MICRO-INFINITY ICN77000 Series Controller Operator's Manual, pages 91 to 100

Pages 91 to 100 of 108

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Newport Electronics, Inc. ICN77530

Page 91

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. COMM.PARAMETERS.210 = 000 300 001 600 010 1200 011 2400 100 4800 101 9600 110 19200 COMM. PARAMETERS.5 = 0 1

BAUD

7 Bit Data 8 Bit Data

COMM. PARAMETERS.43 = 00 01 10 11

No Parity Odd Even N/A

COMM. PARAMETERS.6 = 0 1

1 Stop Bit 2 Stop Bit

Example: Set Baud 9600, Odd, 7 Bit, 1 Stop. The command data is 00001101Bin = 0DHex. Send *W100D. BUSFORMAT.0 = N/A BUSFORMAT.3 = 0 RS-232 1 RS-485

BUS FORMAT.1 = 0 1 BUS FORMAT.4 = 0 1

No LF LF Continuous Command

BUS FORMAT.2 = 0 1 BUS FORMAT.5 = 0 1

No Echo Echo CR Space

Example: Set Space, Continuous, RS-232, Echo, Line Feed, N/A. The command data is 00000110Bin = 06Hex. Send *W1F06.

83

Page 92

part

3

OPERATION: CONFIGURATION MODE

Command Formats cont. Note ☞

DATAFORMAT is used for V01 command or Continuous Mode (RS-232).

DATAFORMAT.0 = 0 No Status 1 Alarm Status DATAFORMAT.3 = 0 No Valley 1 Valley

DATAFORMAT.1 = 0 1 DATAFORMAT.6 = 0 1

No Reading Reading No Unit Unit

DATAFORMAT.2 = 0 No Peak 1 Peak DATAFORMAT.7 = N/A

Example: Set Space, Continuous, RS-232, Echo, Line Feed, N/A. The command data is 00000110Bin = 06Hex. Send *W1F06. Note ☞

ADDRESS is applicable for RS-485 and can be 01 to 199.

Note ☞

TRANSMIT TIME INTERVAL is applicable in the RS-232 Continuous Mode which specifies the time between transmissions and the minimum time is 1 second.

84

Page 93

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. RDGOFF.0~19 = Offset Data

RDGOFF.20~22 = DP+2

RDGOFF.23 = 0 Positive Offset 1 Negative Offset

RDGSC.0~18 = Scale Data

RDGSC.19 = 0 Direct Scale 1 Reverse Scale

RDGSC.20~23 = DP+1

Example: To have an input of 4 to 20 mA displayed as 0 to 100, The Low input value = min. input value * conversion number = 4(mA) x 500 = 2000 The High input value = max. input vlaue * conversion number = 20(mA) x 500 = 10000 (9999) where: converison number is a coefficient of conversion between input values and real display range. The full range of the display = 10000, conversion number = 10000/20 = 500.

85

Page 94

part

3

OPERATION: CONFIGURATION MODE

Reading Scale Scale = (UD - LD)/(UI -LI), where: UD - Upper Display, LD - Low Display UI - Upper Input, LI - Low Input Scale = (100 - 0)/(9999-2000) = 0.0125016 (These values were obtained from example on previous Section 3: Reading Configuration with Process) 0.0125016 = 125016 x 10^ -7, where 125016 is Reading Scale Data, Decimal Point = 7 RDGSC.23~20 = 8 (DP = 7); RDGSC.19 = 0 (direct scale); RDGSC. 18 ~0 = 1E858Hex (125016 Dec) Binary Code:

Hex. Code: Send command: *W1481E858 (scale = 81E858)

86

Page 95

part

OPERATION: CONFIGURATION MODE

3

Reading Offset Offset = UD - Scale x UI Offset = 100 - (0.0125) x (10000) = (-25), where Offset data = 25, Decimal Point = 0, Offset is negative. RDGOFF.23 = 1 (Offset is negative); RDGOFF.22 ~ 20 = 2 (DP = 0); RDGOFF.19 ~ 0 = 00019Hex (25 Dec) Binary Code:

Hex. Code:

Send command: *W03A00019 (offset = A00019)

Note ☞

To communicate when the Continuous Mode is enabled, the Continuous Mode must be stopped by sending 13 Hex (XOFF) and then send ^AE.

87

Page 96 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

Remote Setpoint Option

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX& PRESS ENTER REMOTE, SP1 YES R. SET REMOTE POINT SP2 |_|) )6REMOTE SP3

Figure 3.11 Flowchart for Remote Setpoint

88

Page 97

part

OPERATION: CONFIGURATION MODE

3

Remote Setpoint Option cont. Display

Action

R. S ET p0nt

Press MENU Press ENTER n0t _ INST

Response 1) 2)

Press MENU, if necessary, until the "r.set p0nt" prompt appears. Display advances to "Remote Setpoint 1" submenu.

IF THE REMOTE SETPOINT IS NOT INSTALLED, THE CONTROLLER WILL SHOW

"NOT INSTALLED". Press MENU

Press MENU, if you receive the "Not Installed" message.

R.SP.1 470.0

Press ENTER Press MAX & MIN Press ENTER

REMOTE SETPOINT 1 SUBMENU: 3) Display flashes 1st digit of previous selection for "Remote Setpoint 1" value. 4) Enter a new "Remote Setpoint 1" value. 5) Display flashes "strd" message and advances to "Remote Setpoint 2" submenu.

