The text of a manual · part 5 of 11
MICRO-INFINITY ICN77000 Series Controller Operator's Manual, pages 41 to 50
Pages 41 to 50 of 108
The original document is the PDF (2.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Newport Electronics, Inc. ICN77530
Page 41
part
OPERATION: CONFIGURATION MODE
3
Alarm 1 Display
Action
ALAR 1
Press MENU Press ENTER
ALR. 1 ENBL
Press MAX Press ENTER
ALARM 1 ENABLE/DISABLE SUBMENU: 3) Display flashes previous selection. Press MAX until "Enbl" displays to use Alarm 1. 4) Display flashes "strd" message only if it was changed, otherwise press MENU to advance to "Control Type" submenu.
ALR. 1 ABSo
Press MAX Press ENTER
CONTROL TYPE SUBMENU: 5) Display flashes previous selection. Press MAX to "ABS o " or "Dev." 6) Display flashes "strd" message only if it was changed, otherwise press MENU to advance to "Alarm 1 Latch" submenu.
Note ☞
Response 1) Press MENU, if necessary, until "Alar 1" prompt appears. 2) Display advances to "Alar.1 enbl" or "dsbl" submenu.
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the process being monitored does not change often, then "Absolute" Mode is recommended. Deviation Mode allows changes to Setpoint 1 to be made automatically to Alarm 1. Deviation Mode is typically the ideal mode if the process temperature changes often. In Deviation Mode, set Alarm 1 a certain number of degrees or counts away from Setpoint 1, this relation remains fixed even if Setpoint 1 is changed. 33
Page 42
part
3
OPERATION: CONFIGURATION MODE
Alarm 1 cont. Display
Action
Response
ALR. 1 LTCH
Press MAX Press ENTER
ALARM LATCHED OR UNLATCHED SUBMENU: 7) Display flashes previous selection. Press MAX to Latched or Unlatched. 8) Display flashes "strd" message and advances to "Contact Closure" submenu.
ALR. 1 N. o .
Press MAX
ALR. 1 ABoV
Press ENTER
Press MAX
Press ENTER
CONTACT CLOSURE SUBMENU: 9) Display flashes previous selection. Press MAX to Normally Closed (n.c.) or Normally Open (n.o.). 10) Display flashes "strd" message only if it was changed, otherwise press MENU to advance to "Alarm 1 Setup” submenu. ALARM 1 SETUP SUBMENU: 13) Display flashes previous selection. Press MAX to scroll through the available selections: Above, Below, HI/Low and Band (Band is active if "Deviation" was selected). 14) Display flashes "strd" message only if it was changed, otherwise press MENU to advance to "Alarm 1 Low Value" submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the Alarm Hi Value. (Lo value ignored) Below: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value. (Hi value ignored) Hi/Low: Alarm 1 condition triggered when the process variable is less than the Alarm Low Value or above the Hi Value. Band: Alarm 1 condition triggered when the process variable is above or below the "Band" set around Setpoint 1. Band equals Hi Value (Lo Value ignored). A "Band" is set around the Setpoint 1 by the controller only in the "Deviation" Mode. 34
Page 43
part
OPERATION: CONFIGURATION MODE
3
Alarm 1 cont. Display
Action
A. P . o N ENBL
Press MAX
Press ENTER
Response ALARMS ENABLE/DISABLE AT POWER ON: 11) Display flashes previous selection. Press MAX to enable or disable. If the alarm is enabled at Power On, the alarm will be active right after reset. If the alarm is Note ☞ disabled at Power On, the alarm will become enabled when the process value enters the non alarm area. The alarm is not active while the Process value is approaching Setpoint 1. 12) Display flashes "Stored" message only if it was changed, otherwise press MENU to advance to the "Alarm 1 Low Value" submenu.
