The text of a manual · part 9 of 11

MICRO-INFINITY ICN77000 Series Controller Operator's Manual, pages 81 to 90

Pages 81 to 90 of 108

The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Newport Electronics, Inc. ICN77530

Page 81

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. Where "*" is the selected Recognition Character. You may select any ASCII table symbol from "!" (HEX address "21") to the right-hand brace (HEX "7D") except for the caret "^", "A", "E", which are reserved for bus format request. "(nn)" are the two ASCII characters for the device Bus Address. Use values from "00" to hex "C7" (199 decimal). "ccc" stands for the hex-ASCII Command Class letter (one of eleven given in table 3.12), followed by the two HexASCII Command Suffix characters identifying the meter data, features or menu items to which the command is directed (given in table 3.13). "<data>" is the string of characters containing the variable information the computer is sending to the meter. These data (whether BCD or binary) are encoded into Hex-ASCII characters, two characters to the byte. Square brackets (indicating optional status) enclose this <data> string, since some commands contain no data. "<nn>" is the device address for RS-485 communication and the max is 199 in decimal.

Examples: 1. To reset the controller, send *Z02 (Table 3.1) 2. To read Setpoint 1, send *R01 (Table 3.2) 3. To change Setpoint 1 to 100.0

73

Page 82

part

3

OPERATION: CONFIGURATION MODE

Command Formats cont. Description: SETPOINT.23 ~ 0 means 3 bytes x 8 bit positions (2 characters in each byte). SETPOINT.23 = 0 = positive sign 1 = negative sign

SETPOINT.22~20 = 000 - Not Allowed 001 - Decimal Point 1 (XXXX.) 010 - Decimal Point 1 (XXX.X) 011 - Decimal Point 1 (XX.XX) 101 - Decimal Point 1 (X.XXX) *Process Only

SETPOINT.19~0 = Setpoint data

For 100.0: Positive sign = 0, Decimal Point 2 = 010 Bin, Setpoint data 1000 = 3E8 Hex = 001111101000 Bin The command data = 0010 0000 0000 0011 1110 1000 Bin = 2003E8 Hex A 0 0 3 E 8 Hex Send *W01 2 003E8, where *W01 - *<ccc> - write to Setpoint 1 (Table 3.1) 2003E - <data> - Setpoint data including sign and decimal point (Table 3.2)

74

Page 83

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. Note ☞

No spaces are allowed in the data string. The spaces provided in the previous example are for illustration purposes only.

Note ☞

Decimal Point position for TC/RTD = 1 or 2, for PROCESS = 1, 2 , 3, or 4.

Note ☞

Decimal Point position for setpoint should be the same as Decimal Point position sets for Process Value and can not be overwritten by SETPOINT command. (See RDGCNG command, described below.)

4. To change Setpoint 1 to -100.0 For (-100.0): Negative sign = 1, Decimal Point 2 = 010 Bin, Setpoint data 1000 = 3E8 Hex = 001111101000 Bin The command data = 1010 0000 0000 0011 1110 1000 Bin = A003E8 Hex A 0 0 3 E 8 Send *W01A003E8 5. To send the same as above for RS-485 of transit address 01 the command is *01W01A03E8. Note ☞

Default settings are Recog. Char. “*”, 9600 bps, 7 data, 1 stop, and Odd Parity.

75

Page 84

part

3

OPERATION: CONFIGURATION MODE COMMAND LETTERS AND INDEX (Table 3.2) Command Command Index

RW RW GPRW RW RW GPRW RW RW RW RW RW RW RW RW GPRW

76

01 02 03 05 06 07 08 09 0B 0C 0D 0E 10 12 13 14

Function

Command Bytes

#OF Characters

Default Value

SP1 SP2 RDGOFF ID N/A INPUT RDGCNF AL1CNFG LOOP BREAK TIME OUT1CNF OUT2CNF RAMPTIME COMM.PARAMETERS AL1LO AL1HI RDGSCL

3 3 3 2 1 1 1 2 1 1 2 1 3 3 3

6 6 6 4 2 2 2 4 2 2 4 2 6 6 6

200000 200000 200000 0000 04 4A 00 003B 81 60 0000 0D A003E8 201170 100001

Page 85

part

OPERATION: CONFIGURATION MODE COMMAND LETTERS AND INDEX cont. Command Command Index

GPRW GPRW GPRW GPRW GPRW GPRW RW RW GPRW RW RW RW RW Note ☞

17 18 19 1A 1B 1C 1D 1E 1F 20 21 22 25 26

Function

PB1/DEAD BAND RESET 1 RATE 1 CYCLE 1 N/A PB2/DEAD BAND CYCLE 2 SOAK TIME BUS FORMAT DATA FORMAT ADDRESS TRANSMIT TIME INTERVAL C.J.OFFSET ADJ. RECOGNITION CHARACTER