R.SP.2 375.0

Press ENTER Press MAX & MIN Press ENTER

REMOTE SETPOINT 2 SUBMENU: 6) Display flashes 1st digit of previous selection for "Remote Setpoint 2" value. 7) Enter a new "Remote Setpoint 2" value. 8) Display flashes "strd" message and advances to "Remote Setpoint 3" submenu. 89

Page 98

part

3

OPERATION: CONFIGURATION MODE

Remote Setpoint Option cont. Display

Action

Response

R.SP.3 275.0

Press ENTER Press MAX & MIN Press ENTER

REMOTE SETPOINT 3 SUBMENU: 9) Display flashes 1st digit of previous selection for "Remote Setpoint 3" value. 10) Enter a new "Remote Setpoint 3" value. 11) Display flashes "strd" message and the display shows "Reset" ending the Configuration Mode. RESET: The controller automatically resets after the last menu of the Configuration Mode has been entered. After the controller resets, the controller advances to the Run Mode.

RST

Note ☞

In order to select r.SP remotely connect Bi1 and Bi2 as follows:

r.SP.1 r.SP.2 r.SP.3 Setpoint 1 90

Bi1 GND OPEN GND OPEN

Bi2 GND GND OPEN OPEN

Page 99

part

SPECIFICATIONS Accuracy: See the following Specification Chart. Resolution: 1°/0.1°; 10 µV process Temperature Stability: 0.08°C/°C; 50 ppm/°C process Thermocouple Cold End Tracking: 0.05°C/°C NMRR: 60 dB CMRR: 120 dB A/D Conversion: Dual slope Reading Rate: 3 samples per second Digital Filter: Programmable Display: Dual 4-digit, 7-segment LED, 9.2 mm (0.36"); red process variable, green setpoint; indicators for output and alarm status; 7.6 mm (0.3") for NEMA 12 units Warmup to Rated Accuracy: 30 min INPUT Input Types: Thermocouple, RTD, analog voltage, analog current Thermocouple Lead Resistance: 100 Ω max RTD Input: 100/500/1000Ω Pt sensor, 2, 3, or 4-wire; 0.00385 or 0.00392 curve Voltage Input: 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc Current Input: 0 to 20 mA (5 ohm load) Configuration: Single-ended Polarity: Unipolar Step Response: 0.7 sec for 99.9% Decimal Selection: None, 0.1, 0.01 or 0.001 Span Adjustment: 0.001 to 9999 counts Offset Adjustment: -999 to +9999

4

CONTROL Action: Reverse (heat) or direct (cool) Modes: Time proportioning and proportional control modes; selectable preset tune, adaptive tune, auto-tune, PID, proportional, proportional with integral, proportional with derivative with anti-reset windup, on-off Rate: 000.0 to 399.9 sec Reset: 0 to 3999 sec Cycle Time: 1 to 199 seconds; set to 0 for on/off operation Gain: 0.5 to 100% of span; setpoints 1 or 2 Damping: 0000 to 0008 Soak: 00.00 to 99.59 (HH:MM), or off Ramp to Setpoint: 00.00 to 99.59 (HH:MM), or off Autotune: Operator initiated from front panel CONTROL OUTPUT: Relay: 5 A @ 120 Vac, 3 A @ 240 Vac; configurable for on/off, PID or ramp and soak Output 1: SPDT type Output 2: SPST type SSR: Rated 0.5 A @ 120/240 Vac, continuous DC Pulse: non-isolated; 10 Vdc @ 20 mA Analog Output: 0 to 10 Vdc or 0 to 20 mA; 500 Ω max OPTIONS: Remote Setpoint Selection: Up to 3 setpoints stored in memory; contact closure selection

91

Page 100

part

4

SPECIFICATIONS

COMMUNICATIONS: RS-232 or RS-485: 300 to 19.2k baud; completely programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status RS-485: Addressable from 0 to 199 Connection: Screw terminals ALARM OUTPUT: Type: SPST relay, 3 A @ 120 Vac, 3 A @ 240 Vac Operation: High/low, latching/ non-latching, and process/deviation; front panel configurations ANALOG OUTPUT: Isolated 0 to 10 Vdc or 0 to 20 mA, programmable INSULATION: (per 1 minute test) Power to TC/RTD input: 2300 Vrms Power to Relay/SSR Outputs: 2300 Vrms Power to Relay Alarms: 2300 Vrms Control Relay/SSR to Control Relay/SSR: 2300 Vrms Relay Alarm 1 to Relay Alarm 2: 2300 Vrms RS232/RS485/Analog to Alarms/Controls Relay/SSR/Power: 2300 Vrms RS232/RS485 to Input TC/RTD: 350 Vrms APPROVALS: UL, CE per EN50081-1, EN50082-1, EN61010-1

92

GENERAL: Line Voltage: 90-240 Vac +/-10%, 50-400 Hz Power: 4 Watts External Fuse Required: 100mA/250V Time-Slow-Blow, UL 248-14 Listed 100mA/250V Time-Lag, IEC 127-3 Listed Environmental Condition: 0 to 55°C (32 to 131°F), 90% RH non-condensing ICN77300 Series: 48 H x 48 W x 123.3 mm D (1.89" x 1.89" x 4.85"); ICN77500 Series: 53 H x 53 W x 123.3 mm D (2.1" x 2.1" x 4.85"); Panel Cutout: 45 mm (1.777") square, 1⁄16 DIN ICN77R300 Series: 48 H x 48 W x 135 mm D (1.89" x 1.89" x 5.32"); ICN77R500 Series: 53 H x 53 W x 135 mm D (2.1" x 2.1" x 5.32"); Panel Cutout: 44.5 mm (1.75") dia round Weight: 227 g (0.5 lb)