AL1. L 0762
ALARM 1 LOW VALUE SUBMENU: Press MAX & MIN 15) Display flashes 1st digit of previous value. Use MAX and MIN to enter new value. Press ENTER 16) Display flashes "strd" message, only if it was changed, otherwise press MENU to advance to "Alarm 1 HI Value" submenu.
AL1. H 2722
Press MAX & MIN Press ENTER
Note ☞
ALARM 1 HI VALUE SUBMENU: 17) Display flashes 1st digit of previous value. Use MAX and MIN to enter new value. 18) Display flashes "strd" message only if it was changed, otherwise press MENU to advances to "Alarm 2" submenu.
Latched Mode: Relay remains "latched" until reset. To reset a latched alarm, put unit into “Stand-by” Mode by pressing the ENTER button twice. Then, enter back into Run Mode by pressing the ENTER button a third time and alarm will be de-energized. Unlatched Mode: Relay remains latched only as long as the alarm condition is true. Normally Closed:"Fail Safe" Mode, relay is energized under "normal" conditions and becomes de-energized during alarm or power failure. Normally Open: If this feature is selected, then the relay is "energized" only when an alarm condition occurs.
35
Page 44
part
3
OPERATION: CONFIGURATION MODE
Alarm 2 Display
Action
ALAR 2
Press MENU Press ENTER
NoT _ INST
Press MENU
IF ALARM 2 IS NOT INSTALLED, THE CONTROLLER WILL SHOW "NOT INSTALLED" Press MENU, if you receive the "not installed" message and advance to the "Loop Break" menu.
ALR. 2 ENBL
Press MAX Press ENTER
ALARM 2 ENABLE/DISABLE SUBMENU: 3) Display flashes previous selection. Press MAX until "Enbl" displays to use Alarm 2. 4) Display flashes "strd" message only if it was changed, otherwise press MENU to advance to "Control Type" submenu.
Note ☞
36
Response 1) Press MENU, if necessary, until "Alar 2" display appears. 2) Display advances to "Alarm 2 Enable/Disable" submenu.
The remaining Alarm 2 is identical to Alarm 1 i.e. previous two pages.
Page 45
OPERATION: CONFIGURATION MoDE
MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MINV PRESS MAX& PRESS ENTER DISABLE LOOP | on BREAK l ENABLE "WHEN FLASHING" MAX FOR CHOICE LOOP LOOP BREAK VALUE DISPLAY OFF SET DISABLE ID Option | l ENABLE
Figure 3.5 Flowchart for Loop Break
37
Page 46
part
3
OPERATION: CONFIGURATION MODE
Loop Break Alarm Display
Action
L00P BR. A L
Press MENU Press ENTER
1) Press MENU, if necessary, until the "Loop Break" prompt appears. 2) Display advances to "Loop Break Enable/Disable" submenu.
L. B . A L ENBL
Press ENTER Press MAX Press ENTER
LOOP BREAK ENABLE/DISABLE SUBMENU: 3) Display flashes "enbl" or "dsbl". 4) Scroll through the available selections: Enable (enbl) or Disable (dsbl). 5) Display flashes "strd" message and advances to "Loop Value" menu.
Note ☞
38
Response
Loop Break is an additional safety feature intended to monitor the rate of change of the process value, while approaching the SPI. It is strictly intended as an additional warning system, therefore its use is entirely optional. An active Loop Break will cause the setpoint digits to blink in a rotating pattern. If the process value reaches the setpoint the blinking will stop and Loop brA1 is completed successfully, otherwise Loop brA1 will flash and will activate Alr1.
Page 47
part
OPERATION: CONFIGURATION MODE
3
Loop Break Alarm cont. Display
Action
Response
L. B . A L 00. 1 7
Press ENTER Press MAX & MIN Press ENTER
LOOP BREAK ALARM VALUE SUBMENU: 6) Display flashes 1st digit of previous loop value. 7) Press MAX and MIN buttons to enter a new "Loop Value". 8) Display flashes "strd" message and advances to "CJ Temperature Adjust" Menu.
