Page 61

part

OPERATION: CONFIGURATION MODE

3

Output 2 cont. Display

Action

Response

ACTN TYPE

Press ENTER

ACTION TYPE SUBMENU: 6) Display flashes "dr Ct" or "rUrs".

ACTN DRCT Note ☞

Press MAX Press ENTER

7) Scroll through the available selections: Direct or Reverse. 8) Display flashes "strd" message and advances to "Auto PID" submenu. If "ON/OFF" was selected in the Control Type, the display skips to the "Deadband" submenu.

The error that results from the measurement of the process variable may be positive or negative since it may be greater or smaller than the set point. If a positive error should cause the controller output to increase (i.e. cooling), it would be called Direct Acting. If a negative error should cause the output to increase (i.e. heating), it would be called Reverse Acting.

53

Page 62

part

3

OPERATION: CONFIGURATION MODE

Output 2 cont. Display

Action

Response

AUTO PID

Press ENTER Press MAX

AUTO PID SUBMENU: 9) Display flashes "enbl" or "dsbl". 10) Scroll through the available selections: Enable or Disable.

AUTO ENBL

Press ENTER

If "Enabled", the PID parameter of Output 1 will be copied to Output 2. 11) Display flashes "strd" message and advances to the next submenu, If "Auto PID" was "Enabled", the display skips to the "Cycle Time" submenu. If "Auto PID" was "Disabled", the display will show the "Proportional Band" submenu allowing the user to manually enter the Proportional Band value. Note ☞ The Reset and Rate value are the same as Output 1.

PROP BAND

Press ENTER Press MAX & MIN Press ENTER

PROPORTIONAL BAND SUBMENU: 12) Display flashes 1st digit of the previous "Proportional Band" value. 13) Press MAX and MIN buttons to enter a new "Proportional Band" value. 14) Display flashes "strd" message and advances to the "Cycle Time" submenu. Note ☞

54

Refer to Proportional Band, submenu of Output 1 Menu.

Page 63

part

OPERATION: CONFIGURATION MODE

3

Output 2 cont. Display

Action

Response

CYCL

Press ENTER

CYCLE TIME SUBMENU: 15) Display flashes 1st digit of the previous "Cycle Time" value.

TIME

CYCL 0010 Note ☞

Press MAX & MIN

16) Press MAX and MIN buttons to enter a new "Cycle Time" value. (1 to 199 seconds).

Press ENTER

17) Display flashes "stored" message and advances to "Ramp & Soak" Menu.

A Cycle Time selected between 1 to 199 seconds indicates the total On/Off time of each proportional cycle. For example, a 15 second Cycle Time means that every 15 seconds the output will turn on for part or all of the cycle. For Relay control outputs, do not select a cycle time of less than 7 seconds or the relays life time will be shortened. For a cycle time of less than 7 seconds select SSR or DC pulse. Use an external SSR with the DC pulse option for higher current (higher than 1 Amp).

55

Page 64

part

3

OPERATION: CONFIGURATION MODE

Output 2 cont. Display

Action

DEAD BAND

Press ENTER

DEAD 006. 7 Note ☞

56

Press MAX & MIN Press ENTER

Response The "Dead Band" submenu will only appear if the "On/Off" was selected from the "Control Type" menu. DEAD BAND SUBMENU: 18) Display flashes 1st digit of the previous "Dead Band" value.

19) Press MAX and MIN buttons to enter a new "Dead Band" value. 20) Display flashes "stored" message and advances to the "Ramp Value" menu. Note ☞

Refer to Dead Band submenu of Output 1 Menu.

The Dead Band is the number of degrees or counts around the setpoint which the process variable must pass through before the output changes state.

Page 65 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX & PRESS ENTER | DISABLE rc RAMP

I ENABLE

- - - DISABLE SOAK |___ENABLE [> RAMP &, SOAK RAMP VALUE SOAK VALUE

Figure 3.8 Flowchart for Ramp & Soak

57

Page 66

part

3

OPERATION: CONFIGURATION MODE

Ramp & Soak Display

Action

Response

RAMp SoAc

Press MENU Press ENTER

RAMp ENBL

Press ENTER Press MAX Press ENTER

RAMP ENABLE/DISABLE SUBMENU: 3) Display flashes "enbl" or "dsbl". 4) Scroll through the available selections: Enable or Disable. 5) * Display flashes "strd" message and advances to "Soak Enable/Disable" submenu.

