Page 71
part
OPERATION: CONFIGURATION MODE
3
Analog Output Option cont. Display
Action
Response
RD 1 0000
Press ENTER Press MAX & MIN Press ENTER
READING 1 6) Display flashes 1st digit of previous “Reading 1” value. 7) Enter "Reading 1" value. 8) Display advances to "oUt1".
o UT. 1
Press ENTER Press MAX & MIN Press ENTER
OUT 1 9) Display flashes 1st digit of previous “Out 1” value. 10) Enter "Out 1" value. 11) Display advances to "Reading 2".
RD 2 9999
Press ENTER Press MAX & MIN Press ENTER
READING 2 12) Display flashes 1st digit of previous “Reading 2” value. 13) Enter "Reading 2" value. 14) Display advances to "out.2".
o UT. 2
Press ENTER Press MAX & MIN Press ENTER
00. 0 0
10. 0 0
OUT 2 15) Display flashes 1st digit of previous “Out 2” value. 16) Enter "Out 2" value. 17) Display advances to the "Communication Option" menu. The above example is for 0-10 of the entire range of the process input and analog Note ☞ output. For 0-20 mA output all you need is to set “Out 2” to 20.00. 63
Page 72
OPERATION: CONFIGURATION MoDE
Communication Option
MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX& PRESS ENTER y)
rp vo BAUD 300 600 1200 2400 4800 960019.2K| STATUS 1 YES ~_ - NO, READING Li ves __}+ - rm no PEAK ~_} - L - yes
VALLEY 1 YES
NO
{, + - UNIT {ves
NO
TL ves
LINE No, _ - }R - - FEED YES
JEL
BUS NO ECHO STANDARD, 232C ] TRANSMIT 485 TIME MODE COMMAND 7 CONTINUOUS CARRIAGE SEPARATION RETURN *~._-_ ~ SPACE
Figure 3.10 Flowchart for Communication Option ill
64
Page 73
part
OPERATION: CONFIGURATION MODE
3
Communication Option cont. Display
Action
COM7 OPTN
Press MENU Press ENTER
NoT _ INST
COM7 PARA BAUD 300 _
Press MENU
Response 1) 2)
Press MENU, if necessary, until the "C O M 7 O P T N " prompt appears. Display advances to “Communication Parameters" submenu.
IF THE COMMUNICATION OPTION IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NoT_INST" Press MENU, if you receive the "Not Installed" message and advance to the "Remote Setpoint" menu.
COMMUNICATION PARAMETERS SUBMENU: Display shows "Communication Parameters" prompt. Press ENTER
Press ENTER Press MAX Press ENTER
3)
Display advances to "BAUD" submenu.
BAUD SUBMENU: 4) Display flashes previous selection for "BAUD" value. 5) Scroll through the available selections: 300, 600, 1200, 2400, 4800, 9600, 19.2K. 6) Display flashes "strd" message and advances to "Parity" submenu. 65
Page 74
part
3
OPERATION: CONFIGURATION MODE
Communication Option cont. Display
Action
Response
PRTY EVEN
Press ENTER Press MAX Press ENTER
PARITY SUBMENU: 7) Display flashes previous selection for "Parity". 8) Scroll through the available selections: NO, ODD, EVEN. 9) Display flashes "strd" message and advances to "Data Bit" submenu.
DATA 7BIT
Press ENTER Press MAX Press ENTER
DATA BIT SUBMENU: 7) Display flashes previous selection for "Data Bit". 8) Scroll through the available selections: 7 BIT, 8 BIT. 9) Display flashes "strd" message and advances to "Stop Bit" submenu.
STOP 1BIT
Press ENTER Press MAX Press ENTER
STOP BIT SUBMENU: 7) Display flashes previous selection for "Stop Bit". 8) Scroll through the available selections: 1 BIT, 2 BIT. 9) Display flashes "strd" message and advances to "BUS FORMAT" submenu.
_ BUS FRMT 66
BUS FORMAT SUBMENU: Display shows "bus frMt" prompt. Press ENTER
10) Display advances to "Check Sum" submenu.
Page 75
part
OPERATION: CONFIGURATION MODE
3
Communication Option cont. Display
Action
Response
C. S UM _ yes
Press ENTER Press MAX Press ENTER
CHECK SUM SUBMENU: 11) Display flashes previous selection for "Check Sum". 12) Scroll through the available selections: NO, YES. 13) Display flashes "strd" message and advances to "Line Feed" submenu.
_ LF _ _ No _
Press ENTER Press MAX Press ENTER
LINE FEED SUBMENU: 14) Display flashes previous selection for "Line Feed". 15) Scroll through the available selections: NO, YES. 16) Display flashes "strd" message and advances to "ECHO" submenu.
ECKO _ YES
Press ENTER Press MAX Press ENTER
ECHO SUBMENU: 17) Display flashes previous selection for "ECHO". 18) Scroll through the available selections: NO, YES. 19) Display flashes "strd" message and advances to "Standard" submenu.
STND 485 _
Press ENTER Press MAX Press ENTER
STANDARD SUBMENU: 20) Display flashes previous selection for "Standard". 21) Scroll through the available selections: 232C, 485. 22) Display flashes "strd" message and advances to "Mode" submenu.
