Utilization category)
B300 Light Pilot Duty
Max. rated operational voltage
300 V AC
Max. thermal uninterrupted current cos = 1 at B300
5A
Maximum make/break capacity cos ≠ 1 (Make/break) at B300
3600/360 VA
Control Circuit Rating Codes (Utilization category)
R300 Light Pilot Duty
Max. rated operational voltage
300 V DC
Max. thermal uninterrupted current at R300
1A
DC
08/00 AWB2528-1304-GB
Maximum make/break capacity at 28/28 VA R300
207
Page 211
Technical Data
Number of outputs Contacts Rated voltage Ue Permissible range Residual ripple Supply current 0 signal 1 signal Reverse polarity protection
EASY-412-D.-T..., EASY62... EASY412-D.-T... 4 Semiconductors 24 V DC 20.4 to 28.8 V DC
EASY62... 8 Semiconductors 24 V DC 20.4 to 28.8 V DC
Normally 9 mA, max. 16 mA Normally 18 mA, max. 32 mA Normally 12 mA, max. 22 mA Normally 24 mA, max. 44 mA Yes, caution! If voltage is applied to the outputs when the polarity of the power supply is reversed, this will result in a short circuit. Potential isolation to mains supply, inputs Yes Yes Rated current Ie for 1 signal max. 0.5 A DC max. 0.5 A DC Lamp load 5 watts without RV 5 watts without RV Residual current at state “0” per channel 0.1 mA 0.1 mA Max. output voltage 0 signal with ext. load 10 2.5 V 2.5 V 1 when Ie = 0.5 A U = Ue–1 V U = Ue–1 V Short-circuit protection Yes, thermal (detected via diagnostics input I16, I15; R15;R16) 0.7 A Ie 2 A (depending on number of active channels Short-circuit tripping current for and their load) Ra 10 Max. total short-circuit current 8A 16 A Peak short-circuit current 16 A 32 A Thermal cutout Yes Yes Maximum switching frequency with 40 000 (depends on circuit diagram and load) constant resistive load RL 100 : switching operations pro hour Group 1: Q1 to Q4 Group 1: Parallel connection of outputs with Q1 to Q4, S1 to S4 resistive load; inductive load with external Group 2: suppression circuit (see page 43) Q5 to Q8, S5 to S8 combination within a group Number of outputs max. 4 max. 4 Total maximum current 2.0 A, caution! Outputs must be actuated simultaneously and for the same time duration. Status display of the outputs LCD display (if provided)
208
08/00 AWB2528-1304-GB
Transistor outputs
Page 212
Transistor outputs Inductive load (without external suppressor circuit) General explanations: T0.95 = time in msec. until 95 % of the stationary current is reached T0.95 ≈ = --L R Utilization category Q1 to Q4 T0.95 = 1 ms R = 48 L = 16 mH
DC13 T0.95 = 72 ms R = 48 L = 1.15 H
Utilization factor g = 0.25
Rel. duty factor
100%
Max. switching frequency Max. duty factor => switching cycles per hour f = 0.5 Hz DF = 50 % 1500
Utilization factor g = 0.25
Rel. duty factor
100%
Max. switching frequency Max. duty factor => switching cycles per hour f = 0.5 Hz DF = 50 % 1500
Other inductive loads: T0.95 = 15 ms R = 48 L = 0.24 H
Utilization factor g = 0.25
Rel. duty factor
100%
Max. switching frequency Max. duty factor => switching cycles per hour f = 0.5 Hz DF = 50 % 1500
08/00 AWB2528-1304-GB
Inductive load with external suppressor circuit for each load (see section “Connecting transistor outputs” on page 41) Utilization factor g=1
Rel. duty factor
100%
Max. switching frequency Max. duty factor => switching cycles per hour
Depends on the suppressor circuit
209
Page 213
Technical Data Cycle time
EASY412-... Number Time duration in s Basic pulse
1
210
Refresh
1
3500
Contacts and bridged contact fields
22, 23
Coils
22, 23
Circuit connections from the first one to the last one, with empty ones in between
50
Connecting lines (only f,v,d)
22, 23
Timing relays (see Table 4)
–
Counters (see Table 4)
–
Analog value function relays (see Table 4)
–
Total
Total Table 4: List of times for processing function relays 1
2
3
4
Timing relays in s 22,
40
80
120 160 200 240 280
Counters in s
50
90
130 170 210 260 310
22,
Analog value 80 comparators in s
210
5
6
7
8
100 120 140 160 180 220 260
08/00 AWB2528-1304-GB
Number
Page 214
Cycle time EASY600 Number Time duration in s Basic pulse
1
Total
520
Refresh
5700
Contacts and bridged contact fields
40
Coils
22, 23
Circuit connections from the first one to the last one, with empty ones in between
70
Connecting lines (only f,v,d)
40
Timing relays (see Table 5)
–
Counters (see Table 5)
–
Analog value function relays (see Table 5)
–
Total Table 5: List of times for processing function relays Number
1
2
3
4
5
6
7
8
Timing relays in s 40
120 160 220 300 370 440 540
Counters in s
100 160 230 300 380 460 560
40
08/00 AWB2528-1304-GB
Analog value 120 180 220 260 300 360 420 500 comparators in s
211
Page 215
08/00 AWB2528-1304-GB
212