The text of a manual · part 2 of 8
Model 325 URICA Universal Remote Interface for Control & Acquisition User's Manual, pages 11 to 20
Pages 11 to 20 of 74
The original document is the PDF (1.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Moore URICA Model 325
Page 11
UM325-1 INTRODUCTION the TIC representative taking the call to use the central customer database to quickly identify the caller’s location and past support needs.
e Product part number or model number and version e If there is a problem with product’s operation: - Is problem intermittent - The steps performed before the problem occurred - Any error messages displayed - Installation environment
October 1995 1-3
Page 12
INTRODUCTION UM325-!
1-4 October 1995
Page 13
UM325-1 INSTALLATION
2. INSTALLATION
This Section describes installation of a Model 325 Universal Remote Interface for Control & Acquisition (URICA™). Topics include: handling and storage, installation considerations, and mechanical and electrical installation.
IMPORTANT
The installation must conform to the National Electrical Code and all other applicable construction and electrical codes.
2.1 EQUIPMENT DELIVERY AND HANDLING
2.1.1 Factory Shipment
Prior to shipment, URICA is fully tested and inspected to ensure proper operation. It is then packaged for shipment.
2.1.2 Receipt of Shipment
Each carton should be inspected at the time of delivery for possible external damage. Any visible damage should be immediately recorded on the carrier's copy of the delivery slip.
Each carton should be carefully unpacked and its contents checked against the enclosed packing list. At the same time, each item should be inspected for possible previously hidden damage that may or may not have been accompanied by exterior carton damage.
If it is found that some items have been damaged or are missing, notify Moore Products Co. immediately and provide full details. In addition, damages must be reported to the carrier with a request for their on-site inspection of the damaged item and its shipping carton.
2.1.3 Storage
If the unit is to be stored for a period prior to installation, review the environmental specifications in Section 6.3.
2.1.4 Return Shipment
Call the Service Department at (215) 646-7400, ext 4RMA (4762) weekdays between 8:00 a.m. and 4:45 p.m. Eastern Time to obtain an RMA (Return Material Authorization} number. Mark the RMA number prominently on the outside of the return shipment.
When calling for an RMA number, provide the reason for the return. If returning equipment for repair, failure information (e.g. error code, failure symptom, installation environment) will be requested. A purchase order number will be requested.
October 1995 2-1
Page 14
INSTALLATION UM325-1
MATERIAL SAFETY DATA SHEET
A Material Safety Data Sheet (MSDS) must be included with each item being returned that was stored or used anywhere hazardous materials were present.
PACKAGING
Package assembly in original shipping materials. Otherwise, package it for safe shipment or contact the factory for shipping recommendations.
2.2 ENVIRONMENTAL CONSIDERATIONS
Many industrial processes create severe environmental conditions. The conditions at each URICA location must be within the specifications stated in Section 6.3.4.
The Model 325 URICA is designed to perform in industrial environments; however, it is prudent to locate the unit to minimize the effects of heat, vibration, shock, and electrical interference.
CAUTION
Exceeding the specified operating temperature limits can adversely affect performance and may cause damage.
2.3 INSTALLATION
Section 2.3.1 outlines basic considerations to achieve a successful installation. Sections 2.3.2 and 2.3.3 describe the mechanical and electrical installation.
2.3.1 Installation Considerations
The steps necessary to install URICA are summarized below.
e Determine hardware configuration by selecting the MODBUS address, interface standard, baud rate, data format and other communications related characteristics. Set hardware configuration switches. See Section 3.
e URICA communicates with devices on the HART bus and with a user's control system (computer) or modem. Switches within URICA must be set to establish communications and Section 6.2 lists accessories used when RS232C interface standard is selected.
e Select mounting location; observe environmental requirements. See section 2.2.
¢ Mechanically install URICA. See Section 2.3.2 e Electrically install URICA and selected accessories. See sections 2.3.3.
