Page 71

part

OPERATION: CONFIGURATION MODE

3

Analog Output Option cont. Display

Action

Response

RD 1 0000

Press ENTER Press MAX & MIN Press ENTER

READING 1 6) Display flashes 1st digit of previous “Reading 1” value. 7) Enter "Reading 1" value. 8) Display advances to "oUt1".

o UT. 1

Press ENTER Press MAX & MIN Press ENTER

OUT 1 9) Display flashes 1st digit of previous “Out 1” value. 10) Enter "Out 1" value. 11) Display advances to "Reading 2".

RD 2 9999

Press ENTER Press MAX & MIN Press ENTER

READING 2 12) Display flashes 1st digit of previous “Reading 2” value. 13) Enter "Reading 2" value. 14) Display advances to "out.2".

o UT. 2

Press ENTER Press MAX & MIN Press ENTER

00. 0 0

10. 0 0

OUT 2 15) Display flashes 1st digit of previous “Out 2” value. 16) Enter "Out 2" value. 17) Display advances to the "Communication Option" menu. The above example is for 0-10 of the entire range of the process input and analog Note ☞ output. For 0-20 mA output all you need is to set “Out 2” to 20.00. 63

Page 72 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

Communication Option

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX& PRESS ENTER y)

rp vo BAUD 300 600 1200 2400 4800 960019.2K| STATUS 1 YES ~_ - NO, READING Li ves __}+ - rm no PEAK ~_} - L - yes

VALLEY 1 YES

NO

{, + - UNIT {ves

NO

TL ves

LINE No, _ - }R - - FEED YES

JEL

BUS NO ECHO STANDARD, 232C ] TRANSMIT 485 TIME MODE COMMAND 7 CONTINUOUS CARRIAGE SEPARATION RETURN *~._-_ ~ SPACE

Figure 3.10 Flowchart for Communication Option ill

64

Page 73

part

OPERATION: CONFIGURATION MODE

3

Communication Option cont. Display

Action

COM7 OPTN

Press MENU Press ENTER

NoT _ INST

COM7 PARA BAUD 300 _

Press MENU

Response 1) 2)

Press MENU, if necessary, until the "C O M 7 O P T N " prompt appears. Display advances to “Communication Parameters" submenu.

IF THE COMMUNICATION OPTION IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NoT_INST" Press MENU, if you receive the "Not Installed" message and advance to the "Remote Setpoint" menu.

COMMUNICATION PARAMETERS SUBMENU: Display shows "Communication Parameters" prompt. Press ENTER

Press ENTER Press MAX Press ENTER

3)

Display advances to "BAUD" submenu.

BAUD SUBMENU: 4) Display flashes previous selection for "BAUD" value. 5) Scroll through the available selections: 300, 600, 1200, 2400, 4800, 9600, 19.2K. 6) Display flashes "strd" message and advances to "Parity" submenu. 65

Page 74

part

3

OPERATION: CONFIGURATION MODE

Communication Option cont. Display

Action

Response

PRTY EVEN

Press ENTER Press MAX Press ENTER

PARITY SUBMENU: 7) Display flashes previous selection for "Parity". 8) Scroll through the available selections: NO, ODD, EVEN. 9) Display flashes "strd" message and advances to "Data Bit" submenu.

DATA 7BIT

Press ENTER Press MAX Press ENTER

DATA BIT SUBMENU: 7) Display flashes previous selection for "Data Bit". 8) Scroll through the available selections: 7 BIT, 8 BIT. 9) Display flashes "strd" message and advances to "Stop Bit" submenu.

STOP 1BIT

Press ENTER Press MAX Press ENTER

STOP BIT SUBMENU: 7) Display flashes previous selection for "Stop Bit". 8) Scroll through the available selections: 1 BIT, 2 BIT. 9) Display flashes "strd" message and advances to "BUS FORMAT" submenu.

_ BUS FRMT 66

BUS FORMAT SUBMENU: Display shows "bus frMt" prompt. Press ENTER

10) Display advances to "Check Sum" submenu.

Page 75

part

OPERATION: CONFIGURATION MODE

3

Communication Option cont. Display

Action

Response

C. S UM _ yes

Press ENTER Press MAX Press ENTER

CHECK SUM SUBMENU: 11) Display flashes previous selection for "Check Sum". 12) Scroll through the available selections: NO, YES. 13) Display flashes "strd" message and advances to "Line Feed" submenu.

_ LF _ _ No _

Press ENTER Press MAX Press ENTER

LINE FEED SUBMENU: 14) Display flashes previous selection for "Line Feed". 15) Scroll through the available selections: NO, YES. 16) Display flashes "strd" message and advances to "ECHO" submenu.

ECKO _ YES

Press ENTER Press MAX Press ENTER

ECHO SUBMENU: 17) Display flashes previous selection for "ECHO". 18) Scroll through the available selections: NO, YES. 19) Display flashes "strd" message and advances to "Standard" submenu.

STND 485 _

Press ENTER Press MAX Press ENTER

STANDARD SUBMENU: 20) Display flashes previous selection for "Standard". 21) Scroll through the available selections: 232C, 485. 22) Display flashes "strd" message and advances to "Mode" submenu.

