Page 71
UM325-! Appendix G
Appendix G CABLE CAPACITANCE AND MAXIMUM LENGTH
A cable length calculation is necessary when HART communication is to be employed. Cable capacitance directly affects maximum Network length.
Cable Capacitance
Cable type, conductor size, and recommended cable model numbers are stated in Section 2.3.3.
Cable capacitance is a parameter used in the calculation of the maximum length of cable that can be used to construct the Network. The lower the cable capacitance the longer the Network can be.
Manufacturers typically list two capacitance values for an instrumentation cable:
1. Capacitance between the two conductors.
2. Capacitance between one conductor and the other conductor(s) connected to shield. This capacitance is the worst case value and is to be used in the cable length formula.
Maximum Cable Length Calculation
The maximum permissible single-pair cable length is 10,000 feet (3000 meters) or less as determined by the following formula:
65,000,000 C; + 10,000
RxC C
Formula Definitions:
L: The maximum total Jength of cable permitted to construct the Network. L = Feet when C is in pF/ft. L = meters when C is in pF/meter.
R: The Network Resistance which is the ohmic sum of the Current Sense Resistance, Barrier Resistance (both Return and Supply), if any, in the Network, and the resistance of the wire.
C: Cable capacitance per unit length between one conductor and the other conductor connected to the shield. C may be in pF/ft or pF/meter.
Ce Total input terminal capacitance of Field Instruments; the Primary Master (URICA) is excluded. Cr is given by the following formula:
C; = (sum of all C, values) x (5000)
Where C, is an integer (e.g. 1, 2, 3) corresponding to the input terminal capacitance of a Field Instrument. C, values are determined as follows:
October 1995 G-1
Page 72
Appendix G
UM325-1
FIELD INSTRUMENT CAPACITANCE Cy VALUE
Less than 5000 pF
5000 pF to less than 10000 pF 10000 pF to less than 15000 pF 15000 pF to less than 20000 pF 20000 pF to less than 25000 pF
Mm hwWN, For Field Instruments without C, values, use C, = |
Example Calculation:
Assume a Network consists of two Field Instruments (both C, = 1).
Let R = 250 Q, C = 40 pF/ft., Cr = (1 + 1) x 5000 = 10,000 65,000,000 10,000 + 10,000
ThenL = - = 6000 feet (1800 meters) (250)(40) 40
October 1995
Page 73
PARTS LIST yy [MOORE Model 325 URICA™
® Drawing No. 325PL ITEM | PART NUMBER | DESCRIPTION QTY 1* 16260-41 Main Circuit Board 1 2* 7447-214 Power Supply Fuse 125 Volt, 5 Amp 1 3 16260-14 Case Cover Assembly 1 4 1-1162 6-32 x 0.25 Flat Head Enclosure Mounting Screw I 5 16260-20 Case Base Assembly I 6 1-0621 4-40 x 0.25 Phillips Head Circuit Board Mounting Screw 1
Notes:
e = Refer to Section 5 of the Model 325 URICA User’s Manual before servicing URICA. e See Figure for disassembly and Item number reference e An * identifies a recommended on-hand spare part.
e When ordering spare or replacement parts, always provide the complete model number, serial number, and other nameplate information.
xo28e7S0
October 1995 Ref. UM325-1
Page 74
UM325-! Warranty
WARRANTY
The Company warrants all equipment manutactured by it and bearing its nameplate, and all repairs made by it, to be free from defects in material and workmanship under normal use and service. If any part of the equipment herein described and sold by the Company, proves to be defective in material or workmanship and if such part is within twelve months from date of shipment from the Company's factory, returned to such factory, transportation charges prepaid, and if the same is found by the Company to be defective in material or workmanship, it will be replaced or repaired, free of charfe, f.0.b. Company's factory. The Company assumes no liability for the consequence of its use or misuse by Purchaser, his employees or others. A defect in the meaning of this warranty in any part of said equipment shall not, when such part is capable of being renewed, repaired or replaced, operate to condemn such equipment. This warranty 1s expressly in lieu of all other warranties, guaranties, obligations, or liabilities, expressed or implied by the Company or its representatives. All statutory or implied warranties other than title are hereby expressly negated and excluded.
Warranty repair or replacement requires the equipment to be returned to one of the following addresses. Equipment manufactured or sold by MOORE PRODUCT CO.: MOORE PRODUCTS Co. Sumneytown Pike Spring House, PA 19477 Equipment manufactured or sold by MOORE PRODUCTS Co. (CANADA) INC.: MOORE PRODUCTS Co. (CANADA) INC.: 2KM West of Mississauga Rd, Hwy. 7 Brampton, Ontario, Canada Equipment manufactured or sold by MOORE PRODUCTS Co. (UK} LTD.: MOORE PRODUCTS Co. (UK) LTD Copse Road Lufton, Yeovil,
Somerset, BA22 8RN, ENGLAND
The warranty will be null and void if repair is attempted without authorization by MOORE PRODUCTS Co.
October 1995 W-!