2-2 October 1995
Page 15
UM325-1 INSTALLATION
Typical! URICA mounting locations are:
e A vibration-free instrument panel e A NEMA 4 enclosure e The desk or cabinet with the user's computer or modem
The location should be indoors or sheltered from the weather. Refer to Section 6.3 for URICA operating temperature limits and operating humidity range. Note that the air surrounding an operating the unit must be kept below 75°C (167°F).
Industrial environments often contain particulate, liquid, and gaseous contaminants. Particulate matter, usually dust and dirt, is abrasive and can cause intermittent contact in connectors associated with circuit subassemblies. A layer of dust on circuit boards can have a corrosive effect on metal, rubber, plastic, and circuit board components. Extended exposure to these contaminants may result in equipment malfunctions.
To reduce contaminant related to equipment malfunctions:
e Identify contaminants and implement methods to reduce their presence.
e When cleaning equipment and surrounding areas, especially the floor, either vacuum away all dust and dirt or use a dampened rag or mop. Sweeping or dry dusting recirculates dust and dirt.
e Clean or replace all air conditioning filters, room air filters, and equipment filters regularly. e Inform all personnel with access to the equipment of the need for cleanliness.
2.3.2 Mechanical Installation
This section describes mechanical installation of URICA. The unit can be mounted in any orientation, preferably so the faceplate LEDs can be viewed. Allow sufficient clearance for wiring the screw terminals and for cover removal to set the internal communication switches.
2.3.2.1 Mounting
Mount URICA to a flat surface with user-supplied 1/4 inch bolts as described below. 1) Determine mounting hardware. See Figure 2-1 and Figure 6-1.
2) Lay out the mounting hole pattern on the selected surface. Drill four mounting holes in the wall or plate [typically, 0.281 (9/32) inch diameter to accept 1/4 inch bolts].
Consider the thickness of the mounting surface and the selected mounting hardware (e.g. screw anchors, nuts and washers) in determining mounting bolt length.
3) Place URICA against the surface and align the mounting cutouts in the flanges with the surface mounting holes. Install user-supplied 1/4 inch bolts, washers, and hex nuts.
October 1995 2.3
Page 16
INSTALLATION UM325-1 oN, s/ cma:
____.. 1/4 Inch Bolt 4 Places / See Note aN
Note: Mounting hardware supplied by installer to suit mounting surface thickness and material.
FIGURE 2-1 Mounting Diagram
2.3.3 Electrical Installation
This section describes the electrical connections to URICA. Figure 2-2 shows the unit’s faceplate. The removable screw terminals (see Figure 5-1) will accommodate wire sizes up to 14 AWG. Terminal assignments are shown in Table 2-1. There is a DB9 female RS232C connector and a terminal block on the faceplate. Figures 2-3, 2-4, and 2-5 show typical installation wiring.
WARNING
Electrical shock hazard. Remove power from all involved wires and terminals before wiring or servicing.
2-4 October 1995
Page 17
UM325-1 INSTALLATION
URICA a Se
+ _ ve pa a “SS. Ground Screw Ooo oO ULE RDY CMD HAT ACT 153456789 101128 \ \Terminal Block
FIGURE 2-2 URICA Faceplate
TABLE 2-1 Terminal Assignments
TERMINAL CONNECTION 1 Not Used Not Used 3 Receive + 4 RS422 Common 5 Receive - 6 Transmit + 7 RS422/485 Common 8 Transmit - 9 Hart + 10 Hart - a Power + 12 Power -
2.3.3.1 DC Power Input Connections Terminal 11 (PWR+) is the +24 Vdc connection for the power supply. Terminal 12 (PWR-) is the common connection for the power supply.
Refer to Section 6.3 for power supply specifications.
October 1995 2-5
Page 18
INSTALLATION
UM325-1
URICA Terminal Block _ Power + See Note 2 - +, HART - HART | | || 1 | F3 + U U ? HARTS \ Model 348 See Note 1 FIELDPAC Notes:
1. 250 ohm resistor recommended. Total network resistance must be greater than 230 and less than 1100 ohms to support communication.