SoAc ENBL

Press ENTER Press MAX Press ENTER

SOAK ENABLE/DISABLE SUBMENU: 6) Display flashes "enbl" or "dsbl". 7) Scroll through the available selections: Enable or Disable. 8) Display flashes "strd" message and advances to "Ramp Value" submenu.

1) Press MENU, if necessary, until the "raMp soac" prompt appears. 2) Display advances to "Ramp Enable/Disable" submenu.

Ramp & Soak provides users with the flexibility to slowly bring the process variable to the desired set point. Ramp & Soak Values are specified in HH.MM format. The Ramp Value indicates the time specified to bring the process variable to Setpoint 1. Once setpoint is reached, the PID takes over and the process variable will be controlled at the desired setpoint indefinitely. If Soak is enabled, PID will control the process variable at the specified setpoint for the duration of soak time and then will turn off Output 1. To start a new ramp/soak cycle, reset the controller by pressing MENU and then MIN button.An active ramp/soak will change SP1 one degree above the PV and will cause the most significant digit to blink. The SP1 will be incremented by one degree until it reaches the original SP1. The minimum ramp time must be at least twice the time that it will take the PV to reach the SV with OUT1 fully ON. * NOTE: If “Ramp” Disable was selected, the display skips “Soak” submenu to the next menu item. Note ☞

58

Page 67

part

OPERATION: CONFIGURATION MODE

3

Ramp & Soak cont. Display

Action

Response

RAMp 05. 6 7

Press ENTER Press MAX & MIN Press ENTER

RAMP VALUE SUBMENU: 9) Display flashes 1st digit of previous "raMp" value. 10) Press MAX and MIN buttons to enter a new "raMp" value. 11) Display flashes "strd" message and advances to "Soak Value" submenu.

SoAc 05. 6 7

Press ENTER Press MAX & MIN Press ENTER

SOAK VALUE SUBMENU: 9) Display flashes 1st digit of previous "Soak" value. 10) Press MAX and MIN buttons to enter a new "Soak" value. 11) Display flashes "strd" message and advances to the "Analog Output".

Note ☞

The Ramp & Soak time is 00:00 to 99:59 i.e. HH.MM.(from zero to 99 hours and 59 minutes) During Ramp & Soak do not perform any operations or settings before first pressing MENU and MIN buttons or using software disable Ramp. Any alarms or other output are disabled during this time.

59

Page 68

part

3

OPERATION: CONFIGURATION MODE

3.3 Available Options The Controller may be ordered with one of the three following options: 1) Analog Output: This option provides additional flexibility to transmit the equivalent value of process variable to other devices using a 4 to 20 mA current loop or 0-10 V signal. 2) Communication Option: This option makes the controller a very powerful instrument providing the user with even greater capability since all the parameters can be transmitted via a personal computer. 3) Remote Setpoint: One of the three already stored setpoints can be activated.

60

Page 69 read from a scan by OCR; it may hold reading errors

OPERATION: CONFIGURATION MoDE

Analog Output Option

MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MIN¥ PRESS MAX& PRESS ENTER CURRENT. Analog Output J __¥- - - YES Type L__ VOLTAGE. ANALOG OUT

Output | Scale&Offset | RDG1| OUT1| RDG2| oUT2 >

Figure 3.9 Flowchart for Analog Output Option

61

Page 70

part

3

OPERATION: CONFIGURATION MODE

Analog Output Option cont. Display

Action

ANLG 0UT

Press MENU Press ENTER

NoT _ INST ANLG VOLT

62

Press MENU

Press ENTER Press MAX Press ENTER

Response 1) Press MENU, if necessary, until the "A N L G O UT " prompt appears. 2) Display advances to "Analog Type" submenu.

IF THE ANALOG OUTPUT OPTION IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NoT_INST" Press MENU, if you receive the "Not Installed" message and advance to the "Communication" submenu. ANALOG RETRANSMISSION TYPE SUBMENU: 3) Display flashes "v0lt" or "CUrr". 4) Scroll through the available selections: Volt or Current. 5) Display flashes "stored" message and advances to "Reading 1" of the Output Reading submenu.