Manual · Newport Electronics, Inc.
MICRO-INFINITY ICN77000 Series Controller Operator's Manual
Manual108 pagesPDF 2.2 MB
Operator's manual for the Newport MICRO-INFINITY ICN77000 Series 1/16 DIN process controller: ordering, setup, configuration and specifications.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Newport Electronics operator's manual for the MICRO-INFINITY ICN77000 Series, a dual display process controller in a 1/16 DIN case for thermocouple, RTD, voltage or current inputs. It opens with the model number ordering guide (case type, control outputs, options), then covers safety, mounting, the front and rear panels, DIP switch settings and input wiring, configuration mode menus for set points, input type, alarms, loop break alarm, outputs and ramp and soak, the analog output, communication and remote setpoint options, and specifications.
Its parts
- Introduction
- Setup
- Operation: Configuration Mode
- Specifications
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
This is the operator's manual for the Newport Electronics MICRO-INFINITY ICN77000 Series Controller, a 1/16 DIN process controller with two displays for thermocouple, RTD, voltage or current inputs. It covers the whole ICN77000 series, not only the ICN77530. It shows how to read the order code, mount and wire the controller, set its DIP switch, use the front panel menus, and set up ramp and soak.
- What it is
- Process controller with dual displays for thermocouple, RTD, voltage or current inputs in a 1/16 DIN case p. 3
- Inputs
- Thermocouple, RTD, 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc, 0 to 20 mA p. 99
- Display
- Dual 4-digit, 7-segment LED, 9.2 mm (0.36 in); red process value, green setpoint; 7.6 mm (0.3 in) on NEMA 12 units p. 99
- Power
- 90-240 Vac, 50-400 Hz; 4 watts p. 100
- Control relays
- 5 A @ 120 Vac, 3 A @ 240 Vac; output 1 SPDT, output 2 SPST p. 99
- Alarm output
- SPST relay, 3 A @ 120 Vac, 3 A @ 240 Vac; high/low, latching or non-latching, process or deviation p. 100
- Control modes
- Preset tune, adaptive tune, auto-tune, PID, PI, PD, on-off; reverse (heat) or direct (cool) action p. 3, 99
- Communications
- Optional RS-232 or RS-485, 300 to 19.2k baud; RS-485 addressable 0 to 199; screw terminals p. 3, 100
- Analog output
- Optional isolated 0 to 10 Vdc or 0 to 20 mA, programmable p. 3, 100
- Remote setpoint
- Option: up to 3 setpoints stored in memory, selected by contact closure p. 99
- Size and weight
- ICN77500 Series: 53 H x 53 W x 123.3 mm D; 45 mm square 1/16 DIN cutout; 227 g (0.5 lb) p. 100
- Operating conditions
- 0 to 55°C (32 to 131°F), 90% RH non-condensing p. 100
- Power fuse
- External 100 mA/250 V slow-blow (UL 248-14) or time-lag (IEC 127-3) fuse required p. 100
- Reading rate
- 3 samples per second; 30 min warm-up to rated accuracy p. 99
What this manual walks you through
- Reading the order code of an ICN77000 controller p. 3
- Mounting the controller in a square or round panel cutout p. 12, 13, 14
- Setting the DIP switch for the input type p. 18, 19
- Wiring power and choosing fuses p. 20
- Wiring a thermocouple input p. 21
- Wiring a 2, 3 or 4-wire RTD p. 22
- Wiring process current and voltage inputs p. 23
- Using the front panel buttons and indicators p. 15, 25
- Setting up ramp and soak p. 66
- Hooking up an external solid state relay p. 102
Good to know
- The controller has no power switch; the building wiring needs an external switch or circuit breaker as the disconnect. p. 9
- Options cannot be added in the field; the controller must be ordered fully configured. p. 3
- Changing any menu setting other than the setpoints and alarms resets the controller before it returns to Run mode. p. 25
- Not designed for, and not to be used in, patient connected applications. p. 2
- The ramp time must be at least twice the time the process takes to reach the setpoint with output 1 fully on. p. 66
Questions this manual answers
What does the model number ICN77530 mean?
In the ICN77000 order code, 5 is the NEMA 4 bezel case for a 1/16 DIN cutout, 3 is a relay for control output 1, and 0 means no second control output. p. 3
What power supply does the ICN77000 controller need?
90-240 Vac at 50-400 Hz, drawing 4 watts, with an external 100 mA/250 V slow-blow or time-lag fuse. p. 100
How do I quickly turn off all outputs on the controller?
In Run mode press ENTER twice to go to Standby, which disables all outputs and alarms; press ENTER once more to resume. p. 11
Can I add RS-485 communications to my controller later?
No. The manual says the controller must be ordered completely configured and options are not field installable. p. 3
What panel cutout does the round mount version need?
A 44.5 mm (1.75 in) round hole; the square mount versions fit a 45 mm square 1/16 DIN cutout. p. 100