3

COMMAND LETTERS AND INDEX cont. Command #OF Default Bytes Characters Value

2 2 2 1 2 1 2 1 1 1 2 3 1

4 4 4 2 4 2 4 2 2 2 4 6 2

00C8 00B4 0000 07 00C8 07 0000 14 02 01 0010 200000 2A

Command Command Index

D D D E E E X X X X X U U V Z

01 03 04 01 03 04 01 02 03 04 05 01 03 01 02

Function

DISABLE ALARM 1 STANDBY DISABLE SELF ENABLE ALARM 1 DISABLE STANDBY ENABLE SELF SEND MAIN READING SEND PEAK READING SEND VALLEY READING SEND READING SEND READING SEND ALARM STATUS SEND SW VERSION SEND DATA STRING HARD RESET

Except for Setpoints and Alarms, modifying and setting of the menu configuration should be followed by the RESET Command.

77

Page 86

part

3

OPERATION: CONFIGURATION MODE

Command Formats Description: INPUT.76543210 means 8 bit positions of the Input Command Data (Operand). INPUT.76 = 00 = 100 ohm RTD 01 = 500 ohm RTD 10 = 1000 ohm

INPUT.5432 = 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001

J/392-2/0-100 mV K/392-3/0-1 V T/392-4/0-10 V E/385.2/0-20 mA N/385.3 DIN-J/385.4 R S B C

INPUT.10 = 00 01 10 11

TC RTD PC N/C

Example: Set RTD, 4-wire, .00392 Curve, 100 m ohms. The command data is 00001001Bin = 09Hex. Send *W0709. Note ☞

78

Send Read Command first to determine the bits which are not specified for some positions (TC, PC for positions 7, 6 above).

Page 87

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. RDGCNF.210 = 000 Not Allowed 001 Decimal Point 1 (XXXX.) 010 Decimal Point 2 (XXX.X) 011 Decimal Point 3* (XX.XX) 100 Decimal Point 4* (X.XXX) *Process only

RDGCNFG.3 = 0 °C 1 °F

RDGCNFG.765 = 000 001 010 011 100 101 110 111

Filter constant 1 Filter constant 2 Filter constant 4 Filter constant 8 Filter constant 16 Filter constant 32 Filter constant 64 Filter constant 128

Example: Set Decimal Point 1, °C, Filter constant 16. The command data is 10000001Bin = 81Hex. Send *W0881. Note ☞

Send a Read Command first to determine the proper Decimal Point position (*R08).

79

Page 88

part

3

OPERATION: CONFIGURATION MODE

Command Formats cont. AL1CNFG.0 = 0 Disable 1 Enable

AL1CNFG.1 = 0 Absolute 1 Deviation

AL1CNFG.2 = 0 Unlatch 1 Latch

AL1CNFG.54 = 00 Above AL1CNFG.6 = 0 Loop Break Alarm Disable 01 Below 1 Loop Break Alarm Enable 10 Hi/Lo * 11 Band * Deviation Only

AL1CNFG.3 = 0 Normally Open 1 Normally Closed

AL1CNFG.7 = 0 Alarm Power On Enable 1 Alarm Power On Disable

Example: Set Alarm 1 Enable, Deviation, Unlatch, N.C., Band, Loop Disable, Alarm Power On Enable. The command data is 10111011Bin = BBHex. Send *W09BB.

80

Page 89

part

OPERATION: CONFIGURATION MODE

3

Command Formats cont. Time Proportional: OUT1CNFG.0 = 0 On/off 1 PID

Analog Proportional: OUT1CNFG.6 = 0 0 - 20 mA 1 4 - 20 mA

OUT1CNFG.1 = 0 Reverse 1 Direct

OUT1CNFG.2 = 0 Auto PID Disable 1 Auto PID Enable

OUT1CNFG.4 = 0 Anti Wind Up Disable 1 Anti Wind Up Enable

OUT1CNFG.5 = 0 Auto PID Stop 1 Auto PID Start

OUT1CNFG.3 = 0 Adaptive Disable 1 Adaptive Enable

Example: Set PID, Direct, Auto PID Enable, Adaptive Enable, Anti Integral Disable, Auto PID Start. The command data is 00101111Bin = 2FHex. Send *W0C17.

81

Page 90

part

3

OPERATION: CONFIGURATION MODE

Command Formats cont. OUT2CNFG.0 = 0 On/off 1 PID

OUT2CNFG.1 = 0 Reverse 1 Direct

OUT2CNFG.2 = 0 Manual PID 1 Auto PID

OUT2CNFG.3 = 0 Ramp Disable 1 Ramp Enable

OUT2CNFG.4 = 0 Soak Disable 1 Soak Enable

OUT2CNFG.765 = 000 Damping 1 001 Damping 2 010 Damping 3 011 Damping 4 100 Damping 5 101 Damping 6 110 Damping 7 111 Damping 8

Example: Set On/Off, Reverse, Auto PID Disable, Ramp, Disable, Soak Disable, Damping 5. The command data is 10000000Bin = 80Hex. Send *W0D85.

82