T. A DJ 006. 7
Press ENTER Press MAX & MIN Press ENTER
TEMPERATURE ADJUST SUBMENU: 9) Display flashes 1st digit of previous temperature adjust value. 10) Press MAX and MIN buttons to enter a new "Temperature Adjust" value. 11) Display flashes "strd" message and advances to "ID Option" submenu.
Note ☞
Loop Break Alarm Value allows the user to determine the time interval in MM:SS (from zero to 99 minutes and 59 seconds) that the process value changes 10 counts or if the input type is either RTD or Thermocouple, the value would be 4°Fahrenheit or 2°Celsius. At the specified time interval, if the process value change is less than the stated rate flashing, "L.B.AL" will be displayed, the output "1" will be de-energized, and Alarm 1 energized. Loop Break Alarm will be disabled when the process value (PV) enters the control band. Display Offset Adjust allows the user to fine tune a minor error of the transducer, however some applications may require a large offset adjust. (Displayed Process Value = Measured Process Value ± t.A.dJ). t.A.dJ is adjustable between -1999 to 9999.
39
Page 48
part
3
OPERATION: CONFIGURATION MODE
Loop Break Alarm cont. Display
ID DSBL Note ☞
40
Action
Response
Press MAX Press ENTER
ID CODE OPTION SUBMENU 12) Display flashes current status of ID Option, enabled or disabled. 13) Press MAX button to select between Enable and Disable. 14) Display flashes “strd” and advances to “Output 1.”
With ID Code Option disabled, the ID Number submenu is hidden. Refer to the appropriate setpoints section for setting differences.
Page 49
OPERATION: CONFIGURATION MoDE
MENU LEVEL MENU LEVEL 2 MENU LEVEL SELECT DIGIT INCR. DIGIT STORE PRESS MENU PRESS ENTER PRESS ENTER PRESS MIN¥W PRESS MAX & PRESS ENTER
| scr po ENABLE l ] Le oisaste oo ENABLE Le oisaste___t [ - ON OFF
L - pip, _ I r - Reverse] Le DIRECT DISABLE
Kees ENABLE, I Cc DISABLE:
be ENABLE I rT DISABLE
Le ENABLE, I
FACTOR Li detet«tet7 tet
Figure 3.6 Flowchart for Output 1
41
Page 50
part
3
OPERATION: CONFIGURATION MODE
Output 1 Display oUT 1 SELF DSBL Note ☞
Action Press MENU Press ENTER
Press MAX Press ENTER
Response 1) Press MENU, if necessary, until the "out 1" prompt appears. 2) Display advances to “Self” submenu. SELF SUBMENU The Self Option allows the output of the controller to be controlled manually from the front panel. 3) Display flashes the current setting of Self, enabled or disabled. 4) Press the MAX button to select between Enable and Disable. 5) If Self enable was selected, Output 1 setting is completed and the display advances to the next menu.
The output is now under the direct control of the operator and can be adjusted in the run mode, by pressing the MAX and| MIN buttons. The control value (0 - 99), now displayed in the SV window indicate, approximately in percent, the output. For example, a setting of 0050 of an analog output of 0~10 Vdc would produce roughly 5 Vdc at the output. Also, to insure smooth transition when switching to self mode, the proportional control output is left in its last value, when Self Mode is activated for the first time. 6) Display advances to the “Minimum/Percent Low” submenu, if Self is disabled. MINIMUM/PERCENT LOW SUBMENU Specify in percent, the minimum value (0000) for control output. If the output is analog, then the minimum voltage or current, in percent, is specified. If the output is time proportional, then the minimum duty-cycle, in percent, is specified.
% % L0
0000 42
Press MIN & MAX Press ENTER
7) Display shows “% % L 0 ”, and flashes the 10s digit of the current “Percent Low” setting. 8) Use MAX & MIN buttons to enter a new value for “Percent Low”. 9) Press ENTER to store the current setting and to advance to Maximum/Percent High.