Note ☞

By setting stardard to 485, the device will only respond to commands to its serial port that include the address, as selected on the following pages. (Transmit Time Section) 67

Page 76

part

3

OPERATION: CONFIGURATION MODE

Communication Option cont. Display

Action

Response

MoDE CMD _

Press ENTER Press MAX Press ENTER

MODE SUBMENU: 23) Display flashes previous selection for "Mode". 24) Scroll through the available selections: CMND, CONT (command, continuous). 25) Display flashes "strd" message and advances to "Separation" submenu.

SEPR SPCE

Press ENTER Press MAX Press ENTER

SEPARATION SUBMENU: 26) Display flashes previous selection for "Separation". 27) Scroll through the available selections: SPCE, CR (space, carriage return). 28) Display flashes "strd" message and advances to "Data Format" submenu.

Press ENTER

DATA FORMAT SUBMENU: Display shows "data frMt" prompt. This menu is applicable for continuous mode of RS-232 communication. 32) Display advances to "Status" submenu.

DATA FRMT Note ☞

68

The Data Format options determine what readings and values will be returned in the data string sent from the unit either when operating in Continuous Mode or when receiving a Send-Data-String request via the serial port.

Page 77

part

OPERATION: CONFIGURATION MODE

3

Communication Option cont. Display

Action

Response

STAT _ YES

Press ENTER Press MAX Press ENTER

STATUS SUBMENU: 33) Display flashes previous selection for "Status" (alarm status). 34) Scroll through the available selections: NO, YES. 35) Display flashes "strd" message and advances to "Reading" submenu.

RDNG _ YES

Press ENTER Press MAX Press ENTER

READING SUBMENU: 36) Display flashes previous selection for "Reading". 37) Scroll through the available selections: NO, YES. 38) Display flashes "strd" message and advances to "Peak" submenu.

PEAI_ YES

Press ENTER Press MAX Press ENTER

PEAK SUBMENU: 39) Display flashes previous selection for "Peak". 40) Scroll through the available selections: NO, YES. 41) Display flashes "strd" message and advances to "Valley" submenu.

VALY _ YES

Press ENTER Press MAX Press ENTER

VALLEY SUBMENU: 42) Display flashes previous selection for "Valley". 43) Scroll through the available selections: NO, YES. 44) Display flashes "strd" message and advances to "Unit" submenu.

69

Page 78

part

3

OPERATION: CONFIGURATION MODE

Communication Option cont. Display

Action

Response

UNIT _ YES

Press ENTER Press MAX Press ENTER

UNIT SUBMENU: 45) Display flashes previous selection for "Unit". 46) Scroll through the available selections: NO, YES. 47) Display flashes "strd" message and advances to "ID" submenu.

ID _ no _

Press ENTER Press MAX Press ENTER

ID SUBMENU: NOT INSTALLED 48) Display flashes previous selection for "ID". 49) Scroll through the available selections: NO, YES. 50) Display flashes "strd" message and advances to "Address Setup" submenu.

Press ENTER

ADDRESS SETUP SUBMENU: . Display shows "addr st.up" prompt. This menu is applicable to the RS-485 option only. 51) Display advances to "Address Value" (0000 to 0199) submenu.

ADDR ST. U P ADDR 0000

70

Press ENTER Press MAX & MIN Press ENTER

ADDRESS VALUE SUBMENU: 52) Display flashes 1st digit of previous address value. 53) Enter new address value. 54) Display flashes "strd" message and advances to "Transmit Time" submenu. If no change press “Menu” to go on.

Page 79

part

OPERATION: CONFIGURATION MODE

3

Communication Option cont. Display

Action

TRANSMIT TIME SUBMENU: Display shows "tr.ti st.up" prompt. This menu is applicable if Continuous Mode was selected.

TR. T I ST. U P Press ENTER

TR. T I 0030

Press ENTER Press MAX & MIN Press ENTER

Note ☞

Response

55) Display advances to "Transmit Time Value" submenu. TRANSMIT TIME VALUE SUBMENU: 56) Display flashes 1st digit of previous transmit time in seconds. 57) Enter new transmit time, e.g. 0030 will send every 30 seconds the data in Continuous Mode. 58) Display flashes "strd" message and advances to "Remote Setpoint" menu. If no change press “Menu” to go on.

Transmit time can be set from 0 to 9999.

71

Page 80

part

3

OPERATION: CONFIGURATION MODE

COMMUNICATION COMMANDS (Table 3.1) Command Prefix (Command Class) ^AE P (Put) W (Write) G (Get) R (Read) U V X D E Z

Meaning Special read, Communication parameters Write HEX data into RAM Write HEX data into EEPROM. 1,000,000 writes to EEPROM is guaranteed! Read HEX data from RAM Read HEX data from EEPROM Read status byte Read measurement data string in decimal format Read measurement data values in decimal format Disable Enable Reset

Command Formats For “P” and “W” Command Classes: Point-to-point mode: * ccc [<data>] <CR> Multipoint mode: * nnccc [<data>] <CR> 72

For “G” and “R” Command Classes: Point-to-point mode: * ccc <CR> Multipoint mode: * nnccc <CR>

For “X”, “V”, “U”, “D”, “E” and “Z” Command Classes: Point-to-point mode: * ccc <CR> Multipoint mode: * nnccc <CR>