Note ☞
By setting stardard to 485, the device will only respond to commands to its serial port that include the address, as selected on the following pages. (Transmit Time Section) 67
Page 76
part
3
OPERATION: CONFIGURATION MODE
Communication Option cont. Display
Action
Response
MoDE CMD _
Press ENTER Press MAX Press ENTER
MODE SUBMENU: 23) Display flashes previous selection for "Mode". 24) Scroll through the available selections: CMND, CONT (command, continuous). 25) Display flashes "strd" message and advances to "Separation" submenu.
SEPR SPCE
Press ENTER Press MAX Press ENTER
SEPARATION SUBMENU: 26) Display flashes previous selection for "Separation". 27) Scroll through the available selections: SPCE, CR (space, carriage return). 28) Display flashes "strd" message and advances to "Data Format" submenu.
Press ENTER
DATA FORMAT SUBMENU: Display shows "data frMt" prompt. This menu is applicable for continuous mode of RS-232 communication. 32) Display advances to "Status" submenu.
DATA FRMT Note ☞
68
The Data Format options determine what readings and values will be returned in the data string sent from the unit either when operating in Continuous Mode or when receiving a Send-Data-String request via the serial port.
Page 77
part
OPERATION: CONFIGURATION MODE
3
Communication Option cont. Display
Action
Response
STAT _ YES
Press ENTER Press MAX Press ENTER
STATUS SUBMENU: 33) Display flashes previous selection for "Status" (alarm status). 34) Scroll through the available selections: NO, YES. 35) Display flashes "strd" message and advances to "Reading" submenu.
RDNG _ YES
Press ENTER Press MAX Press ENTER
READING SUBMENU: 36) Display flashes previous selection for "Reading". 37) Scroll through the available selections: NO, YES. 38) Display flashes "strd" message and advances to "Peak" submenu.
PEAI_ YES
Press ENTER Press MAX Press ENTER
PEAK SUBMENU: 39) Display flashes previous selection for "Peak". 40) Scroll through the available selections: NO, YES. 41) Display flashes "strd" message and advances to "Valley" submenu.
VALY _ YES
Press ENTER Press MAX Press ENTER
VALLEY SUBMENU: 42) Display flashes previous selection for "Valley". 43) Scroll through the available selections: NO, YES. 44) Display flashes "strd" message and advances to "Unit" submenu.
69
Page 78
part
3
OPERATION: CONFIGURATION MODE
Communication Option cont. Display
Action
Response
UNIT _ YES
Press ENTER Press MAX Press ENTER
UNIT SUBMENU: 45) Display flashes previous selection for "Unit". 46) Scroll through the available selections: NO, YES. 47) Display flashes "strd" message and advances to "ID" submenu.
ID _ no _
Press ENTER Press MAX Press ENTER
ID SUBMENU: NOT INSTALLED 48) Display flashes previous selection for "ID". 49) Scroll through the available selections: NO, YES. 50) Display flashes "strd" message and advances to "Address Setup" submenu.
Press ENTER
ADDRESS SETUP SUBMENU: . Display shows "addr st.up" prompt. This menu is applicable to the RS-485 option only. 51) Display advances to "Address Value" (0000 to 0199) submenu.
ADDR ST. U P ADDR 0000
70
Press ENTER Press MAX & MIN Press ENTER
ADDRESS VALUE SUBMENU: 52) Display flashes 1st digit of previous address value. 53) Enter new address value. 54) Display flashes "strd" message and advances to "Transmit Time" submenu. If no change press “Menu” to go on.
Page 79
part
OPERATION: CONFIGURATION MODE
3
Communication Option cont. Display
Action
TRANSMIT TIME SUBMENU: Display shows "tr.ti st.up" prompt. This menu is applicable if Continuous Mode was selected.
TR. T I ST. U P Press ENTER
TR. T I 0030
Press ENTER Press MAX & MIN Press ENTER
Note ☞
Response
55) Display advances to "Transmit Time Value" submenu. TRANSMIT TIME VALUE SUBMENU: 56) Display flashes 1st digit of previous transmit time in seconds. 57) Enter new transmit time, e.g. 0030 will send every 30 seconds the data in Continuous Mode. 58) Display flashes "strd" message and advances to "Remote Setpoint" menu. If no change press “Menu” to go on.
Transmit time can be set from 0 to 9999.
71
Page 80
part
3
OPERATION: CONFIGURATION MODE
COMMUNICATION COMMANDS (Table 3.1) Command Prefix (Command Class) ^AE P (Put) W (Write) G (Get) R (Read) U V X D E Z
Meaning Special read, Communication parameters Write HEX data into RAM Write HEX data into EEPROM. 1,000,000 writes to EEPROM is guaranteed! Read HEX data from RAM Read HEX data from EEPROM Read status byte Read measurement data string in decimal format Read measurement data values in decimal format Disable Enable Reset
Command Formats For “P” and “W” Command Classes: Point-to-point mode: * ccc [<data>] <CR> Multipoint mode: * nnccc [<data>] <CR> 72
For “G” and “R” Command Classes: Point-to-point mode: * ccc <CR> Multipoint mode: * nnccc <CR>
For “X”, “V”, “U”, “D”, “E” and “Z” Command Classes: Point-to-point mode: * ccc <CR> Multipoint mode: * nnccc <CR>