. : X02935S0 2. Cable shield is grounded only at URICA. 1 of 2
FIGURE 2-3 URICA to Model 348 Connections
| 24 Vde Non-Hazardous Hazardous | Location : Location Power i URICA | Supply Terminal -S S§+ Block | } - | 12, Power = } - - | \ Barrier } Field +
Transmitter
HART rt See Notes 2 and 3 Notes: ; X02935S0
20f2
1. 250 ohm resistor recommended. Total network resistance must be greater than 230 and less than 1100 ohms to support communication.
2. Cable shield is grounded only at the barrier.
3. All cable shields at a barrier should be connected to earth ground.
FIGURE 2-4 URICA to Field Transmitter Connections, Hazardous Location
2-6
October 1995
Page 19
UM325-1
INSTALLATION
24 Vde | Non-Hazardous | Hazardous Power | Location Location URICA | Supply Terminal ic > i+ Block i -| 12, \ iti Power ° Model 340 or 344 Valve Positioner + | 44 Barrier Transmitter-Controller or | Tansaucer i orn re i 77 Oto 4 ro € 1 |
HART ard
\ See Note 1
See Note 2
HART Communication Filter See Note 3
Notes:
1. 250 ohm resistor recommended. Total network resistance must be greater than 230 and less than 1100 ohms to support communication.
Cable shield is grounded only at the barrier. All cable shields at a barrier should be connected to earth ground.
X02034S0 A transducer or valve positioner (e.g. Moore Products Co. Model 77, 771, 750E)
with high resistive or inductive input impendence requires a communication filter (PN 16202-3) to allow HART communication between devices in the loop.
The communication filter increases the loop voltage requirement by 5.2 volts because the filter's 237 ohm series resistor must be included in the loop resistance calculation.
. URICA can communicate with one Model 340 or 344 Transmitter-Controller on a point-to-point network., - - FIGURE 2-5 URICA to Transmitter-Controller Connections, Hazardous Location
2.3.3.2 HART Connections
Installation diagrams are shown in Figures 2-3, 2-4, and 2-5. As shown, URICA communicates with either:
e one HART field device (e.g., XTC transmitter-controller or transmitter only or Model 348) ona point-to-point network or e upto 15 HART field devices (e.g., XTC transmitter only or Model 348) on a multi-drop network.
At URICA, the HART communication link is connected to terminals 9 (HART +) and 10 (HART -). A current sense resistor should be connected between terminals 9 and 10. When connecting to a Model 348 or XTC this resistor is typically 250Q. Refer to the field device’s installation instructions for more information. See Table 2-2 for recommended HART cable.
October 1995 2-7
Page 20
INSTALLATION UM325-1
TABLE 2-2 HART Two-Wire Cable
Type Twisted single-pair, shielded, copper Conductor Size for Network Length:
Less than 5000 ft. (1500m) 24 AWG minimum
More than 5000 ft (1500m) 20 AWG minimum, 16 AWG maximum Cable Capacitance Refer to Appendix G Recommendation Beldon 8641, 24 AWG
Beldon 8762, 20 AWG
Length, Maximum Refer to Appendix G
2.3.3.3 RS232C Serial Port Cable Connections
Table 2-3 shows the pin-out and functions of URICA’s RS232 serial port lines. URICA can be set as either a DTE (Data Terminal Equipment) or DCE (Data Circuit-Terminating Equipment) device. Refer to section 3.1.2.5 for information on configuring the communication terminal mode. The factory setting is DCE. In most cases:
e If URICA is communicating with a modem, set it for DTE.
e If URICA is connected directly to a computer, set it to DCE.
The cable between URICA and a master will require a minimum of three lines: TXD, RXD, and SG. Refer to the MODBUS master’s documentation to see what connections it requires. A modem typically requires RTS/CTS handshaking. Refer to Section 3.1.3.1 to set the handshaking.
TABLE 2-3 URICA RS232 Serial Port Layout
DIRECTION PIN # ABBR DESCRIPTION DTE DCE ] 2 RXD Received Data Input Output 3 TXD Transmitted Data Output | Input rn [eee 5 SG Signal Ground N/A N/A 6 7 RTS Request To Send Output | Input 8 CTS Clear To Send Input Output QO | weet
2-8 October 1995