Page 1 of MICRO-INFINITY ICN77000 Series Controller Operator's Manual

Manual · Newport Electronics, Inc.

MICRO-INFINITY ICN77000 Series Controller Operator's Manual

Manual108 pagesPDF 2.2 MB

Operator's manual for the Newport MICRO-INFINITY ICN77000 Series 1/16 DIN process controller: ordering, setup, configuration and specifications.

Download the PDF2.2 MB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Newport Electronics operator's manual for the MICRO-INFINITY ICN77000 Series, a dual display process controller in a 1/16 DIN case for thermocouple, RTD, voltage or current inputs. It opens with the model number ordering guide (case type, control outputs, options), then covers safety, mounting, the front and rear panels, DIP switch settings and input wiring, configuration mode menus for set points, input type, alarms, loop break alarm, outputs and ramp and soak, the analog output, communication and remote setpoint options, and specifications.

Its parts

  1. Introduction
  2. Setup
  3. Operation: Configuration Mode
  4. Specifications

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This is the operator's manual for the Newport Electronics MICRO-INFINITY ICN77000 Series Controller, a 1/16 DIN process controller with two displays for thermocouple, RTD, voltage or current inputs. It covers the whole ICN77000 series, not only the ICN77530. It shows how to read the order code, mount and wire the controller, set its DIP switch, use the front panel menus, and set up ramp and soak.

Read for this summary: pages 1 to 3, 5 to 7, 9 to 25, 64 to 66 and 99 to 103 of 108.

What it is
Process controller with dual displays for thermocouple, RTD, voltage or current inputs in a 1/16 DIN case p. 3
Inputs
Thermocouple, RTD, 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc, 0 to 20 mA p. 99
Display
Dual 4-digit, 7-segment LED, 9.2 mm (0.36 in); red process value, green setpoint; 7.6 mm (0.3 in) on NEMA 12 units p. 99
Power
90-240 Vac, 50-400 Hz; 4 watts p. 100
Control relays
5 A @ 120 Vac, 3 A @ 240 Vac; output 1 SPDT, output 2 SPST p. 99
Alarm output
SPST relay, 3 A @ 120 Vac, 3 A @ 240 Vac; high/low, latching or non-latching, process or deviation p. 100
Control modes
Preset tune, adaptive tune, auto-tune, PID, PI, PD, on-off; reverse (heat) or direct (cool) action p. 3, 99
Communications
Optional RS-232 or RS-485, 300 to 19.2k baud; RS-485 addressable 0 to 199; screw terminals p. 3, 100
Analog output
Optional isolated 0 to 10 Vdc or 0 to 20 mA, programmable p. 3, 100
Remote setpoint
Option: up to 3 setpoints stored in memory, selected by contact closure p. 99
Size and weight
ICN77500 Series: 53 H x 53 W x 123.3 mm D; 45 mm square 1/16 DIN cutout; 227 g (0.5 lb) p. 100
Operating conditions
0 to 55°C (32 to 131°F), 90% RH non-condensing p. 100
Power fuse
External 100 mA/250 V slow-blow (UL 248-14) or time-lag (IEC 127-3) fuse required p. 100
Reading rate
3 samples per second; 30 min warm-up to rated accuracy p. 99

What this manual walks you through

  • Reading the order code of an ICN77000 controller p. 3
  • Mounting the controller in a square or round panel cutout p. 12, 13, 14
  • Setting the DIP switch for the input type p. 18, 19
  • Wiring power and choosing fuses p. 20
  • Wiring a thermocouple input p. 21
  • Wiring a 2, 3 or 4-wire RTD p. 22
  • Wiring process current and voltage inputs p. 23
  • Using the front panel buttons and indicators p. 15, 25
  • Setting up ramp and soak p. 66
  • Hooking up an external solid state relay p. 102

Good to know

  • The controller has no power switch; the building wiring needs an external switch or circuit breaker as the disconnect. p. 9
  • Options cannot be added in the field; the controller must be ordered fully configured. p. 3
  • Changing any menu setting other than the setpoints and alarms resets the controller before it returns to Run mode. p. 25
  • Not designed for, and not to be used in, patient connected applications. p. 2
  • The ramp time must be at least twice the time the process takes to reach the setpoint with output 1 fully on. p. 66

Questions this manual answers

What does the model number ICN77530 mean?

In the ICN77000 order code, 5 is the NEMA 4 bezel case for a 1/16 DIN cutout, 3 is a relay for control output 1, and 0 means no second control output. p. 3

What power supply does the ICN77000 controller need?

90-240 Vac at 50-400 Hz, drawing 4 watts, with an external 100 mA/250 V slow-blow or time-lag fuse. p. 100

How do I quickly turn off all outputs on the controller?

In Run mode press ENTER twice to go to Standby, which disables all outputs and alarms; press ENTER once more to resume. p. 11

Can I add RS-485 communications to my controller later?

No. The manual says the controller must be ordered completely configured and options are not field installable. p. 3

What panel cutout does the round mount version need?

A 44.5 mm (1.75 in) round hole; the square mount versions fit a 45 mm square 1/16 DIN cutout. p. 100

The whole text · 11 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 108101-108

The file

Size and text

PublisherNEWPORT Electronics, Inc.
Pages108
PDF2.2 MB
TextText from the PDF itself; 10 pages are scans, read by OCR, which may hold reading errors.